LRD3359 - TeSys LRD Thermal Overload Relays - 48...65 A - Class 10A.
Short description of LRD3359
TeSys LRD thermal overload relay, 65A/1000V, thermal setting range 48-65A, tripping class 10A, for protection of 3-phase motors 30kW@400V. Differential device with phase failure (loss). It provides a thermal adjustement dial, a manual-automatic reset selector acting also as reset button, a trip test button for simulation of a tripping, a stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D80-D95. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LA7D3064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
-  product name : TeSys LRD
-  product or component type : Differential thermal overload relay
-  device short name : LRD
-  relay application : Motor protection
-  product compatibility : LC1D80LC1D95
-  network type : ACDC
-  thermal overload class : Class 10A conforming to IEC 60947-4-1
-  thermal protection adjustment range : 48…65 A
-  [Ui] rated insulation voltage : Power circuit :  1000 V conforming to IEC 60947-4-1Power circuit :  600 V conforming to CSAPower circuit :  600 V conforming to UL
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Control Type | blue push-button: reset red push-button: stop |
Product Or Component Type | differential thermal overload relay |
[Ie] Rated Operational Current | blue push-button: reset red push-button: stop |
[Ue] Rated Operational Voltage | 1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
Device Short Name | LRD |
Mounting Support | plate, with specific accessories rail, with specific accessories under contactor |
Network Type | AC DC |
Range | TeSys |
Range Name | TeSys LRD |
Relay Application | motor protection |
Thermal Overload Class | class 10A conforming to IEC 60947-4-1 |
COMPLEMENTARY | |
Communication Network Type | 1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
Product Name | TeSys LRD |
Associated Fuse Rating | 4 A BS for signalling circuit 4 A gG for signalling circuit |
Auxiliary Contact Composition | 1 NO + 1 NC |
Compatibility Code | LRD |
Connections - Terminals | control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible with cable end control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible without cable end control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² solid without cable end power circuit: screw clamp terminals 1 cable(s) 4-35 mm² flexible with cable end power circuit: screw clamp terminals 1 cable(s) 4-35 mm² flexible without cable end power circuit: screw clamp terminals 1 cable(s) 4-35 mm² solid without cable end |
Depth | 115 mm |
Flame Retardance | V1 conforming to UL 94 |
Height | 81 mm |
Mechanical Robustness | shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 vibrations: 6 Gn conforming to IEC 60068-2-6 |
Net Weight | 0.51 kg |
Network Frequency | 0...400 Hz |
Permissible Current | 0.06 A at 440 V DC-13 for signalling circuit 0.72 A at 500 V AC-15 for signalling circuit |
Phase Failure Sensitivity | tripping current 130 % of Ir on two phase, the last one at 0 |
Product Compatibility | LC1D80 LC1D95 |
Temperature Compensation | -20-60 °C |
Thermal Protection Adjustment Range | 48-65 A |
Tightening Torque | control circuit: 1.7 N.m - on screw clamp terminals power circuit: 9 N.m - on screw clamp terminals |
Tripping Threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Width | 70 mm |
[Ith] Conventional Free Air Thermal Current | 5 A for signalling circuit |
[Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947-1 |
[Ui] Rated Insulation Voltage | power circuit: 1000 V conforming to IEC 60947-4-1 power circuit: 600 V conforming to CSA power circuit: 600 V conforming to UL |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -20-60 °C without derating conforming to IEC 60947-4-1 |
Ambient Air Temperature For Storage | -60-70 °C |
Dielectric Strength | 2.2 kV at 50 Hz conforming to IEC 60947-1 |
IP Degree Of Protection | IP20 conforming to IEC 60529 |
Product Certifications | ATEX INERIS CCC CSA EAC IEC UKCA UL |
Protective Treatment | TH conforming to IEC 60068 |
Standards | CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 EN 50495 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.4 GB/T 14048.5 UL 60947-4-1 UL 60947-5-1 |
OTHER | |
Poles Description | differential thermal overload relay |