VIGILOHM 12 CHANNEL FAULT LOCATOR WITH MODBUS HOSPITAL - 110-230VAC - 125/250VDC

Schneider
SKU
SE_IMDIFL12H
Model
IMDIFL12H
SGD $1,672.27

Short description of IMDIFL12H

VIGILOHM 12CH. LOCATOR MODBUS HOSP.
Country of Origin
India
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 6 To 8 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
VIGILOHM 12 CHANNEL FAULT LOCATOR WITH MODBUS HOSPITAL
-  110-230VAC
-  125/250VDC.
Label :  Vigilohm
-  range :  Vigilohm
-  range of product :  Vigilohm
-  product name :  Vigilohm IFL
-  language :  French,German,Italian,Portuguese,Russian,Spanish,English,Chinese
-  device short name :  IFL12H
-  product or component type :  insulation fault locator
-  device application :  hospital
-  earthing system :  IT
-  Range Presentation :  The Vigilohm range of insulation monitoring devices (IMDs) are an indispensible solution for implementing an IT (ungrounded) networks. Vigilohm provides solutions tailored to your network, including simple, reliable insulation monitoring, communication, and fault location.
This renewed and simplified offer helps improve personnel and equipment safety, and process availability.
Find out more : 
Vigilohm ebrochure
Brochure :  Vigilohm for Photovoltaic
Application guide :  The IT earthing system
-  Range Benefits :  In low voltage electrical distributions, the combined use of an IT network arrangement and insulation monitoring devices : 
-  Increases personnel safety
-  Reduces risk of fire or explosion
-  Increases process uptime
-  Eases maintenance and reduces OPEX
-  Range Application Presentation :  Vigilohm helps you make the best of your IT electrical network : 
-  Industry, including chemical, refinery, and transformation processes, where continuous process is critical
-  Infrastructure like airports, harbors, tunnels, and railways where safety is at stake
-  Healthcare, specifically in areas like operation theaters and intensive care unit for security of patient and medical staff
-  Marine for safety reasons
-  Power Generation like photovoltaic, wind, hydro and nuclear, to help prevent fires
-  Extraction, such as oil & gas and mining, to prevent fire and/or explosion
MAIN SPECIFICATIONS
Analogue Input Number110...230 V AC 50/60 Hz +/- 15 %
125...250 V DC +/- 15 %
Display Typedigital display
Product Or Component Typeinsulation fault locator
Range Of ProductVigilohm
Communication Port ProtocolModbus
Device Short NameIFL12H
EAN133606489504854
Mounting SupportDIN rail
panel
Number Of Channels12
RangeVigilohm
Range NameVigilohm
Signal Contacts Composition1 C/O standard or fail-safe
Signalling Circuit Voltage250 V - AC at 6 A
48 V - DC at 1 A
Type Of Measurementnetwork insulation resistance - measurement range: 200 Ohm...250 kOhm
User LanguageChinese
English
French
German
Italian
Portuguese
Russian
Spanish
COMPLEMENTARY
Analogue Output Numberdigital display
Product NameVigilohm IFL
Accuracy+/- 15 %
Communication Port SupportRS485
Connections - Terminalscommunication: removable screw terminal block0.2-2.5 mm²
output relay: removable screw terminal block0.2-2.5 mm²
power supply: removable screw terminal block0.2-2.5 mm²
toroids inputs: removable screw terminal block0.2-1.5 mm²
voltage inputs: removable screw terminal block0.2-2.5 mm²
Cut-out Dimensions92 x 104 mm
Depth59 mm
Device Applicationhospital
Earthing SystemIT
Height110 mm
Insulation Shieldyes
Local Signallinggreen indicator light: satisfactory insulation
green/red indicator light: product status
yellow flashing indicator light: communication
yellow flashing indicator light: transient fault
yellow indicator light: insulation fault
Materialthermoplastic
Mounting Modeclip-on
flush-mounted
Mounting Positionhorizontal
vertical
Net Weight0.5 kg
Network Rated Voltage0-230 V - AC at 45...65 Hz
0-230 V - DC
Power Consumption In VA25 VA
Power Consumption In W10 W
Response Time<= 5 s
Test Functionauto test at start and every 5h
manual
remote test
Threshold Settingalarm: 50...200 kOhm
Type Of Installationindoor
Type Of Settingalarm threshold: settable per feeder
Width108 mm
ENVIRONMENT
Ambient Air Temperature For Operation-25-55 °C
Ambient Air Temperature For Storage-40-85 °C
Environmental Characteristicexposure to damp heat in service conforming to IEC 60068-2-56
exposure to damp heat not in service conforming to IEC 60068-2-30
salt mist conforming to IEC 60068-2-52
IP Degree Of Protectioncase: IP20
front face: IP54
Operating Altitude<= 3000 m
Overvoltage CategoryIII
Pollution Degree2
Product CertificationsCE
cULus
DNV-GL
EAC
UL
Relative Humidity5-92 %
StandardsIEC 60364-7-710
IEC 61010-1
IEC 61326-2-4
IEC 61557-9
OTHER
Poles Descriptioninsulation fault locator
[Us] Rated Supply Voltage110...230 V AC 50/60 Hz +/- 15 %
125...250 V DC +/- 15 %
Write Your Own Review
You're reviewing:VIGILOHM 12 CHANNEL FAULT LOCATOR WITH MODBUS HOSPITAL - 110-230VAC - 125/250VDC
Your Rating