RMTJ40BD - Harmony Analog, Converter for Thermocouples, Temperature Transmitter, 0...150 °C/32...302 °F.

Schneider
SKU
SE_RMTJ40BD
Model
RMTJ40BD

Obsolete

All prices inclusive of GST

Short description of RMTJ40BD

RMTJ40BD. Analog Converters
Obsolete
range of product : Harmony Analog
-  product or component type : Converter for thermocouples
-  analogue input type : Thermocouple 0...150 °C/32...302 °F thermocouple J conforming to IEC 60584
-  analogue output type : Current 0...20 mA
MAIN SPECIFICATIONS
Analog/digital Conversioncurrent 0...20 mA <= 500 Ohm
current 4...20 mA <= 500 Ohm
voltage 0...10 V >= 100 kOhm
Analogue Input Number24 V DC +/- 20 %, non isolated
Product Or Component Typeconverter for thermocouples
Range Of ProductHarmony Analog
Range NameHarmony Analog
COMPLEMENTARY
Analogue Input Typethermocouple 0...150 °C/32...302 °F thermocouple J conforming to IEC 60584
Analogue Output Typecurrent 0...20 mA <= 500 Ohm
current 4...20 mA <= 500 Ohm
voltage 0...10 V >= 100 kOhm
Output Voltagethermocouple 0...150 °C/32...302 °F thermocouple J conforming to IEC 60584
Analogue Output Current-30-0 mA when no input or input wire broken
Analogue Output Voltage11...15 V when no input or input wire broken
-15...-11 V when no input or input wire broken
Clamping Connection Capacity1 x 2.5 mm²
2 x 1.5 mm²
Cold Junction Compensationbuilt-in, measurement: between 0 and 60 °C
Current Consumption<= 60 mA for current output
Fixing Modeby screws (mounting plate)
clip-on (35 mm symmetrical DIN rail)
Local SignallingLED (green) for power ON
MarkingCE
Measurement Error+/- 1 % of full scale at 20 °C
+/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m)
Net Weight0.12 kg
Protection Typeovervoltage protection on output (+/- 30 V)
reverse polarity protection on output
short-circuit protection on output
Repeat Accuracy+/- 0.25 % full scale at 20 °C
+/- 0.8 % full scale at 60 °C
Safety Reliability DataB10d = 45447
MTTFd = 49.2 years
Surge Withstand0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5
Temperature Coefficient200 ppm/°C
Tightening Torque0.6-1.1 N.m
[Ui] Rated Insulation Voltage2 kV
ENVIRONMENT
Ambient Air Temperature For Operation0-50 °C mounting side by side
0-60 °C 2 cm spacing
Ambient Air Temperature For Storage-40-85 °C
Disturbance Radiated/conductedCISPR 11
CISPR 22 group 1 - class B
Fire Resistance850 °C conforming to IEC 60695-2-1
850 °C conforming to UL
IP Degree Of ProtectionIP20 (terminal block)
IP50 (housing)
Pollution Degree2 conforming to IEC 60664-1
Product CertificationsCSA
GL
UL
Resistance To Electrostatic Discharge6 kV (in contact) conforming to IEC 61000-4-2 level 3
8 kV (in air) conforming to IEC 61000-4-2 level 3
Resistance To Fast Transients1 kV (on input-output) conforming to IEC 61000-4-4
2 kV (on power supply) conforming to IEC 61000-4-4
Shock Resistance50 gn for 11 ms conforming to IEC 60068-2-27
StandardsIEC 60584-1
IEC 60947-1
Vibration Resistance5 gn (f= 10-100 Hz) conforming to IEC 60068-2-6
OTHER
Poles Descriptionconverter for thermocouples
[Us] Rated Supply Voltage24 V DC +/- 20 %, non isolated