Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

Anti Harmonic Detuned Reactor 12.5kvar 190Hz (3.8) 7% 50Hz 400V

Schneider
SKU
SE_LVR07125A40T
Model
LVR07125A40T
SGD $1,148.11

Short description of LVR07125A40T

DETUNED REACTOR 400V 50HZ 12,5KVAR 190HZ
Country of Origin
China
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 2 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
Anti Harmonic detuned reactor 12.5kvar 190Hz (3.8) 7% 50Hz 400V.
Label :  Detuned reactors
-  device short name :  DR
-  product or component type :  detuned reactor
-  network frequency :  50 Hz
-  reactive power rating :  12.5 kvarfor 400 V AC 50 Hz
-  network rated voltage :  400 V AC 50 Hz
-  tuning order :  3.8
-  190 Hz
-  7 %
-  50 Hz
-  Range Presentation :  Detuned reactors are specific three phase inductors dedicated to attenuating the amplification of harmonics on highly polluted networks and to protecting the different components of the installation.
They form a complete product range from 6 to 100 kvar and are available in the most common tunings like 135, 190 and 215 Hz for network voltage of 400/415V 50Hz. They must be chosen according to the capacitors they are associated with.
Technical data

-  anti-rust coating
-  thermal probe with no volt contact
-  Merlin Gerin label
-  standard :  IEC 60289, EN 60289
-  Range Benefits :  Simplicity : 

-  long service life improved by a wide range with the right sizing to fit all risk of harmonicsPeace of mind : 

-  safety operating mechanism provided by a thermal probe protection
-  product with dry type which needs minimum maintenance
-  Range Application Presentation : 

-  Power quality supplied :  limitation of pollution to the network.
MAIN SPECIFICATIONS
Product Or Component Typedetuned reactor
Device Short NameDR
EAN133606480541520
RangePowerLogic
Range NameSAH detuned reactors
Reactive Power Rating12.5 kvar for 400 V AC 50 Hz
Tuning Order3.8 - 190 Hz - 7 % - 50 Hz
Value Of Inductance2.987 mH
[Imp] Maximum Permanent Current1.2 x I1
COMPLEMENTARY
Connections - Terminalspad terminal
Depth160 mm
Dynamic Withstand Current2.2 x Isc
Electrical Insulation Classclass H
Fixing Center200 x 125 mm
Fundamental Current Rating18 A
Harmonic Current Spectrum13.6 % x I7
3.7 % x I3
38.2 % x I5
4.9 % x I11
Height220 mm
Inductance Tolerance- 5 % to 5 % per phase
Maximum Current Irms19.5 A
Net Weight10 kg
Network Frequency50 Hz
Network Rated Voltage400 V AC 50 Hz
Power Losses150 W
Type Of Coolingforced convection
Type Of Installationindoor installation
Width240 mm
[Ith] Conventional Free Air Thermal Current2 A at 250 V AC 50 Hz
[Ui] Rated Insulation Voltage1.1 kV
ENVIRONMENT
Ambient Air Temperature For Operation0-50 °C at > 1000...2000 m
0-55 °C at <= 1000 m
Average Ambient Air Temperature For Operation35 °C at > 1000...2000 m (average over 1 year)
40 °C at <= 1000 m (average over 1 year)
45 °C at > 1000...2000 m (average over 24 hours)
50 °C at <= 1000 m (average over 24 hours)
Climatic Withstandrelative humidity: 20...80 %
salt mist (400 V/50 Hz) : 250 hours
Dielectric Test Voltage4 kV 50 Hz 1 minute
IP Degree Of ProtectionIP00
Operating Altitude<= 2000 m
StandardsIEC 60068
OTHER
Poles Descriptiondetuned reactor
Write Your Own Review
You're reviewing:Anti Harmonic Detuned Reactor 12.5kvar 190Hz (3.8) 7% 50Hz 400V
Your Rating