Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

Module XPSAK - Emergency Stop - 110 V AC.

Schneider
SKU
SE_XPSAK361144
Model
XPSAK361144

Obsolete

Short description of XPSAK361144

Safety Modules
Obsolete
*All information are subjected to changes without prior notice.
range of product : Preventa Safety automation
-  product or component type : Preventa safety module
-  safety module name : XPSAK
-  safety module application : For emergency stop, switch, sensing mat/edges or safety light curtain monitoring
-  function of module : Monitoring of electro
- sensitive protection equipment (ESPE)Monitoring of a movable guard associated with 2 switches and automatic startMonitoring of a movable guardMultiple emergency stop monitoring 2-channel wiringEmergency stop with 2 NC contacts monitoring 2-channel wiringSensing mat and edges monitoringProximity sensor monitoringEmergency stop monitoring 1-channel wiring
-  safety level : Can reach PL e/category 4 conforming to EN/ISO 13849-1Can reach SILCL 3 conforming to EN/IEC 62061
-  safety reliability data : DC > 99 % conforming to EN/ISO 13849-1MTTFd = 154.5 years conforming to EN/ISO 13849-1PFHd = 7.39E
- 9 1/h conforming to EN/IEC 62061
-  type of start : Configurable
-  connections
-  terminals : Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
-  output type : Relay instantaneous opening, 3 NO circuit(s), volt
- free
-  number of additional circuits : 1 NC + 4 solid state outputs
-  [Us] rated supply voltage : 110 V AC
-  15...10 %24 V DC-15...10 %
MAIN SPECIFICATIONS
Analogue Input Number110 V AC - 15...10 %
24 V DC - 15...10 %
Breaking Capacity1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
180 VA holding AC-15 C300 relay output
1800 VA inrush AC-15 C300 relay output
Continuous Powercan reach PL e/category 4 conforming to EN/ISO 13849-1
can reach SILCL 3 conforming to EN/IEC 62061
Product Or Component TypePreventa safety module
Range Of ProductPreventa Safety automation
[Uc] Control Circuit Voltage24 V DC
Function Of Moduleemergency stop monitoring 1-channel wiring
emergency stop with 2 NC contacts monitoring 2-channel wiring
monitoring of a movable guard
monitoring of a movable guard associated with 2 switches and automatic start
monitoring of electro-sensitive protection equipment (ESPE)
multiple emergency stop monitoring 2-channel wiring
proximity sensor monitoring
sensing mat and edges monitoring
Mounting Support35 mm symmetrical DIN rail
Number Of Additional Circuits1 NC + 4 solid state outputs
Range NamePreventa XPS
Safety Module Applicationfor emergency stop, switch, sensing mat/edges or safety light curtain monitoring
Safety Module NameXPSAK
Type Of Startconfigurable
COMPLEMENTARY
Interlocked Device1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
180 VA holding AC-15 C300 relay output
1800 VA inrush AC-15 C300 relay output
Product Namerelay instantaneous opening, 3 NO circuit(s), volt-free
Associated Fuse Rating4 A gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
6 A fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Connections - Terminalscaptive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid with cable end, with double bezel
captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid with cable end, with double bezel
captive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
Current Consumption30 mA at 24 V AC on power supply
Input Protection Typeinternal, electronic
Local Signalling4 LEDs
Maximum Line Resistance28 Ohm
Maximum Power Consumption In VA6 VA AC
Maximum Response Time On Input Open40 ms
Minimum Output Current10 mA for relay output
Minimum Output Voltage17 V for relay output
Net Weight0.4 kg
Output Thermal Current6 A per relay for relay output
Output Typerelay instantaneous opening, 3 NO circuit(s), volt-free
Safety Reliability DataDC > 99 % conforming to EN/ISO 13849-1
MTTFd = 154.5 years conforming to EN/ISO 13849-1
PFHd = 7.39E-9 1/h conforming to EN/IEC 62061
Supply Frequency50/60 Hz
Synchronisation Time Between Inputs2 or 4 s depending of wiring (automatic start)
unlimited (manual start)
[Ith] Conventional Free Air Thermal Current18 A
[Uimp] Rated Impulse Withstand Voltage4 kV overvoltage category III conforming to DIN VDE 0110 part 1
4 kV overvoltage category III conforming to IEC 60947-5-1
[Ui] Rated Insulation Voltage300 V (pollution degree 2) conforming to DIN VDE 0110 part 1
300 V (pollution degree 2) conforming to IEC 60947-5-1
ENVIRONMENT
Safety Levelcan reach PL e/category 4 conforming to EN/ISO 13849-1
can reach SILCL 3 conforming to EN/IEC 62061
Ambient Air Temperature For Operation-10-55 °C
Ambient Air Temperature For Storage-25-85 °C
IP Degree Of ProtectionIP20 (terminals) conforming to EN/IEC 60529
IP40 (enclosure) conforming to EN/IEC 60529
Product CertificationsCSA
TÜV
UL
StandardsEN 1088/ISO 14119
EN/IEC 60204-1
EN/IEC 60947-5-1
EN/ISO 13850
OTHER
Poles DescriptionPreventa safety module
[Us] Rated Supply Voltage110 V AC - 15...10 %
24 V DC - 15...10 %