Advanced Power Base, TeSys U, 3P, 12A/690V.

Schneider
SKU
SE_LUB120
Model
LUB120
SGD $202.72

Short description of LUB120

All-in-one motor starters up to 38 A (18.5 kW / 400 V)
Country of Origin
France
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 13 To 15 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
range : TeSys
-  product name : TeSys U
-  device short name : LUB
-  product or component type : Non reversing power base
-  device application : Motor controlMotor protection
-  poles description : 3P
-  suitability for isolation : Yes
-  [Ue] rated operational voltage : 690 V AC for power circuit
-  network frequency : 40...60 Hz
-  [Ith] conventional free air thermal current : 12 A
-  [Ie] rated operational current : 12 A at - utilisation category : AC
- 43AC
- 44AC
- 41
-  [Ics] rated service breaking capacity : 50 kA at 230 V50 kA at 440 V10 kA at 500 V4 kA at 690 V
-  auxiliary contact composition : 1 NO + 1 NC
-  auxiliary contacts type : type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1 type mirror contact (1 NC) conforming to IEC 60947-1
-  [Uc] control circuit voltage : 24 V AC 50/60 Hz24 V DC48...72 V AC 50/60 Hz48...72 V DC110...240 V AC 50/60 Hz110...220 V DC
MAIN SPECIFICATIONS
Breaking Capacity Code10 kA at 500 V
4 kA at 690 V
50 kA at 230 V
50 kA at 440 V
Control Type3P
Product Or Component Typenon reversing power base
Range Of ProductTeSys U
[Ie] Rated Operational Current12 A at <= 440 V
12 A at 500 V
9 A at 690 V
[Uc] Control Circuit Voltage110...220 V DC
110...240 V AC 50/60 Hz
24 V AC 50/60 Hz
24 V DC
48...72 V AC 50/60 Hz
48...72 V DC
[Ue] Rated Operational Voltage690 V AC for power circuit
Device Short NameLUB
RangeTeSys
Range NameTeSys U
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Suitability For Isolationyes
Utilisation CategoryAC-41
AC-43
AC-44
COMPLEMENTARY
Communication Network Type690 V AC for power circuit
Product NameTeSys U
[Ics] Rated Service Breaking Capacity10 kA at 500 V
4 kA at 690 V
50 kA at 230 V
50 kA at 440 V
Auxiliary Contact Composition1 NO + 1 NC
Auxiliary Contacts Type type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1
type mirror contact (1 NC) conforming to IEC 60947-1
Compatibility CodeLUB
Connections - Terminalscontrol circuit: without connection
power circuit: screw clamp terminals 1 cable(s) 1-10 mm² rigid
power circuit: screw clamp terminals 1 cable(s) 1-6 mm² flexible with cable end
power circuit: screw clamp terminals 1 cable(s) 2.5-10 mm² flexible without cable end
power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
power circuit: screw clamp terminals 2 cable(s) 1-6 mm² flexible with cable end
power circuit: screw clamp terminals 2 cable(s) 1-6 mm² rigid
Depth126 mm
Device Applicationmotor control
motor protection
Fixing Modeclipped (DIN rail)
screw-fixed (plate)
Height154 mm
Immunity To Microbreaks3 ms for control circuit
Maximum Operating Rate3600 cyc/h
Mechanical Durability15 Mcycles
Net Weight0.865 kg
Network Frequency40...60 Hz
Operating Time35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit
50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
75 ms closing with LUCM for control circuit
Safe Separation Of Circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N
Tightening Torquecontrol circuit: 0.8-1.2 N.m flat screwdriver 5 mm
control circuit: 0.8-1.2 N.m Philips no 1 screwdriver 5 mm
power circuit: 1.9-2.5 N.m flat screwdriver 6 mm
power circuit: 1.9-2.5 N.m Philips No 2 screwdriver 6 mm
Typical Current Consumption130 mA at 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
140 mA at 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
150 mA at 24 V DC I maximum while closing with LUCM
280 mA at 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
35 mA at 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
35 mA at 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
35 mA at 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
35 mA at 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
60 mA at 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
70 mA at 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
70 mA at 24 V DC I rms sealed with LUCM
Width45 mm
[Ith] Conventional Free Air Thermal Current12 A
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947-6-2
[Ui] Rated Insulation Voltage600 V conforming to CSA C22.2 No 60947-4-1
600 V conforming to UL 60947-4-1
690 V conforming to IEC 60947-6-2 (pollution degree 3)
ENVIRONMENT
Ambient Air Temperature For Operation-25-60 °C with LUCM
-25-70 °C with LUCA, LUCB, LUCC, LUCD
Ambient Air Temperature For Storage-40-85 °C
Fire Resistance650 °C conforming to IEC 60695-2-12
960 °C parts supporting live components conforming to IEC 60695-2-12
Heat Dissipation1.7-1.7 W for control circuit with LUCM
2-2 W for control circuit with LUCA, LUCB, LUCC, LUCD
Immunity To Radioelectric Fields10 V conforming to IEC 61000-4-6
Immunity To Voltage Dips70 % / 500 ms conforming to IEC 61000-4-11
IP Degree Of ProtectionIP20 conforming to IEC 60947-1 (front panel and wired terminals)
IP20 conforming to IEC 60947-1 (other faces)
IP40 conforming to IEC 60947-1 (front panel outside connection zone)
Non-dissipating Shock Wave1 kV serial mode 24...240 V AC conforming to IEC 60947-6-2
1 kV serial mode 48...220 V DC conforming to IEC 60947-6-2
2 kV common mode 24...240 V AC conforming to IEC 60947-6-2
2 kV common mode 48...220 V DC conforming to IEC 60947-6-2
Operating Altitude2000 m
Product CertificationsASEFA
ATEX
CCC
CE
CSA
EAC
Marine
UL
Protective TreatmentTH conforming to IEC 60068
Resistance To Electrostatic Discharge8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance To Fast Transients2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Resistance To Radiated Fields10 V/m 3 conforming to IEC 61000-4-3
Shock Resistance10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
StandardsCSA C22.2 No 60947-4-1, with phase barrier
EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
Vibration Resistance2 gn (f= 5-300 Hz) power poles open conforming to IEC 60068-2-27
4 gn (f= 5-300 Hz) power poles closed conforming to IEC 60068-2-27
OTHER
Poles Description3P
[Us] Rated Supply VoltageTeSys U