Short description of ABR2SB312B

ABR2SB312B. Electromechanical and solid state interfaces for discrete signals
Obsolete
range of product : Interface for discrete signals
-  product or component type : Slim electromechanical output interface module
-  product specific application : For very low level switching
-  contacts type and composition : 1 C/O
-  [Uc] control circuit voltage : 24 V
-  control circuit type : DC
-  width pitch dimension : 17.5 mm
-  maximum [In] rated current : 23 mA
-  reverse polarity protection : With
-  short-circuit protection : 0.4 A external fuse fast blow (Ik
-  [Ith] conventional free air thermal current : 0.05 A conforming to IEC 60947-1
-  local signalling : Green LED for control signal state
MAIN SPECIFICATIONS
Contacts Type And Composition1 C/O
Discrete Input Number1 C/O
Product Or Component Typeslim electromechanical output interface module
Range Of Productinterface for discrete signals
[Uc] Control Circuit Voltage24 V
[Ue] Rated Operational Voltage<= 48 V AC conforming to IEC 60947-5-1
<= 48 V DC conforming to IEC 60947-5-1
Control Circuit TypeDC
Maximum [In] Rated Current23 mA
Mounting Supportasymmetrical DIN rail
combination rail
symmetrical DIN rail
Product Specific Applicationfor very low level switching
Range NameZelio Interface
Short-circuit Protection0.4 A external fuse fast blow (Ik <= 1 kA AC and Ik <= 100 A DC)
Width Pitch Dimension17.5 mm
COMPLEMENTARY
Communication Network Type<= 48 V AC conforming to IEC 60947-5-1
<= 48 V DC conforming to IEC 60947-5-1
Cable Cross Section0.27-4 mm², 1 wire rigid
0.34-2.5 mm², 1 or 2 wires flexible with cable end
0.6-2.5 mm², 1 or 2 wires flexible without cable end
Connections - Terminalsscrew clamp terminal
Contact Bounce Time<= 2 ms
Control Circuit Voltage Limits28.8 V energization threshold: 16.9 V
Drop-out Voltage3.8 V
Electrical Reliability<= 0.00000001
Flame RetardanceV0 conforming to UL 94
Holding Current2 mA
Immunity To Microbreaks1 ms
Local Signallinggreen LED for control signal state
Maximum Switching Voltage60 V AC
60 V DC
Mechanical Durability20000000 cycles
Minimum Switching Current0.01 mA
Minimum Switching Voltage0.01 V
Net Weight0.048 kg
Network Frequency50/60 Hz
Operating Positionany position
Operating Rate In Hz10 Hz at no-load
Operating Time<= 6 ms between de-energisation of coil and closing of NC contact
<= 6 ms between de-energisation of coil and closing of NO contact DC
<= 6 ms between energisation of coil and closing of NC contact
<= 6 ms between energisation of coil and closing of NO contact DC
Power Dissipation In W0.55 W
Reverse Polarity Protectionwith
[Ith] Conventional Free Air Thermal Current0.05 A conforming to IEC 60947-1
[Ui] Rated Insulation Voltage250 V conforming to VDE 0110 group C
300 V conforming to IEC 60947-1
ENVIRONMENT
Ambient Air Temperature For Operation-25-55 °C at Us
-25-70 °C at Us with 8 mm space between ABR2S1...
-5-40 °C unrestricted operation
-5-55 °C from 0.85...1.1 Us
Ambient Air Temperature For Storage-40-80 °C
Dielectric Strength1000 V for 1 minute between open contacts
1500 V between coil circuit and contact circuits
2500 V for 1 minute between wired interface and earth
Electromagnetic Compatibility1.2/50 µs shock waves immunity test conforming to IEC 60947-1
electromagnetic field immunity test: level 3 10 V/m between 27...1000 MHz conforming to IEC 61000-4-3
electrostatic discharge immunity test: level 3 8 kV conforming to IEC 61000-4-2
fast transients immunity test: level 3 on input/output 1 kV conforming to IEC 61000-4-4
fast transients immunity test: level 3 on power supply 2 kV conforming to IEC 61000-4-4
Fire Resistance960 °C conforming to IEC 60695-2-1
Installation CategoryII conforming to IEC 60947-1
IP Degree Of ProtectionIP20 conforming to IEC 60529
Operating Altitude<= 3000 m
Pollution Degree2 conforming to IEC 60947-1
Product CertificationsBV
CSA
DNV
LROS (Lloyds register of shipping)
UL
Protective TreatmentTC
Shock Resistance30 gn for 11 ms conforming to IEC 60068-2-27
StandardsIEC 60947-5-1
Vibration Resistance3 gn conforming to IEC 60068-2-6 (f = 10-150 Hz)
OTHER
Poles Descriptionslim electromechanical output interface module