Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

VIGILOHM IM400 100 - 440 VCA

Schneider
SKU
SE_IMD-IM400
Model
IMD-IM400
SGD $12,114.13

Short description of IMD IM400

VIGILOHM INSULATION MONITOR IM400
Country of Origin
India
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 2 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
VIGILOHM IM400 110
-  440 VCA.
Label :  Vigilohm
-  range :  Vigilohm
-  range of product :  Vigilohm
-  product name :  Vigilohm IM
-  language :  Italian,French,German,Chinese,Portuguese,Russian,Spanish,English
-  device short name :  IM400
-  product or component type :  insulation monitoring device
-  device application :  marine application,standard environment application
-  application :  large or highly disturbed network
-  earthing system :  IT
-  Range Presentation :  The Vigilohm range of insulation monitoring devices (IMDs) provides you with a simple, reliable insulation monitoring, communication and fault location solution for your IT (ungrounded) networks.
This renewed and simplified offer helps increase personnel and equipment safety and process availability.
-  Range Benefits :  In low voltage electrical distributions, the combined use of an IT network arrangement and Insulation Monitoring Devices : 
-  Increases personnel safety
-  Reduces risk of fire or explosion
-  Increases process uptime
-  Ease maintenance and reduce OPEX
-  Range Application Presentation :  Your solution to make the best of your IT electrical network
-  Industry, including chemical, refinery, and transformation processes, where continuous process is critical
-  Infrastructure like airports, harbors, tunnels, and railways where safety is at stake
-  Healthcare areas like operation theaters and intensive care unit for security of patient and medical staff
-  Marine for safety reasons
-  Power Generation like photovoltaic, wind, hydro and nuclear, to prevent fire
-  Extraction, such as oil &gas and mining, to prevent fire and/or explosion
MAIN SPECIFICATIONS
Analogue Input Number100...440 V AC 400 Hz +/- 15 %
100...440 V AC 50/60 Hz +/- 15 %
100...440 V DC +/- 15 %
Display Typedigital display
Product Or Component Typeinsulation monitoring device
Range Of ProductVigilohm
Thread Type0...120 min for signalling circuit
Applicationlarge or highly disturbed network
Communication Port ProtocolModbus
Device Short NameIM400
EAN133606480573347
Mounting Supportpanel
RangeVigilohm
Range NameVigilohm
Signal Contacts Composition2 C/O standard or fail-safe
Signalling Circuit Voltage250 V - AC at 6 A
48 V - DC at 1 A
Type Of Measurementearth leakage capacitance - measurement range: 0.1...500 µF
network insulation resistance - measurement range: 10 Ohm...10 MOhm
User LanguageChinese
English
French
German
Italian
Portuguese
Russian
Spanish
COMPLEMENTARY
Analogue Output Numberdigital display
Product NameVigilohm IM
Time Delay Range0...120 min for signalling circuit
Communication Port SupportRS485
Compatibility CodeIM400
Connections - Terminalsremovable screw terminal block0.2-2.5 mm²
Cut-out Dimensions112 x 148 mm
Depth90 mm
Device Applicationmarine application
standard environment application
Earthing SystemIT
Height123 mm
Input Functioninjection inhibition: 24 V AC 5 mA
Insulation ShieldNO
Local Signallinggreen indicator light: satisfactory insulation resistance
red indicator light: wiring or internal fault
white indicator light: below prevention threshold
yellow flashing indicator light: communication
yellow indicator light: insulation fault
Materialthermoplastic
Measurement Current0-3 mA
0-375 µA
0-825 µA
Measurement Voltage120-120 V
15-15 V
33-33 V
Mounting Modeflush-mounted
Mounting Positionhorizontal
Net Weight0.75 kg
Network Rated Voltage0-480 V - AC at 45...440 Hz (device connected to phase)
0-480 V - DC
0-830 V - AC at 45...440 Hz (device connected to neutral)
Power Consumption In VA25 VA
Relative Impedance40 kOhm - AC at 0.1...440 Hz
40 kOhm - DC
Response Time<= 4 s
Test Functionmanual
self test
Threshold Settingalarm: 40 Ohm...500 kOhm
pre-alarm: 1 kOhm...1 MOhm
Type Of Installationindoor
Width159 mm
ENVIRONMENT
Ambient Air Temperature For Operation-25-55 °C
Ambient Air Temperature For Storage-40-70 °C
Dielectric Strength4000 V - AC
5500 V - DC
Environmental Characteristicexposure to damp heat in service conforming to IEC 60068-2-56
exposure to damp heat not in service conforming to IEC 60068-2-30
salt mist conforming to IEC 60068-2-52
IP Degree Of Protectioncase: IP20
front face: IP54
Operating Altitude<= 3000 m
Overvoltage CategoryIII
Pollution Degree2
Product CertificationsABS
CE
CSA
cULus
DNV
EAC
RMRS
UL
Relative Humidity0-90 %
StandardsCSA C22.2 No 14-05
IEC 60364-4-41
IEC 60364-5-51
IEC 61010-1
IEC 61557-8
UL 508
OTHER
Poles Descriptioninsulation monitoring device
[Us] Rated Supply Voltage100...440 V AC 400 Hz +/- 15 %
100...440 V AC 50/60 Hz +/- 15 %
100...440 V DC +/- 15 %
Write Your Own Review
You're reviewing:VIGILOHM IM400 100 - 440 VCA
Your Rating