Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

Module XPSAC - Emergency Stop - 115 V AC.

Schneider
SKU
SE_XPSAC3421
Model
XPSAC3421
SGD $436.48

Short description of XPSAC3421

Safety Modules
Country of Origin
Indonesia
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 4 To 6 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
range of product : Preventa Safety automation
-  product or component type : Preventa safety module
-  safety module name : XPSAC
-  safety module application : For emergency stop and switch monitoring
-  function of module : Switch monitoringEmergency stop
-  safety level : Can reach PL e/category 4 conforming to EN/ISO 13849-1Can reach SILCL 3 conforming to EN/IEC 62061
-  safety reliability data : MTTFd = 210.4 years conforming to EN/ISO 13849-1DC > 99 % conforming to EN/ISO 13849-1PFHd = 3.56E
- 9 1/h conforming to EN/IEC 62061
-  type of start : Unmonitored
-  connections
-  terminals : Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
-  output type : Relay instantaneous opening, 3 NO circuit(s), volt
- free
-  number of additional circuits : 1 solid state output
-  [Us] rated supply voltage : 115 V AC
-  15...15 %
MAIN SPECIFICATIONS
Analogue Input Number115 V AC - 15...15 %
Breaking Capacity1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
180 VA holding AC-15 C300 relay output
1800 VA inrush AC-15 C300 relay output
Continuous Powercan reach PL e/category 4 conforming to EN/ISO 13849-1
can reach SILCL 3 conforming to EN/IEC 62061
Product Or Component TypePreventa safety module
Range Of ProductPreventa Safety automation
[Uc] Control Circuit Voltage115 V
Function Of Moduleemergency stop
switch monitoring
Mounting Support35 mm symmetrical DIN rail
Number Of Additional Circuits1 solid state output
Range NamePreventa XPS
Safety Module Applicationfor emergency stop and switch monitoring
Safety Module NameXPSAC
Type Of Startunmonitored
COMPLEMENTARY
Interlocked Device1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
180 VA holding AC-15 C300 relay output
1800 VA inrush AC-15 C300 relay output
Product Namerelay instantaneous opening, 3 NO circuit(s), volt-free
Associated Fuse Rating4 A gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
6 A fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Connections - Terminalscaptive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid with cable end, with double bezel
captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid with cable end, with double bezel
captive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezel
captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
Current Consumption60 mA at 115 V AC on power supply
Local Signalling2 LEDs
Maximum Power Consumption In VA7 VA AC
Maximum Response Time On Input Open100 ms
Minimum Output Current10 mA for relay output
Minimum Output Voltage16 V for relay output
Net Weight0.21 kg
Output Thermal Current6 A per relay for relay output
Output Typerelay instantaneous opening, 3 NO circuit(s), volt-free
Safety Reliability DataDC > 99 % conforming to EN/ISO 13849-1
MTTFd = 210.4 years conforming to EN/ISO 13849-1
PFHd = 3.56E-9 1/h conforming to EN/IEC 62061
Supply Frequency50/60 Hz
[Ith] Conventional Free Air Thermal Current10.5 A
[Uimp] Rated Impulse Withstand Voltage4 kV overvoltage category III conforming to DIN VDE 0110 part 1
4 kV overvoltage category III conforming to IEC 60947-5-1
[Ui] Rated Insulation Voltage300 V (pollution degree 2) conforming to DIN VDE 0110 part 1
300 V (pollution degree 2) conforming to IEC 60947-5-1
ENVIRONMENT
Safety Levelcan reach PL e/category 4 conforming to EN/ISO 13849-1
can reach SILCL 3 conforming to EN/IEC 62061
Ambient Air Temperature For Operation-10-55 °C
Ambient Air Temperature For Storage-25-85 °C
IP Degree Of ProtectionIP20 (terminals) conforming to EN/IEC 60529
IP40 (enclosure) conforming to EN/IEC 60529
Product CertificationsCSA
TÜV
UL
StandardsEN 1088/ISO 14119
EN 60204-1
EN/IEC 60947-5-1
EN/ISO 13850
OTHER
Poles DescriptionPreventa safety module
[Us] Rated Supply Voltage115 V AC - 15...15 %
Write Your Own Review
You're reviewing:Module XPSAC - Emergency Stop - 115 V AC.
Your Rating