Short description of IMD IM9
VIGILOHM INSULATION MONITOR IM9
This device belongs to the Vigilohm range designed to monitor ungrounded/IT electrical networks, in accordance to installation and products standards. According to standards, it is recommanded to equip your systems with Insulation Monitoring Devices (IMD). This device is dedicated to monitoring pure AC systems of limited size, with low disturbances. It mesures the system insulation resistance by injecting a DC current between the network and ground. Configuration will be set depending on the installation. Settings are available on the front of the device. Settings are alarm and pre-alarm thresholds. It is equipped with a manual auto-test. In case the system insulation resistance drops below the set threshold, meaning a ground fault occurred, an alarm is triggered thru the IMD output relay. Once no fault is monitored, the alarm is cleared, the alarm relay is back to normal. This product can be installed on DIN rail.
Label :  Vigilohm
-  range :  Vigilohm
-  range of product :  Vigilohm
-  product name :  Vigilohm IM
-  device short name :  IM9
-  product or component type :  insulation monitoring device
-  device application :  marine application,standard environment application
-  application :  small and not disturbed network
-  earthing system :  IT
-  Range Presentation :  The Vigilohm range of insulation monitoring devices (IMDs) provides you with a simple, reliable insulation monitoring, communication and fault location solution for your IT (ungrounded) networks.
This renewed and simplified offer helps increase personnel and equipment safety and process availability.
-  Range Benefits :  In low voltage electrical distributions, the combined use of an IT network arrangement and Insulation Monitoring Devices : 
-  Increases personnel safety
-  Reduces risk of fire or explosion
-  Increases process uptime
-  Ease maintenance and reduce OPEX
-  Range Application Presentation :  Your solution to make the best of your IT electrical network
-  Industry, including chemical, refinery, and transformation processes, where continuous process is critical
-  Infrastructure like airports, harbors, tunnels, and railways where safety is at stake
-  Healthcare areas like operation theaters and intensive care unit for security of patient and medical staff
-  Marine for safety reasons
-  Power Generation like photovoltaic, wind, hydro and nuclear, to prevent fire
-  Extraction, such as oil &gas and mining, to prevent fire and/or explosion
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 110...415 V AC 45...440 Hz +/- 15 % 125...250 V DC +/- 15 % |
Product Or Component Type | insulation monitoring device |
Range Of Product | Vigilohm |
Application | small and not disturbed network |
Communication Port Protocol | - |
Device Short Name | IM9 |
EAN13 | 3606480321658 |
Mounting Support | DIN rail panel |
Range | Vigilohm |
Range Name | Vigilohm |
Signal Contacts Composition | 1 C/O standard or fail-safe |
Signalling Circuit Voltage | 12...24 V - DC at 6 A 250 V - AC at 6 A |
Type Of Measurement | network insulation resistance |
COMPLEMENTARY | |
Product Name | Vigilohm IM |
Compatibility Code | IM9 |
Connections - Terminals | tunnel type terminals0.2-2.5 mm² |
Depth | 67.5 mm |
Device Application | marine application standard environment application |
Earthing System | IT |
Height | 90 mm |
Insulation Shield | NO |
Market Segment | residential small commercial |
Material | thermoplastic |
Measurement Current | 0-70 µA |
Mounting Mode | clip-on flush-mounted |
Mounting Position | horizontal vertical |
Net Weight | 0.2 kg |
Network Rated Voltage | 0-480 V - AC at 45...440 Hz (device connected to phase) 0-600 V - AC at 45...440 Hz (device connected to neutral) |
Power Consumption In VA | 7 VA |
Relative Impedance | 230 kOhm - AC at 45...440 Hz |
Response Time | <= 7 s |
Test Function | local remote test |
Threshold Setting | alarm: 1...250 kOhm pre-alarm: 2...500 kOhm |
Type Of Installation | indoor |
Width | 71 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-55 °C |
Ambient Air Temperature For Storage | -40-70 °C |
Environmental Characteristic | exposure to damp heat in service conforming to IEC 60068-2-56 exposure to damp heat not in service conforming to IEC 60068-2-30 salt mist conforming to IEC 60068-2-52 |
IP Degree Of Protection | case: IP20 front face: IP40 |
Product Certifications | BV CE DNV EAC RMRS |
Standards | IEC 60664-1 IEC 61557-8 |
OTHER | |
Poles Description | insulation monitoring device |
[Us] Rated Supply Voltage | 110...415 V AC 45...440 Hz +/- 15 % 125...250 V DC +/- 15 % |