VIGILOHM IM400 100 - 440 VCA
Schneider
SKU
SE_IMD-IM400
Model
IMD-IM400
SGD $12,114.13
Short description of IMD IM400
VIGILOHM INSULATION MONITOR IM400
Country of Origin
India
VIGILOHM IM400 110
-  440 VCA.
Label :  Vigilohm
-  range :  Vigilohm
-  range of product :  Vigilohm
-  product name :  Vigilohm IM
-  language :  Italian,French,German,Chinese,Portuguese,Russian,Spanish,English
-  device short name :  IM400
-  product or component type :  insulation monitoring device
-  device application :  marine application,standard environment application
-  application :  large or highly disturbed network
-  earthing system :  IT
-  Range Presentation :  The Vigilohm range of insulation monitoring devices (IMDs) provides you with a simple, reliable insulation monitoring, communication and fault location solution for your IT (ungrounded) networks.
This renewed and simplified offer helps increase personnel and equipment safety and process availability.
-  Range Benefits :  In low voltage electrical distributions, the combined use of an IT network arrangement and Insulation Monitoring Devices : 
-  Increases personnel safety
-  Reduces risk of fire or explosion
-  Increases process uptime
-  Ease maintenance and reduce OPEX
-  Range Application Presentation :  Your solution to make the best of your IT electrical network
-  Industry, including chemical, refinery, and transformation processes, where continuous process is critical
-  Infrastructure like airports, harbors, tunnels, and railways where safety is at stake
-  Healthcare areas like operation theaters and intensive care unit for security of patient and medical staff
-  Marine for safety reasons
-  Power Generation like photovoltaic, wind, hydro and nuclear, to prevent fire
-  Extraction, such as oil &gas and mining, to prevent fire and/or explosion
-  440 VCA.
Label :  Vigilohm
-  range :  Vigilohm
-  range of product :  Vigilohm
-  product name :  Vigilohm IM
-  language :  Italian,French,German,Chinese,Portuguese,Russian,Spanish,English
-  device short name :  IM400
-  product or component type :  insulation monitoring device
-  device application :  marine application,standard environment application
-  application :  large or highly disturbed network
-  earthing system :  IT
-  Range Presentation :  The Vigilohm range of insulation monitoring devices (IMDs) provides you with a simple, reliable insulation monitoring, communication and fault location solution for your IT (ungrounded) networks.
This renewed and simplified offer helps increase personnel and equipment safety and process availability.
-  Range Benefits :  In low voltage electrical distributions, the combined use of an IT network arrangement and Insulation Monitoring Devices : 
-  Increases personnel safety
-  Reduces risk of fire or explosion
-  Increases process uptime
-  Ease maintenance and reduce OPEX
-  Range Application Presentation :  Your solution to make the best of your IT electrical network
-  Industry, including chemical, refinery, and transformation processes, where continuous process is critical
-  Infrastructure like airports, harbors, tunnels, and railways where safety is at stake
-  Healthcare areas like operation theaters and intensive care unit for security of patient and medical staff
-  Marine for safety reasons
-  Power Generation like photovoltaic, wind, hydro and nuclear, to prevent fire
-  Extraction, such as oil &gas and mining, to prevent fire and/or explosion
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 100...440 V AC 400 Hz +/- 15 % 100...440 V AC 50/60 Hz +/- 15 % 100...440 V DC +/- 15 % |
Display Type | digital display |
Product Or Component Type | insulation monitoring device |
Range Of Product | Vigilohm |
Thread Type | 0...120 min for signalling circuit |
Application | large or highly disturbed network |
Communication Port Protocol | Modbus |
Device Short Name | IM400 |
EAN13 | 3606480573347 |
Mounting Support | panel |
Range | Vigilohm |
Range Name | Vigilohm |
Signal Contacts Composition | 2 C/O standard or fail-safe |
Signalling Circuit Voltage | 250 V - AC at 6 A 48 V - DC at 1 A |
Type Of Measurement | earth leakage capacitance - measurement range: 0.1...500 µF network insulation resistance - measurement range: 10 Ohm...10 MOhm |
User Language | Chinese English French German Italian Portuguese Russian Spanish |
COMPLEMENTARY | |
Analogue Output Number | digital display |
Product Name | Vigilohm IM |
Time Delay Range | 0...120 min for signalling circuit |
Communication Port Support | RS485 |
Compatibility Code | IM400 |
Connections - Terminals | removable screw terminal block0.2-2.5 mm² |
Cut-out Dimensions | 112 x 148 mm |
Depth | 90 mm |
Device Application | marine application standard environment application |
Earthing System | IT |
Height | 123 mm |
Input Function | injection inhibition: 24 V AC 5 mA |
Insulation Shield | NO |
Local Signalling | green indicator light: satisfactory insulation resistance red indicator light: wiring or internal fault white indicator light: below prevention threshold yellow flashing indicator light: communication yellow indicator light: insulation fault |
Material | thermoplastic |
Measurement Current | 0-3 mA 0-375 µA 0-825 µA |
Measurement Voltage | 120-120 V 15-15 V 33-33 V |
Mounting Mode | flush-mounted |
Mounting Position | horizontal |
Net Weight | 0.75 kg |
Network Rated Voltage | 0-480 V - AC at 45...440 Hz (device connected to phase) 0-480 V - DC 0-830 V - AC at 45...440 Hz (device connected to neutral) |
Power Consumption In VA | 25 VA |
Relative Impedance | 40 kOhm - AC at 0.1...440 Hz 40 kOhm - DC |
Response Time | <= 4 s |
Test Function | manual self test |
Threshold Setting | alarm: 40 Ohm...500 kOhm pre-alarm: 1 kOhm...1 MOhm |
Type Of Installation | indoor |
Width | 159 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-55 °C |
Ambient Air Temperature For Storage | -40-70 °C |
Dielectric Strength | 4000 V - AC 5500 V - DC |
Environmental Characteristic | exposure to damp heat in service conforming to IEC 60068-2-56 exposure to damp heat not in service conforming to IEC 60068-2-30 salt mist conforming to IEC 60068-2-52 |
IP Degree Of Protection | case: IP20 front face: IP54 |
Operating Altitude | <= 3000 m |
Overvoltage Category | III |
Pollution Degree | 2 |
Product Certifications | ABS CE CSA cULus DNV EAC RMRS UL |
Relative Humidity | 0-90 % |
Standards | CSA C22.2 No 14-05 IEC 60364-4-41 IEC 60364-5-51 IEC 61010-1 IEC 61557-8 UL 508 |
OTHER | |
Poles Description | insulation monitoring device |
[Us] Rated Supply Voltage | 100...440 V AC 400 Hz +/- 15 % 100...440 V AC 50/60 Hz +/- 15 % 100...440 V DC +/- 15 % |