LC1F500 - TeSys F Contactor - 3P(3 NO)-AC-3 <= 440V 1100A with Coil LX1/ LX9 - 48…1000V AC 40/400Hz, LX4 - 48...440V DC.
Schneider
SKU
SE_LC1F500
Model
LC1F500
Obsolete
Short description of LC1F500
LC1F500. Contactors to control motors up to 1000 A (500 kW / 440 V)
Obsolete
range : TeSys
-  product name : TeSys F
-  product or component type : Contactor
-  device short name : LC1F
-  contactor application : Resistive loadMotor control
-  utilisation category : AC
- 4AC
- 1AC
- 3
-  poles description : 3P
-  power pole contact composition : 3 NO
-  [Ue] rated operational voltage-  [Ie] rated operational current : 700 A (at - motor power kW : 250 kW at 380...400 V AC 50/60 Hz (AC
- 3)280 kW at 415 V AC 50/60 Hz (AC
- 3)295 kW at 440 V AC 50/60 Hz (AC
- 3)335 kW at 1000 V AC 50/60 Hz (AC
- 3)355 kW at 500 V AC 50/60 Hz (AC
- 3)147 kW at 220...240 V AC 50/60 Hz (AC
- 3)335 kW at 660...690 V AC 50/60 Hz (AC
- 3)80 kW at 400 V AC 50/60 Hz (AC
- 4)
-  product name : TeSys F
-  product or component type : Contactor
-  device short name : LC1F
-  contactor application : Resistive loadMotor control
-  utilisation category : AC
- 4AC
- 1AC
- 3
-  poles description : 3P
-  power pole contact composition : 3 NO
-  [Ue] rated operational voltage-  [Ie] rated operational current : 700 A (at - motor power kW : 250 kW at 380...400 V AC 50/60 Hz (AC
- 3)280 kW at 415 V AC 50/60 Hz (AC
- 3)295 kW at 440 V AC 50/60 Hz (AC
- 3)335 kW at 1000 V AC 50/60 Hz (AC
- 3)355 kW at 500 V AC 50/60 Hz (AC
- 3)147 kW at 220...240 V AC 50/60 Hz (AC
- 3)335 kW at 660...690 V AC 50/60 Hz (AC
- 3)80 kW at 400 V AC 50/60 Hz (AC
- 4)
MAIN SPECIFICATIONS | |
---|---|
Control Type | 3P |
Product Or Component Type | contactor |
Range Of Product | TeSys F |
[Ie] Rated Operational Current | 500 A (at <55 °C) at <= 440 V AC AC-3 700 A (at <40 °C) at <= 440 V AC AC-1 |
[Uc] Control Circuit Voltage | 48...1000 V AC 40...400 Hz with LX1/LX9 coil 48...440 V DC with LX4 coil |
[Ue] Rated Operational Voltage | <= 1000 V AC 50/60 Hz <= 460 V DC |
Average Impedance | 0.18 mOhm - Ith 700 A 50 Hz |
Contactor Application | motor control resistive load |
Device Short Name | LC1F |
Mounting Support | plate |
Pole Contact Composition | 3 NO |
Power Dissipation Per Pole | 45 W AC-3 88 W AC-1 |
Range | TeSys |
Range Name | TeSys F |
Utilisation Category | AC-1 AC-3 AC-4 |
COMPLEMENTARY | |
Communication Network Type | <= 1000 V AC 50/60 Hz <= 460 V DC |
Product Name | TeSys F |
Associated Fuse Rating | 500 A aM at <= 440 V 800 A gG at <= 440 V |
Compatibility Code | LC1F |
Connections - Terminals | control circuit: screw clamp terminals 1 cable(s) 1-4 mm² control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²solid without cable end control circuit: screw clamp terminals 2 cable(s) 1-4 mm² control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end power circuit: bar 2 cable(s) - busbar cross section: 40 x 5 mm power circuit: bolted connection power circuit: lugs-ring terminals 2 cable(s) 240-240 mm² |
Control Circuit Voltage Limits | drop-out: 0.2...0.35 Uc N/A with LX4 coil drop-out: 0.3...0.5 Uc N/A 40...400 Hz with LX1/LX9 coil operational: 0.85...1.1 Uc N/A 40...400 Hz with LX1/LX9 coil operational: 0.85...1.1 Uc N/A with LX4 coil |
Depth | 232 mm |
Height | 238 mm |
Hold-in Power Consumption In VA | 16-20 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 4.54-8 VA (at 20 °C)with LX4 coil |
Inrush Power In VA | 1050-1150 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 990-1220 VA (at 20 °C)with LX4 coil |
Irms Rated Making Capacity | 5000 A AC conforming to IEC 60947-4-1 |
Maximum Operating Rate | 2400 cyc/h 55 °C |
Mechanical Durability | 10 Mcycles |
Mechanical Robustness | shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms) shocks contactor open: 9 Gn for 1/2 sine wave (11 ms) vibrations contactor closed: 4 Gn, 5...300 Hz vibrations contactor open: 2 Gn, 5...300 Hz |
Motor Power KW | 147 kW at 220...240 V AC 50/60 Hz (AC-3) 250 kW at 380...400 V AC 50/60 Hz (AC-3) 280 kW at 415 V AC 50/60 Hz (AC-3) 295 kW at 440 V AC 50/60 Hz (AC-3) 335 kW at 1000 V AC 50/60 Hz (AC-3) 335 kW at 660...690 V AC 50/60 Hz (AC-3) 355 kW at 500 V AC 50/60 Hz (AC-3) 80 kW at 400 V AC 50/60 Hz (AC-4) |
Net Weight | 9.75 kg |
Operating Time | 100...170 ms opening for with LX1/LX9 coil 40...75 ms closing for with LX1/LX9 coil 45...60 ms opening for with LX4 coil 50...60 ms closing for with LX4 coil |
Rated Breaking Capacity | 4000 A conforming to IEC 60947-4-1 |
Tightening Torque | control circuit: 1.2 N.m power circuit: 35 N.m |
Width | 233 mm |
[Icw] Rated Short-time Withstand Current | 1200 A 40 °C - 10 min 1500 A 40 °C - 3 min 2400 A 40 °C - 1 min 3200 A 40 °C - 30 s 4200 A 40 °C - 10 s |
[Ith] Conventional Free Air Thermal Current | 700 A (at 40 °C) |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
[Ui] Rated Insulation Voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -5-55 °C |
Ambient Air Temperature For Storage | -60-80 °C |
Heat Dissipation | 18-18 W |
IP Degree Of Protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
Operating Altitude | 3000 m without derating |
Overvoltage Category | III |
Permissible Ambient Air Temperature Around The Device | -40-70 °C |
Product Certifications | ABS BV CB CSA DNV LROS (Lloyds register of shipping) RINA RMRoS UKCA UL |
Protective Treatment | TH |
Standards | EN 60947-1 EN 60947-4-1 IEC 60947-1 IEC 60947-4-1 JIS C8201-4-1 |
OTHER | |
Poles Description | 3P |
[Us] Rated Supply Voltage | TeSys F |