Variable Speed Drive, Altivar Process ATV600, ATV630, 75kW/100 Hp, 380...480 V, IP21/UL Type 1

Schneider
SKU
SE_ATV630D75N4
Model
ATV630D75N4
SGD $8,249.41

Short description of ATV630D75N4

variable speed drive IP21 75KW 400v/480v
Country of Origin
India
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 2 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
variable speed drive ATV630
-  75kW/100HP
-  380...480V
-  IP21/UL type 1.
Label :  Altivar Process ATV600
-  range of product :  Altivar Process ATV600
-  degree of protection :  UL type 1 conforming to UL 508C
-  type of cooling :  forced convection
-  supply frequency :  50...60 Hz
-  5...5 %
-  network number of phases :  3 phases
-  [Us] rated supply voltage :  380...480 V
-  15...10 %
-  motor power kW :  75 kW (normal duty), 55 kW (heavy duty)
-  motor power hp :  100 hp normal duty, 75 hp heavy duty
-  line current :  131.3 A at 380 V (normal duty), 112.7 A at 480 V (normal duty), 98.9 A at 380 V (heavy duty), 86.9 A at 480 V (heavy duty)
-  prospective line Isc :  50 kA
-  apparent power :  93.7 kVA at 480 V (normal duty), 72.2 kVA at 480 V (heavy duty)
-  product or component type :  variable speed drive
-  continuous output current :  145 A at 2.5 kHzfor normal duty, 106 A at 2.5 kHzfor heavy duty
-  maximum transient current :  159.5 A during 60 s (normal duty), 159 A during 60 s (heavy duty)
-  asynchronous motor control profile :  variable torque standard,constant torque standard,optimized torque mode
-  synchronous motor control profile :  permanent magnet motor
-  output frequency :  0.0001-0.5 kHz
-  speed drive output frequency :  0.1-599 Hz
-  nominal switching frequency :  2.5 kHz
-  switching frequency :  2.5...8 kHz with derating factor, 2...8 kHz adjustable
-  safety function :  STO (safe torque off) SIL 3
-  product specific application :  process and utilities
-  discrete input logic :  16 preset speeds
-  communication port protocol :  Ethernet,Modbus serial,Modbus TCP
-  option card :  N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A
-  device short name :  ATV630
-  variant :  standard version
-  product destination :  synchronous motors,asynchronous motors
-  mounting mode :  wall mount
-  EMC filter :  integrated conforming to EN/IEC 61800-3 category C3 with 150 m
-  IP degree of protection :  N/A, N/A
-  Range Presentation :  Altivar Process is a Services Oriented Drive designed to reduce OPEX in Process & Utilities installations, thanks to embedded digital services
Altivar Process also provides unique engineered drive solutionsThe first Services Oriented Drive with -  Embedded Power measurement and Energy dashboard
-  Embedded process monitoring and control
-  Embedded Pump curves embedded (easy to set 5 points curve)
-  Low Harmonics (THDi 48% at 80% load or THDi 5% with low harmonic offer)
-  Start & Stop function to reduce consumption at stop.
-  Asset monitoring & protection
-  Drift monitoring
-  Easy maintenance (Dynamic QR
- Code)
-  Seamless integration with embedded Ethernet
-  From device to process control with the Smart Process Object
-  From data to insights with the embedded Web Server
Unique Engineered Drives -  Proven technical cooling and harmonics solutions
-  Modular and compact design
-  Easy grid integration
-  Embedded Control (PLC, RTU, HMI)
-  A full set of control option
-  Range Benefits :  Services Oriented Drives
This new concept of drives meets the major needs of the process and utilities in terms of over equipment efficiency and Total Cost of ownership by supporting the energy management, asset management and also the overall performances of the process.
-  Sustainable cost savings thanks to predictive condition
- based maintenance
-  Up to 20% downtime reduction without additional investment
Unique Engineered Drives
Schneider Electric’s expertise in design and application services delivers solution
- specific designs dedicated to your process requirements for seamless plant integration.
-  Minimize design and delivery risks
-  Reduces the commissioning and adaptation time
Enhanced Drives specifications
Compact and modular, suitable even in harsh environments, Altivar Process is perfect for upgrades, retrofits, or new installations.
-  Withstand the severe conditions of use both electrical as environmental
-  Range Application Presentation :  Altivar Process drives have been specifically designed for industrial processes, such as : 
WWW :  Pumping station, boosting station, borehole pump, lifting station, aeration, as compression, sludge conveying…
O&G :  Electrically submersible pump, jack pumps, oil line pump, swapping pump, water injection pump, regasification compressor... Refinery :  pumps, fans, compressors…MMM  : 
-  Mining :  Floatation & thickening, de
- watering and filtration, mine shaft pumps…
-  Cement :  Pre
- heater fan, kiln waste gas fan, cooler exhaust fan, vertical roller mill, pump for water supply…
-  Metal :  blast furnace blower, water distribution pump system, draught fan, dedusting fan, coke machine (Oven)… F&B :  dairy (pumping pipe distribution, milk powder drying, centrifugal pump…), sugar (pumps, blower for drying…)
MAIN SPECIFICATIONS
Analog/digital Conversionsoftware-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
software-configurable current DQ-, DQ+: 100 mA
software-configurable current DQ-, DQ+: 30 V DC
software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Analogue Input Number3
Analogue Input Range3
Discrete Input Number8
Discrete Output Typerelay outputs R1A, R1B, R1C 250 V AC 3000 mA
relay outputs R1A, R1B, R1C 30 V DC 3000 mA
relay outputs R2A, R2C 250 V AC 5000 mA
relay outputs R2A, R2C 30 V DC 5000 mA
relay outputs R3A, R3C 250 V AC 5000 mA
relay outputs R3A, R3C 30 V DC 5000 mA
Display Type2-wire RS 485
Ethernet
Measurement AccuracyRJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
Physical Interface2-wire RS 485
Ethernet
Product Or Component Typevariable speed drive
Range Of ProductAltivar Process ATV600
Communication Port ProtocolEthernet
Modbus serial
Modbus TCP
Degree Of ProtectionUL type 1 conforming to UL 508C
Design Of Frequency ChangerU converter
Device Short NameATV630
EAN133606480701450
EMC Filterintegrated with 150 m conforming to EN/IEC 61800-3 category C3
Line Current112.7 A at 480 V (normal duty)
131.3 A at 380 V (normal duty)
86.9 A at 480 V (heavy duty)
98.9 A at 380 V (heavy duty)
Method Of Accessslave Modbus TCP
Motor Power Hp100 hp normal duty
75 hp heavy duty
Network Number Of Phases3 phases
Number Of Input Phases3
Number Of Output Phases3
Product Specific Applicationprocess and utilities
Range NameAltivar Process ATV600
Relative Symmetric Mains Voltage Tolerance10 %
COMPLEMENTARY
Analogue Input TypeAI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Analogue Output Number2
Analogue Output Typesoftware-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
software-configurable current DQ-, DQ+: 100 mA
software-configurable current DQ-, DQ+: 30 V DC
software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Connector TypeRJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
Discrete Output Number2
Output Voltage<= power supply voltage
[Ics] Rated Service Breaking Capacityrelay outputs R1A, R1B, R1C 250 V AC 3000 mA
relay outputs R1A, R1B, R1C 30 V DC 3000 mA
relay outputs R2A, R2C 250 V AC 5000 mA
relay outputs R2A, R2C 30 V DC 5000 mA
relay outputs R3A, R3C 250 V AC 5000 mA
relay outputs R3A, R3C 30 V DC 5000 mA
1 Phase Low Current Possiblefalse
4 Quadrant Operation Possiblefalse
Acceleration And Deceleration Rampslinear adjustable separately from 0.01...9999 s
Accuracy+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Apparent Power72.2 kVA at 480 V (heavy duty)
93.7 kVA at 480 V (normal duty)
Application In Domestic And Commercial Area Permittedfalse
Application In Industrial Area Permittedtrue
Asynchronous Motor Control Profileconstant torque standard
optimized torque mode
variable torque standard
Base Load Current At High Overload106 A
Base Load Current At Low Overload145 A
Brake Chopper Integratedfalse
Braking To Standstillby DC injection
Capacity Of DC Link5600 µF
Computer Porttrue
Continuous Output Current106 A at 2.5 kHz for heavy duty
145 A at 2.5 kHz for normal duty
Data Format8 bits, configurable odd, even or no parity
Depth323 mm
Discrete Input Logicnegative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)
16 preset speeds
Discrete Input TypeDI7, DI8 programmable as pulse input: 0-30 kHz, 24 V DC (<= 30 V)
Electrical Connectioncontrol: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16
line side: screw terminal 95...120 mm²/AWG 3/0...250 kcmil
motor: screw terminal 95...120 mm²/AWG 3/0...250 kcmil
EMC Limit Value (complied)true
Enclosure Mountingwall mounted
Exchange Modehalf duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Frequency Resolutionanalog input: 0.012/50 Hz
display unit: 0.1 Hz
Functionalityfull
Height922 mm
Housing Materialsheet steel
Input CompatibilityDI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
Insulation Resistance> 1 MOhm 500 V DC for 1 minute to earth
Isolationbetween power and control terminals
Linearity ErrorAI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Local Signalling1 LED (red) for presence of voltage
3 LEDs (dual colour) for embedded communication status
3 LEDs for local diagnostic
4 LEDs (dual colour) for communication module status
MarkingCE
Maximum Associated Fuse Rating250 A
Maximum Input Current131.3 A
Maximum Output Frequency500 kHz
Maximum Output Voltage480 V
Maximum Switching Currentrelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 250 V AC
relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 30 V DC
Maximum Transient Current159 A during 60 s (heavy duty)
159.5 A during 60 s (normal duty)
Minimum Switching Currentrelay output R1, R2, R3: 5 mA at 24 V DC
Motor Power KW55 kW (heavy duty)
75 kW (normal duty)
Motor Slip Compensationadjustable
automatic whatever the load
can be suppressed
not available in permanent magnet motor law
Motor Starter Typevariable speed drive
Mounting Modewall mount
Net Weight58 kg
Network Frequency50...60 Hz
Nominal Output Current145 A
Nominal Output Power75 kW
Nominal Switching Frequency2.5 kHz
Number Of Addresses1-247 for Modbus serial
Number Of HW Interfaces Industrial Ethernet1
Number Of HW Interfaces Serial RS4851
Operating Element Presenttrue
Operating Positionvertical +/- 10 degree
Optical Interface Presentfalse
Option Cardcommunication module, BACnet MS/TP
communication module, Ethernet Powerlink
slot A/slot B: digital and analog I/O extension module
slot A/slot B: output relay extension module
slot A: communication module, CANopen daisy chain RJ45
slot A: communication module, CANopen screw terminals
slot A: communication module, CANopen SUB-D 9
slot A: communication module, DeviceNet
slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
slot A: communication module, Modbus TCP/EtherNet/IP
slot A: communication module, Profibus DP V1
slot A: communication module, Profinet
Permissible Temporary Current Boost1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)
Power Dissipation In Wforced convection: 1369 W at 380 V, switching frequency 2.5 kHz
natural convection: 174 W at 380 V, switching frequency 2.5 kHz
Power Loss Per Device Current Dependent1785 W
Power Loss Static Current Independent32 W
Power Range55-100 kW at 380-440 V 3 phases
55-100 kW at 480-500 V 3 phases
Product Destinationasynchronous motors
synchronous motors
Prospective Line Isc50 kA
Protection Typebreak on the control circuit: drive
line supply overvoltage: drive
line supply phase loss: drive
line supply undervoltage: drive
motor phase break: drive
motor phase break: motor
overcurrent between output phases and earth: drive
overheating: drive
overload of output voltage: drive
overspeed: drive
overvoltages on the DC bus: drive
safe torque off: drive
safe torque off: motor
short-circuit protection: drive
thermal protection: drive
thermal protection: motor
Quantity Per Set1
Refresh Timerelay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Relative Symmetric Network Frequency Tolerance5 %
Relay Output Number3
Relay Output Typeconfigurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Safety FunctionSTO (safe torque off) SIL 3
Sampling Duration10 ms +/- 1 ms (AO1) - analog output
2 ms +/- 0.5 ms (DI1...DI4) - discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
5 ms +/- 1 ms (DI5, DI6) - discrete input
Specific Applicationutility
Speed Drive Output Frequency0.1-500 Hz
Supplyexternal supply for digital inputs: 24 V DC (19-30 V), <1.25 mA, protection type: overload and short-circuit protection
internal supply for digital inputs and STO: 24 V DC (21-27 V), <200 mA, protection type: overload and short-circuit protection
internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Supply Frequency50...60 Hz - 5...5 %
Supporting Protocol For AS-Interface Safety At Workfalse
Supporting Protocol For ASIfalse
Supporting Protocol For BACnetfalse
Supporting Protocol For CANtrue
Supporting Protocol For Data-Highwayfalse
Supporting Protocol For DeviceNetfalse
Supporting Protocol For DeviceNet Safetyfalse
Supporting Protocol For EtherNet/IPtrue
Supporting Protocol For Foundation Fieldbusfalse
Supporting Protocol For INTERBUSfalse
Supporting Protocol For INTERBUS-Safetyfalse
Supporting Protocol For KNXfalse
Supporting Protocol For LONfalse
Supporting Protocol For MODBUStrue
Supporting Protocol For Other Bus Systemsfalse
Supporting Protocol For PROFIBUStrue
Supporting Protocol For PROFINET CBAtrue
Supporting Protocol For PROFINET IOtrue
Supporting Protocol For PROFIsafefalse
Supporting Protocol For SafetyBUS Pfalse
Supporting Protocol For SERCOSfalse
Supporting Protocol For SUCONETfalse
Supporting Protocol For TCP/IPtrue
Switching Frequency2...8 kHz adjustable
2.5...8 kHz with derating factor
Synchronous Motor Control Profilepermanent magnet motor
synchronous reluctance motor
Transmission FrameRTU
Transmission Rate10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Type Of Coolingforced convection
Type Of Polarizationno impedance
Width290 mm
With Safety Function Safe Brake Management (SBC/SBT)false
With Safety Function Safe Direction (SDI)false
With Safety Function Safe Operating Stop (SOS)false
With Safety Function Safe Position (SP)false
With Safety Function Safe Programmable Logicfalse
With Safety Function Safe Speed Monitor (SSM)false
With Safety Function Safe Stop 1 (SS1)false
With Safety Function Safe Torque Off (STO)true
With Safety Function Safely Limited Position (SLP)false
With Safety Function Safely Limited Speed (SLS)false
With Sft Fct Safe Stop 2 (SS2)false
ENVIRONMENT
Ambient Air Temperature For Operation-15-50 °C (without derating)
-15-60 °C
50-60 °C (with derating factor)
Ambient Air Temperature For Storage-40-70 °C
Ambient Air Transport Temperature-40-70 °C
Electromagnetic Compatibility1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Environmental Class (during Operation)class 3C3 according to IEC 60721-3-3
class 3S3 according to IEC 60721-3-3
Environmental Class (during Storage)class 1C3 according to EN 60721-3-1
class 1S2 according to EN 60721-3-1
Environmental Class (during Transport)class 2C3 according to EN 60721-3-2
class 2S1 according to EN 60721-3-2
IP Degree Of ProtectionIP21
IP21 conforming to IEC 60529
IP21 conforming to IEC 61800-5-1
Maximum Acceleration Under Shock Impact (during Operation)150 m/s² at 11 ms
Maximum Acceleration Under Shock Load (during Storage)150 m/s² at 11 ms
Maximum Acceleration Under Shock Load (during Transport)150 m/s² at 11 ms
Maximum Acceleration Under Vibrational Stress (during Operation)10 m/s² at 13...200 Hz
Maximum Acceleration Under Vibratory Load (during Storage)10 m/s² at 13...200 Hz
Maximum Acceleration Under Vibratory Load (during Transport)10 m/s² at 13...200 Hz
Maximum Deflection Under Vibratory Load (during Operation)1.5 mm at 2...13 Hz
Maximum Deflection Under Vibratory Load (during Storage)1.5 mm at 2...13 Hz
Maximum Deflection Under Vibratory Load (during Transport)1.5 mm at 2...13 Hz
Maximum THDI <48 % from 80...100 % of load conforming to IEC 61000-3-12
NEMA Degree Of ProtectionNEMA 1
Noise Level62.4 dB
62.4 dB conforming to 86/188/EEC
Operating Altitude<= 1000 m without derating
1000...4800 m with current derating 1 % per 100 m
Overvoltage CategoryIII
Permitted Relative Humidity (during Operation)class 3K5 according to EN 60721-3
Permitted Relative Humidity (during Storage)class 1K5 according to EN 60721-3
Permitted Relative Humidity (during Transport)class 2K5 according to EN 60721-3
Pollution Degree2
2 conforming to EN/IEC 61800-5-1
Product CertificationsATEX INERIS
ATEX zone 2/22
CSA
DNV-GL
TÜV
UL
Regulation Loopadjustable PID regulator
Relative Humidity5-95 % without condensation conforming to IEC 60068-2-3
Shock Resistance15 gn for 11 ms conforming to IEC 60068-2-27
Standards EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 13849-1
IEC 60721-3
IEC 61000-3-12
IEC 61508
UL 508C
EN/IEC 61800-3
EN/IEC 61800-3 environment 1 category C2
EN/IEC 61800-3 environment 2 category C3
EN/IEC 61800-5-1
environment 1 category C2 EN/IEC 61800-3
environment 2 category C3 EN/IEC 61800-3
IEC 13849-1
IEC 60721-3
IEC 61000-3-12
IEC 61508
UL 508C
Vibration Resistance1 gn (f= 13-200 Hz) conforming to IEC 60068-2-6
1.5 mm peak to peak (f= 2-13 Hz) conforming to IEC 60068-2-6
Volume Of Cooling Air295 m3/h
OTHER
Poles Descriptionvariable speed drive
[Us] Rated Supply Voltage380...480 V
380...480 V - 15...10 %
Write Your Own Review
You're reviewing:Variable Speed Drive, Altivar Process ATV600, ATV630, 75kW/100 Hp, 380...480 V, IP21/UL Type 1
Your Rating