
ABLS1A12062 - Regulated Power Supply, 100-240V AC, 12V 6.2 A, Single Phase, Optimized
Schneider
SKU
SE_ABLS1A12062
Model
ABLS1A12062
SGD $126.44 All prices inclusive of GST
Short description of ABLS1A12062
ABLS1A12062. POWER SUPPLY 12V 6.2A 1PH OPTIMIZED
Country of Origin
Thailand
MAIN SPECIFICATIONS | |
---|---|
Physical Interface | 12 V DC |
Power Supply Output Current | 6.25 A |
Pressure Sensor Size | 6.25 A |
Pressure Sensor Type | 75 W |
Product Or Component Type | power supply |
Range Of Product | Modicon Power Supply |
Rated Power In W | 75 W |
Enclosure Material | plastic |
Mounting Support | double-profile DIN rail top hat type TH35-15 rail conforming to IEC 60715 top hat type TH35-7.5 rail conforming to IEC 60715 |
Power Supply Type | regulated switch mode |
Range Name | Phaseo ABL7, ABL8 |
COMPLEMENTARY | |
Input Voltage | 100...240 V AC 2 phases 100...240 V AC single phase 140...340 V DC |
Output Voltage | 12 V DC |
Connections - Terminals | screw connection: 0.5...2.5 mm², (AWG 20...AWG 14) for output screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) for input |
Current Consumption | < 0.8 A 140 V DC < 1 A 230 V AC < 1.8 A 115 V AC |
Depth | 102 mm |
Earthing System | IT TN TT |
Efficiency | 87 % at 230 V AC |
Height | 123.6 mm |
Holding Time | > 20 ms 115 V AC > 40 ms 230 V AC |
Input Protection Type | external protection (recommended) 10 A Curve C external protection (recommended) 13 A Curve B external protection (recommended) 20 A Curve C integrated fuse (not interchangeable) 5 A |
Input Voltage Limits | 120...375 V DC (without temperature derating) 85...264 V AC (without temperature derating) 85…120 V DC (with temperature derating) |
Inrush Current | 40.0 A at 115 V 80.0 A at 230 V |
Line And Load Regulation | < 0.5 % network 0 to 100 % load at 25 °C < 1 % network full voltage range in line at 25 °C |
Load Capacitance | 5000 µF |
Maximum Leakage Current | 1 mA 240 V AC |
Meantime Between Failure [MTBF] | 700000 h at 25 °C, full load conforming to SR 332 |
Net Weight | 0.22 kg |
Network Frequency Limits | 50-60 Hz |
Output Coupling | parallel serial |
Output Protection Type | against over temperature, protection technology: manual reset against overload and short-circuits, protection technology: automatic reset against overvoltage, protection technology: manual reset |
Output Voltage Limits | 11...14 V |
Power Dissipation In W | 16 W |
Power Factor | 0.45 at 230 V AC 0.55 at 115 V AC |
Residual Ripple | < 120 mV |
Response Time | < 1.2 s |
Service Life | 10 year(s) |
Status LED | 1 LED (green)output voltage |
Supply | SELV conforming to EN/IEC 60204-1 SELV conforming to EN/IEC 60950-1 SELV conforming to IEC 60364-4-41 |
Variant Option | optimized |
Width | 27 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -10-40 °C without derating mounting position A 115V AC < 2000 m -10-50 °C without derating mounting position A 230V AC < 2000 m -20--10 °C with current derating of 1 % per °C mounting position A < 2000 m 40-70 °C with current derating of 1.67 % per °C mounting position A 115V AC < 2000 m 50-70 °C with current derating of 2.5 % per °C mounting position A 230V AC < 2000 m |
Dielectric Strength | 3000 V AC with input to output |
Electrical Shock Protection Class | class I |
Electromagnetic Compatibility | conducted disturbance emission conforming to EN 55016-1-2 conducted disturbance emission conforming to EN 55016-2-1 disturbing field emission conforming to EN 55016-2-3 immunity to conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6 immunity to conducted RF disturbances - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3 immunity to conducted RF disturbances - test level: 3 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3 immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3 immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2 immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/IEC 61000-4-2 immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4 immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8 immunity to voltage dips conforming to EN/IEC 61000-4-11 limits for harmonic current emissions conforming to EN 61000-3-2 surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5 surge immunity test - test level: 3 kV (between power supply and earth) conforming to EN/IEC 61000-4-5 |
Electromagnetic Emission | conducted emissions conforming to EN 61000-6-3 radiated emissions conforming to EN 61000-6-4 |
Environmental Characteristic | 3M4 conforming to IEC 60721-3-3 |
IP Degree Of Protection | IP20 |
Operating Altitude | < 5000 m |
Pollution Degree | 2 |
Product Certifications | CB Scheme CE cUL listed cUL recognized EAC KC NEC: class 2 RCM |
Shock Resistance | 100 m/s² for 11 ms |
Standards | CSA C22.2 No 61010-1 CSA C22.2 No 61010-2-201 CSA C22.2 No 62368-1 EN 61000-3-2 EN 61000-3-3 EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 61010-2-201 EN 62368-1 EN/IEC 61010-1 EN/IEC 61204-3 EN/IEC 62368-1 UL 61010-1 UL 61010-2-201 UL 62368-1 |
Vibration Resistance | 10 m/s² (f= 9-200 Hz) conforming to IEC 60068-2-6 3 mm (f= 2-9 Hz) conforming to IEC 60068-2-6 |
OTHER | |
Poles Description | power supply |
[Us] Rated Supply Voltage | Modicon Power Supply |
Write Your Own Review