RMTJ40BD - Harmony Analog, Converter for Thermocouples, Temperature Transmitter, 0...150 °C/32...302 °F.
Schneider
SKU
SE_RMTJ40BD
Model
RMTJ40BD
Obsolete
Short description of RMTJ40BD
RMTJ40BD. Analog Converters
Obsolete
range of product : Harmony Analog
-  product or component type : Converter for thermocouples
-  analogue input type : Thermocouple 0...150 °C/32...302 °F thermocouple J conforming to IEC 60584
-  analogue output type : Current 0...20 mA
-  product or component type : Converter for thermocouples
-  analogue input type : Thermocouple 0...150 °C/32...302 °F thermocouple J conforming to IEC 60584
-  analogue output type : Current 0...20 mA
MAIN SPECIFICATIONS | |
---|---|
Analog/digital Conversion | current 0...20 mA <= 500 Ohm current 4...20 mA <= 500 Ohm voltage 0...10 V >= 100 kOhm |
Analogue Input Number | 24 V DC +/- 20 %, non isolated |
Product Or Component Type | converter for thermocouples |
Range Of Product | Harmony Analog |
Range Name | Harmony Analog |
COMPLEMENTARY | |
Analogue Input Type | thermocouple 0...150 °C/32...302 °F thermocouple J conforming to IEC 60584 |
Analogue Output Type | current 0...20 mA <= 500 Ohm current 4...20 mA <= 500 Ohm voltage 0...10 V >= 100 kOhm |
Output Voltage | thermocouple 0...150 °C/32...302 °F thermocouple J conforming to IEC 60584 |
Analogue Output Current | -30-0 mA when no input or input wire broken |
Analogue Output Voltage | 11...15 V when no input or input wire broken -15...-11 V when no input or input wire broken |
Clamping Connection Capacity | 1 x 2.5 mm² 2 x 1.5 mm² |
Cold Junction Compensation | built-in, measurement: between 0 and 60 °C |
Current Consumption | <= 60 mA for current output |
Fixing Mode | by screws (mounting plate) clip-on (35 mm symmetrical DIN rail) |
Local Signalling | LED (green) for power ON |
Marking | CE |
Measurement Error | +/- 1 % of full scale at 20 °C +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m) |
Net Weight | 0.12 kg |
Protection Type | overvoltage protection on output (+/- 30 V) reverse polarity protection on output short-circuit protection on output |
Repeat Accuracy | +/- 0.25 % full scale at 20 °C +/- 0.8 % full scale at 60 °C |
Safety Reliability Data | B10d = 45447 MTTFd = 49.2 years |
Surge Withstand | 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5 |
Temperature Coefficient | 200 ppm/°C |
Tightening Torque | 0.6-1.1 N.m |
[Ui] Rated Insulation Voltage | 2 kV |
ENVIRONMENT | |
Ambient Air Temperature For Operation | 0-50 °C mounting side by side 0-60 °C 2 cm spacing |
Ambient Air Temperature For Storage | -40-85 °C |
Disturbance Radiated/conducted | CISPR 11 CISPR 22 group 1 - class B |
Fire Resistance | 850 °C conforming to IEC 60695-2-1 850 °C conforming to UL |
IP Degree Of Protection | IP20 (terminal block) IP50 (housing) |
Pollution Degree | 2 conforming to IEC 60664-1 |
Product Certifications | CSA GL UL |
Resistance To Electrostatic Discharge | 6 kV (in contact) conforming to IEC 61000-4-2 level 3 8 kV (in air) conforming to IEC 61000-4-2 level 3 |
Resistance To Fast Transients | 1 kV (on input-output) conforming to IEC 61000-4-4 2 kV (on power supply) conforming to IEC 61000-4-4 |
Shock Resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
Standards | IEC 60584-1 IEC 60947-1 |
Vibration Resistance | 5 gn (f= 10-100 Hz) conforming to IEC 60068-2-6 |
OTHER | |
Poles Description | converter for thermocouples |
[Us] Rated Supply Voltage | 24 V DC +/- 20 %, non isolated |