A9R51440 Acti9 IID - RCCB - 4P - 40A - 30mA - Type A
Short description of A9R51440
DIN Rail Residual current circuit breakers (RCCB) up to 100 A
This Acti9 iID is a modular and reliable residual current circuit breaker (RCCB). It is a 4P circuit breaker with 40A In rated current, a sensitivity of 30mA with a A type protection class. This product protects against electrical shock by direct or indirect contact and fire hazards. It performs the function of disconnection of electrical circuits in case of earth fault. Its unique Visitrip indicator reduces intervention time by showing the faulty device with a mechanical indicator on front face. This product also has a VisiSafe window with a green strip on the toggle indicating full opening of the poles allowing downstream maintenance This product is compliant with EN/IEC 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 1500A. The (Inc/IΔc) conditional rated short circuit current is 10kA. The mechanical endurance is going up to 20000 cycles and electrical endurance going up to 15000 cycles. The Ue operational voltage is 380VAC to 415VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is white (RAL9003). The dimensions are (W) 72mm x (H) 91mm x (D) 73.5mm. The weight is 0.37kg. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 85°C.
-  product name : Acti 9 iID
-  product or component type : Residual current circuit breaker (RCCB)
-  device short name : IID
-  poles description : 4P
-  neutral position : Left
-  [In] rated current : 40 A
-  network type : AC
-  earth
- leakage sensitivity : 30 mA
-  earth
- leakage protection time delay : Instantaneous
-  earth
- leakage protection class : Type A
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Contacts Type And Composition | 40 A |
Control Type | toggle |
Product Or Component Type | residual current circuit breaker (RCCB) |
Range Of Product | iID |
[Ie] Rated Operational Current | toggle |
[Ue] Rated Operational Voltage | 380...415 V AC 50/60 Hz |
Device Short Name | iID |
Earth-leakage Protection Class | type A |
Earth-leakage Protection Time Delay | instantaneous |
Mounting Support | DIN rail |
Network Type | AC |
Neutral Position | left |
Range | Acti 9 |
Range Name | Acti 9 iID |
COMPLEMENTARY | |
Communication Network Type | 380...415 V AC 50/60 Hz |
Product Name | Acti9 iID |
[In] Rated Current | 40 A |
9 Mm Pitches | 8 |
Colour | white |
Comb Busbar And Distribution Block Compatibility | top or bottom: tooth |
Compatibility Code | iID |
Connections - Terminals | single terminal top or bottom 1-25 mm² flexible single terminal top or bottom 1-25 mm² flexible with ferrule single terminal top or bottom 1-35 mm² rigid |
Contact Position Indicator | yes |
Depth | 73.5 mm |
Device Location In System | outgoer |
Earth-leakage Sensitivity | 30 mA |
Electrical Durability | AC-1: 15000 cycles |
Height | 91 mm |
Locking Options Description | padlocking device |
Mechanical Durability | 20000 cycles |
Mounting Mode | clip-on |
Net Weight | 0.37 kg |
Network Frequency | 50/60 Hz |
Rated Breaking And Making Capacity | Idm 1500 A Im 1500 A |
Rated Conditional Short-circuit Current | 10 kA |
Residual Current Tripping Technology | voltage independent |
Surge Current | 250 A |
Tightening Torque | 3.5-3.5 N.m top or bottom |
Width | 72 mm |
Wire Stripping Length | 14 mm for top or bottom connection |
[Uimp] Rated Impulse Withstand Voltage | 6 kV |
[Ui] Rated Insulation Voltage | 500 V AC 50/60 Hz |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-60 °C |
Ambient Air Temperature For Storage | -40-85 °C |
Electromagnetic Compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 |
IP Degree Of Protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
Pollution Degree | 3 |
Standards | EN/IEC 61008-1 |
OTHER | |
Poles Description | 4P |
[Us] Rated Supply Voltage | iID |