ABR1S618E - Output Interface Module - 17.5 Mm - Electromechanical - 48 V AC/DC - 1 NC + 1 NO.
Schneider
SKU
SE_ABR1S618E
Model
ABR1S618E
Obsolete
Short description of ABR1S618E
ABR1S618E. Electromechanical and solid state interfaces for discrete signals
Obsolete
range of product : Interface for discrete signals
-  product or component type : Electromechanical output interface module
-  contacts type and composition : 1 NC + 1 NO
-  [Uc] control circuit voltage : 48 V
-  control circuit type : AC/DC
-  control circuit frequency : 50/60 Hz
-  width pitch dimension : 17.5 mm
-  maximum [In] rated current : 32 mA AC36 mA DC
-  reverse polarity protection : With
-  short-circuit protection : 16 A external fuse gF (Ik
-  [Ith] conventional free air thermal current : 12 A conforming to IEC 60947-1
-  local signalling : Green mechanical indicator for position of contacts and 1 green LED control signal state
-  product or component type : Electromechanical output interface module
-  contacts type and composition : 1 NC + 1 NO
-  [Uc] control circuit voltage : 48 V
-  control circuit type : AC/DC
-  control circuit frequency : 50/60 Hz
-  width pitch dimension : 17.5 mm
-  maximum [In] rated current : 32 mA AC36 mA DC
-  reverse polarity protection : With
-  short-circuit protection : 16 A external fuse gF (Ik
-  [Ith] conventional free air thermal current : 12 A conforming to IEC 60947-1
-  local signalling : Green mechanical indicator for position of contacts and 1 green LED control signal state
MAIN SPECIFICATIONS | |
---|---|
Contacts Type And Composition | 1 NC + 1 NO |
Discrete Input Number | 1 NC + 1 NO |
Product Or Component Type | electromechanical output interface module |
Range Of Product | interface for discrete signals |
[Ie] Rated Operational Current | 1 A AC-13 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1 1 A AC-14 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1 1 A AC-15 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1 1 A DC-13 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-1 4 A AC-12 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1 5 A DC-12 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-1 |
[Uc] Control Circuit Voltage | 48 V |
[Ue] Rated Operational Voltage | <= 125 V DC conforming to IEC 60947-5-1 <= 230 V AC conforming to IEC 60947-5-1 |
Control Circuit Frequency | 50/60 Hz |
Control Circuit Type | AC/DC |
Maximum [In] Rated Current | 32 mA AC 36 mA DC |
Mounting Support | asymmetrical DIN rail combination rail symmetrical DIN rail |
Range Name | Zelio Interface |
Short-circuit Protection | 16 A external fuse gF (Ik <= 2.5 kA AC and Ik <= 100 A DC) 16 A external fuse gG (Ik <= 2.5 kA AC and Ik <= 100 A DC) |
Width Pitch Dimension | 17.5 mm |
COMPLEMENTARY | |
Communication Network Type | <= 125 V DC conforming to IEC 60947-5-1 <= 230 V AC conforming to IEC 60947-5-1 |
Cable Cross Section | 0.27-2.5 mm², 2 wires rigid 0.27-4 mm², 1 wire rigid 0.34-2.5 mm², 1 or 2 wires flexible with cable end 0.6-2.5 mm², 1 or 2 wires flexible without cable end |
Connections - Terminals | screw clamp terminal |
Contact Bounce Time | <= 3 ms |
Control Circuit Voltage Limits | 53 V energization threshold: 34 V |
Drop-out Voltage | 8.5 V |
Electrical Reliability | <= 0.00000001 |
Flame Retardance | V0 conforming to UL 94 |
Housing Colour | grey |
Immunity To Microbreaks | 10 ms |
Local Signalling | green mechanical indicator for position of contacts and 1 green LED control signal state |
Maximum Power Dissipation In W | 1.5 W |
Maximum Switching Voltage | 125 V DC |
Mechanical Durability | 10000000 cycles |
Minimum Holding Current | 4.7 mA DC 5.4 mA AC |
Minimum Switching Current | 3 mA |
Minimum Switching Voltage | 17 V |
Net Weight | 0.095 kg |
Network Frequency | 50/60 Hz |
Operating Position | any position |
Operating Rate In Hz | 0.5 Hz at Ie 6 Hz at no-load |
Operating Time | <= 12 ms between de-energisation of coil and closing of NC contact <= 12 ms between de-energisation of coil and closing of NO contact <= 12 ms between energisation of coil and closing of NC contact <= 12 ms between energisation of coil and closing of NO contact |
Overlap Time | 1 ms |
Reverse Polarity Protection | with |
[Ith] Conventional Free Air Thermal Current | 12 A conforming to IEC 60947-1 |
[Ui] Rated Insulation Voltage | 250 V conforming to IEC 60947-1 250 V conforming to VDE 0110 group C |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -20-60 °C at Un -5-40 °C unrestricted operation |
Ambient Air Temperature For Storage | -40-70 °C |
Dielectric Strength | 1500 V for 1 minute between independent contacts 2500 V for 1 minute between wired interface and earth 4000 V for 1 minute between coil circuit and contact circuits |
Electromagnetic Compatibility | 1.2/50 ms shock waves immunity test conforming to IEC 255-4 electrostatic discharge immunity test, level 3 8 kV conforming to IEC 61000-4-2 rapid transients immunity test on input/output 1 kV conforming to IEC 61000-4-4 rapid transients immunity test on power supply 2 kV conforming to IEC 61000-4-4 |
Fire Resistance | 850 °C conforming to IEC 60695-2-1 |
Installation Category | II conforming to IEC 60947-1 |
IP Degree Of Protection | IP20 conforming to IEC 60529 |
Operating Altitude | <= 3000 m |
Pollution Degree | 3 conforming to IEC 60947-5-1 |
Product Certifications | BV CSA DNV LROS (Lloyds register of shipping) UL |
Protective Treatment | TC |
Shock Resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
Standards | IEC 60947-5-1 |
Vibration Resistance | 6 gn conforming to IEC 60068-2-6 (f = 10-55 Hz) |
OTHER | |
Poles Description | electromechanical output interface module |
[Us] Rated Supply Voltage | interface for discrete signals |