PCSP200D5IP54 - Active Harmonic Filter - 200 A 380..480 V AC - IP54 Enclosure
Schneider
SKU
SE_PCSP200D5IP54
Model
PCSP200D5IP54
SGD $115,829.94 All prices inclusive of GST
Short description of PCSP200D5IP54
PCSP200D5IP54. AccuSine PCS+ 200A 380-480 VAC IP54
Country of Origin
India
Active harmonic filter
-  200 A 380..480 V AC
-  IP54 enclosure.
Label :  AccuSine PCS+
-  range of product :  AccuSine
-  range :  AccuSine
-  product name :  AccuSine PCS+
-  product or component type :  active harmonic filter
-  Range Presentation : 
-  A complete solution for harmonic filtering that meets every harmonic standard around the world.
-  Can be operated as a displacement power factor correction and load balancing device independent of or in conjunction with harmonic mitigation.
Technical Data
Standard RMS output current ratings
-  60 A, 120 A, 200 A, 300 A
-  380 V AC to 480 V AC
-  47 A, 94 A, 157 A, 235 A
-  480-600 V AC
-  40 A, 80 A, 133 A , 200 A
-  600-690 V AC
Nominal voltage
-  380-480 V AC; +10%/-15%
-  480-600 V AC; +10%/-15%
-  600-690 V AC; +10%/-15%
Up to 15kV with custom transformers
Nominal frequency
-  50/60 Hz, ±3 Hz auto sensing
Number of phases
-  3-phase, with or without neutral
Spectrum cancellation
-  2nd to 51st, discrete; fully selectable per harmonic order (amplitude and on/off)
Harmonic Attenuation
-  Closed Loop :  3 % THD(i); max 20 : 1 THD(i) reduction with load harmonic current above 50 % of AccuSine PCS+ rating
-  Open Loop :  5 % TDD
-  Requires 3 % or higher inductive impedance per nonlinear load
Power factor correction
-  Optimized unity PF, Leading (capacitive) or lagging (inductive) power factor (Cos φ) to target
Mains current balancing
-  Negative sequence current injected to balance fundamental current on the mains due to load imbalance (inherently corrects displacement PF (Cos φ))
Control response time
-  25 μs
Harmonic correction time
-  2 cycles
Reactive correction time
-  1/4 cycle
Operating Temperature
-  60 A, 120 A & 200 A :  IP00, IP20, UL Type Open, & UL Type 1 configurations
- 0 °C to 45 °C
-  All others 0 °C to 40 °C
-  Derate 2 % per degree °C to 50 °C
Relative humidity
-  to 95 %, noncondensing
Operating Altitude
-  1000 m (derate 1 %/100 m above), max 4800 m
Standards compliance/ certification
-  cULus (UL508 , CSA 22.2 No. 14)
-  CE Certified, ABS, Lloyds, other local standards
Display
-  144 mm QVGA TFT 64k
- color touchscreen
-  Range Benefits :  Flexible and scalable : 
-  All types of harmonic producing loads
-  Single load, bus or global site filtering
-  Compatible with future load changes
-  Easy sizing and independent of system impedance
-  Simple selection online tool
-  Simple installation and ease of expansion
-  Flexible parallel operation modes for multi-unit installations
-  Current transformers can be installed on the incoming mains (source sense) or on the feeders to the loads (load sense) for maximum installation flexibility
-  Peace of mind : 
-  Achieves compliance with any harmonic standard anywhere around the world when sized correctly
-  Compatible with generator sources
-  off loads generators of reactive and harmonic current demands to extend life and ensure proper operation of generators
-  Compatible with UPS sources :  relieves UPS of reactive and harmonic current demands to ensure proper operation of UPS
-  Ensures energy efficiency by optimising transformer and cable capacities; reduces utility power factor penalties; and saves the cost of generation and transmission of reactive and harmonic current (non active currents)
-  Maximises up time when used for harmonic and/or power factor correction.
-  Range Application Presentation : 
-  Anywhere nonlinear loads are present :  water/wastewater facilities, HVAC systems, oil & gas platforms, petrochemical plants, port cranes, mining, pharmaceuticals, pulp & paper, automotive plants, all
- electric ships, wind mill and solar farms, steel mills, plastic extrusion plants, and more.
-  Stop voltage sags and flicker due to load current fluctuations (VAR compensation) :  Ball mills, shredders, arc welders, arc furnaces, hard to start AC motors, and more.
-  200 A 380..480 V AC
-  IP54 enclosure.
Label :  AccuSine PCS+
-  range of product :  AccuSine
-  range :  AccuSine
-  product name :  AccuSine PCS+
-  product or component type :  active harmonic filter
-  Range Presentation : 
-  A complete solution for harmonic filtering that meets every harmonic standard around the world.
-  Can be operated as a displacement power factor correction and load balancing device independent of or in conjunction with harmonic mitigation.
Technical Data
Standard RMS output current ratings
-  60 A, 120 A, 200 A, 300 A
-  380 V AC to 480 V AC
-  47 A, 94 A, 157 A, 235 A
-  480-600 V AC
-  40 A, 80 A, 133 A , 200 A
-  600-690 V AC
Nominal voltage
-  380-480 V AC; +10%/-15%
-  480-600 V AC; +10%/-15%
-  600-690 V AC; +10%/-15%
Up to 15kV with custom transformers
Nominal frequency
-  50/60 Hz, ±3 Hz auto sensing
Number of phases
-  3-phase, with or without neutral
Spectrum cancellation
-  2nd to 51st, discrete; fully selectable per harmonic order (amplitude and on/off)
Harmonic Attenuation
-  Closed Loop : 
-  Open Loop : 
-  Requires 3 % or higher inductive impedance per nonlinear load
Power factor correction
-  Optimized unity PF, Leading (capacitive) or lagging (inductive) power factor (Cos φ) to target
Mains current balancing
-  Negative sequence current injected to balance fundamental current on the mains due to load imbalance (inherently corrects displacement PF (Cos φ))
Control response time
-  25 μs
Harmonic correction time
-  2 cycles
Reactive correction time
-  1/4 cycle
Operating Temperature
-  60 A, 120 A & 200 A :  IP00, IP20, UL Type Open, & UL Type 1 configurations
- 0 °C to 45 °C
-  All others 0 °C to 40 °C
-  Derate 2 % per degree °C to 50 °C
Relative humidity
-  to 95 %, noncondensing
Operating Altitude
-  1000 m (derate 1 %/100 m above), max 4800 m
Standards compliance/ certification
-  cULus (UL508 , CSA 22.2 No. 14)
-  CE Certified, ABS, Lloyds, other local standards
Display
-  144 mm QVGA TFT 64k
- color touchscreen
-  Range Benefits :  Flexible and scalable : 
-  All types of harmonic producing loads
-  Single load, bus or global site filtering
-  Compatible with future load changes
-  Easy sizing and independent of system impedance
-  Simple selection online tool
-  Simple installation and ease of expansion
-  Flexible parallel operation modes for multi-unit installations
-  Current transformers can be installed on the incoming mains (source sense) or on the feeders to the loads (load sense) for maximum installation flexibility
-  Peace of mind : 
-  Achieves compliance with any harmonic standard anywhere around the world when sized correctly
-  Compatible with generator sources
-  off loads generators of reactive and harmonic current demands to extend life and ensure proper operation of generators
-  Compatible with UPS sources :  relieves UPS of reactive and harmonic current demands to ensure proper operation of UPS
-  Ensures energy efficiency by optimising transformer and cable capacities; reduces utility power factor penalties; and saves the cost of generation and transmission of reactive and harmonic current (non active currents)
-  Maximises up time when used for harmonic and/or power factor correction.
-  Range Application Presentation : 
-  Anywhere nonlinear loads are present :  water/wastewater facilities, HVAC systems, oil & gas platforms, petrochemical plants, port cranes, mining, pharmaceuticals, pulp & paper, automotive plants, all
- electric ships, wind mill and solar farms, steel mills, plastic extrusion plants, and more.
-  Stop voltage sags and flicker due to load current fluctuations (VAR compensation) :  Ball mills, shredders, arc welders, arc furnaces, hard to start AC motors, and more.
MAIN SPECIFICATIONS | |
---|---|
Breaking Capacity | 200 kA |
Control Type | door-interlocked with rotary handle |
Product Or Component Type | active harmonic filter |
Range Of Product | AccuSine |
[Ie] Rated Operational Current | door-interlocked with rotary handle |
EAN13 | 3606480851131 |
Function Available | rear plenum with forced ventilation for high heat flow |
Range | AccuSine |
Range Name | AccuSine PCS+ |
Reactive Power Rating | 166 kvar 480 V AC 50/60 Hz |
COMPLEMENTARY | |
Interlocked Device | 200 kA |
Product Name | AccuSine PCS+ |
Accessibility For Operation | front |
Colour | light grey (RAL 7035) |
Depth | 600 mm |
Enclosure Mounting | floor-standing |
Height | 2100 mm |
Location Of Connection | top or bottom |
Maximum Permissible Voltage | 1.1 x Un |
Mounting Location | indoor |
Net Weight | 362 kg |
Network Frequency | 50/60 Hz +/- 3 Hz auto sensing |
Network Rated Voltage | 380-480 V AC |
Neutral Protection Setting | not provided |
Nominal Output Current | 200 A |
Operating Mode | harmonic cancellation mains current balancing power factor correction |
Protection Type | circuit breaker protection |
Width | 900 mm |
Wiring Mode | 3 or 4 wires |
ENVIRONMENT | |
Ambient Air Temperature For Operation | 0-40 °C 0-50 °C maximum with current derating of 2 % per °C |
Ambient Air Temperature For Storage | -20-60 °C |
Electromagnetic Compatibility | conducted EMC, class A conforming to EN 61000-6-4 |
Environmental Characteristic | operating: 3C2 conforming to IEC 60721-3-3 operating: 3S2 conforming to IEC 60721-3-3 storage: 3C3 conforming to IEC 60721-3-3 storage: 3S3 conforming to IEC 60721-3-3 |
Impregnation Material | conformal coated |
IP Degree Of Protection | IP54 |
Operating Altitude | <= 1000 m 1 % per 100 m |
Product Certifications | ABS CE cULus RCM |
Relative Humidity | 0-95 % |
Standards | CSA C22.2 No 14 CSA C22.2 No 60947-1-07 EN 60439-1 EN 61000-6-4 UL 508 UL 60947-1 |
OTHER | |
Poles Description | 3P |
[Us] Rated Supply Voltage | AccuSine |
Write Your Own Review