TM221CE16R - Logic Controller, Modicon M221, 16 IO Relay Ethernet.
Short description of TM221CE16R
This product is part of the Modicon M221 range, an offer of programmable logic controllers for hardwired architectures. This logic controller provides 9 discrete inputs and 7 relay ethernet outputs with 10bit input resolution, normally opened relay output. It is a Modicon logic controller with a rated supply voltage of 100V to 240V AC, an output voltage of 5V to 125V DC, 5V to 250V AC and an output current of 2A with sink or source input logic. This product requires minimal installation and offers tremendous versatility. Integrated connections are USB port with mini B USB 2.0 connector, non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface and ethernet with RJ45 connector. It is a Modicon M221 controller with a network frequency of 50/60Hz, 256KB for internal variables RAM, user application and data RAM, a built-in flash memory of 256KB and a SD card memory capacity of 2GB. It is an IP20 rated product. Its dimensions are 95mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.346kg. This product is certified by CE, IACS E10, RCM, ABS, LR, DNV-GL, CSA, EAC and CULus. It meets EN/IEC 60664-1, EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. It supports DIN rail mount. Achieve benchmark performance while increasing profitability with the Modicon M221 through intuitive machine programming with SoMachine Basic, ready-to-use applications and function blocks.
-  product or component type : Logic controller
-  [Us] rated supply voltage : 100...240 V AC
-  discrete input number : 9, discrete input conforming to IEC 61131-2 Type 1
-  analogue input number : 2 at 0...10 V
-  discrete output type : Relay normally open
-  discrete output number : 7 relay
-  discrete output voltage : 5...125 V DC5...250 V AC
-  discrete output current : 2 A
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 2 at 0...10 V |
Analogue Input Range | 2 at 0...10 V |
Breaking Capacity | 10BASE-T/100BASE-TX 1 port with 100 m copper cable |
Discrete Input Number | 9 , discrete input conforming to IEC 61131-2 Type 1 |
Discrete Output Type | relay normally open |
Power Supply Output Current | 0.12-0.12 A 24 V for expansion bus 0.325-0.325 A 5 V for expansion bus |
Pressure Sensor Size | 0.12-0.12 A 24 V for expansion bus 0.325-0.325 A 5 V for expansion bus |
Product Or Component Type | logic controller |
Range Of Product | Modicon M221 |
Web Server | 256 kB for internal variables RAM 256 kB for user application and data RAM with 10000 instructions |
Analogue Input Resolution | 10 bits |
Communication Port Protocol | Ethernet non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network USB port: USB - SoMachine-Network |
Discrete Input Voltage | 24 V |
Discrete Output Voltage | 5...125 V DC 5...250 V AC |
Mounting Support | plate or panel with fixing kit top hat type TH35-15 rail conforming to IEC 60715 top hat type TH35-7.5 rail conforming to IEC 60715 |
Range Name | Logic Controller - Modicon M221 |
COMPLEMENTARY | |
Analogue Input Type | 9 , discrete input conforming to IEC 61131-2 Type 1 |
Discrete Output Number | 7 relay |
Memory Capacity | 256 kB for internal variables RAM 256 kB for user application and data RAM with 10000 instructions |
Port Ethernet | 10BASE-T/100BASE-TX 1 port with 100 m copper cable |
[Ics] Rated Service Breaking Capacity | relay normally open |
Absolute Accuracy Error | +/- 1 % of full scale for analog input |
Backup Time | 1 year at 25 °C (by interruption of power supply) |
Battery Type | BR2032 lithium non-rechargeable, battery life: 4 year(s) |
Clock Drift | <= 30 s/month at 25-25 °C |
Communication Service | DHCP client Ethernet/IP adapter Modbus TCP client Modbus TCP server Modbus TCP slave device |
Configurable Filtering Time | 0 ms for input 12 ms for input 3 ms for input |
Control Signal Type | A/B pulse/direction single phase |
Conversion Time | 1 ms per channel + 1 controller cycle time for analogue input analog input |
Counting Input Number | 4 fast input (HSC mode) at 100 kHz 32 bits |
Data Backed Up | 256 kB built-in flash memory for backup of application and data |
Data Storage Equipment | 2 GB SD card (optional) |
Depth | 70 mm |
Discrete I/O Number | 16 |
Discrete Input Current | 5 mA for fast input 7 mA for discrete input |
Discrete Input Logic | sink or source (positive/negative) |
Discrete Input Voltage Type | DC |
Discrete Output Current | 2 A |
Electrical Connection | connector, 4 terminal(s) for analogue inputs removable screw terminal block for inputs removable screw terminal block for outputs terminal block, 3 terminal(s) for connecting the 24 V DC power supply mini B USB 2.0 connector for a programming terminal |
Electrical Durability | 100000 cycles AC-12, 120 V, 240 VA, resistive 100000 cycles AC-12, 240 V, 480 VA, resistive 100000 cycles AC-14, cos phi = 0.7 , 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7 , 240 V, 240 VA, inductive 100000 cycles AC-15, cos phi = 0.35 , 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35 , 240 V, 120 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 300000 cycles AC-14, cos phi = 0.7 , 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7 , 240 V, 72 VA, inductive 300000 cycles AC-15, cos phi = 0.35 , 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35 , 240 V, 36 VA, inductive 300000 cycles DC-12, 24 V, 16 W, resistive 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms) |
Exct Time For Event Task | 60 µs response time |
Execution Time For 1 KInstruction | 0.3 ms for event and periodic task |
Execution Time Per Instruction | 0.2 µs Boolean |
Height | 90 mm |
Immunity To Microbreaks | 10 ms |
Input Impedance | 100 kOhm for analog input 3.4 kOhm for discrete input 4.9 kOhm for fast input |
Inrush Current | 40 A |
Insulation | between Ethernet terminal and internal logic at 500 V AC between input and ground at 500 V AC between input and internal logic at 500 V AC between output and ground at 1500 V AC between output and internal logic at 2300 V AC between sensor power supply and ground at 500 V AC between sensor power supply and internal logic at 500 V AC between supply and ground at 1500 V AC between supply and internal logic at 2300 V AC between supply and sensor power supply at 2300 V AC non-insulated between analogue input and internal logic non-insulated between analogue inputs |
Integrated Connection Type | Ethernet with RJ45 connector non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface USB port with mini B USB 2.0 connector |
Local Signalling | 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (green) for SD card access (SD) 1 LED (green) for SL 1 LED (red) for BAT 1 LED (red) for module error (ERR) 1 LED per channel (green) for I/O state Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status) |
LSB Value | 10 mV |
Marking | CE |
Maximum Cable Distance Between Devices | shielded cable: <10 m for fast input unshielded cable: <1 m for analog input unshielded cable: <30 m for digital input unshielded cable: <30 m for output |
Maximum Current Per Output Common | 6 A at COM 1 7 A at COM 0 |
Maximum Number Of I/O Expansion Module | 4 for relay output 4 for transistor output |
Maximum Power Consumption In VA | 33 VA at 100...240 V without I/O expansion module 49 VA at 100...240 V with max number of I/O expansion module |
Maximum Size Of Object Areas | 255 %C counters 255 %TM timers 512 %KW constant words 512 %M memory bits 8000 %MW memory words |
Mechanical Durability | 20000000 cycles for relay output |
Minimum Load | 1 mA at 5 V DC for relay output |
Net Weight | 0.346 kg |
Network Frequency | 50/60 Hz |
Output Voltage Limits | 125 V DC 277 V AC |
Permitted Overload On Inputs | +/- 13 V DC (permanent) for analog input +/- 30 V DC for 5 min (maximum) for analog input |
Protection Type | without protection at 5 A |
Realtime Clock | with |
Reset Time | 1 s |
Response Time | 10 ms turn-off for output 10 ms turn-on for output 100 µs turn-off, other terminals terminal(s) for input 35 µs turn-off, I2...I5 terminal(s) for input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input |
Sensor Power Supply | 24-24 V DC at 250 mA supplied by the controller |
Supply | (serial)serial link supply: 5 V, <200 mA |
Supply Voltage Limits | 85-264 V |
Surge Withstand | 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 |
Switching Frequency | 20 switching operations/minute with maximum load |
Transmission Rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15-15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3-3 m for RS232 480 Mbit/s for USB |
Voltage State 0 Guaranteed | <= 5 V for input |
Voltage State 1 Guaranteed | >= 15 V for input |
Width | 95 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -10-35 °C (vertical installation) -10-55 °C (horizontal installation) |
Ambient Air Temperature For Storage | -25-70 °C |
Electromagnetic Emission | conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10-150 kHz conforming to EN/IEC 55011 conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5-30 MHz conforming to EN/IEC 55011 conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5-300 MHz conforming to EN/IEC 55011 conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15-0.5 MHz conforming to EN/IEC 55011 conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150-1500 kHz conforming to EN/IEC 55011 radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30-230 MHz conforming to EN/IEC 55011 radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200-1000 MHz conforming to EN/IEC 55011 |
Environmental Characteristic | ordinary and hazardous location |
IP Degree Of Protection | IP20 with protective cover in place |
Operating Altitude | 0...2000 m |
Pollution Degree | <= 2 |
Product Certifications | ABS CSA cULus DNV-GL EAC IACS E10 LR RCM |
Regulation Loop | adjustable PID regulator up to 14 simultaneous loops |
Relative Humidity | 10-95 %, without condensation (in operation) 10-95 %, without condensation (in storage) |
Resistance To Conducted Disturbances | 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL) |
Resistance To Electromagnetic Fields | 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 |
Resistance To Electrostatic Discharge | 4 kV on contact conforming to EN/IEC 61000-4-2 8 kV in air conforming to EN/IEC 61000-4-2 |
Resistance To Fast Transients | 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 |
Resistance To Magnetic Fields | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
Shock Resistance | 98 m/s² for 11 ms |
Standards | EN/IEC 60664-1 EN/IEC 61010-2-201 EN/IEC 61131-2 |
Vibration Resistance | 1 gn at 8.4-150 Hz on panel mounting 1 gn at 8.4-150 Hz on symmetrical rail 3.5 mm at 5-8.4 Hz on panel mounting 3.5 mm at 5-8.4 Hz on symmetrical rail |
ENVIRONMENTAL | |
Storage Altitude | 0-3000 m |
OTHER | |
Poles Description | logic controller |
[Us] Rated Supply Voltage | 100...240 V AC |