RM35BA10 - Pump Control Relay RM35-BA - Range 1..10 A
Schneider
SKU
SE_RM35BA10
Model
RM35BA10
Obsolete
Short description of RM35BA10
RM35BA10. PUMP CNTRL RELAY 1PH/3PH 10A 208-480VAC
Obsolete
pump control relay RM35-BA
-  range 1..10 A.
Label :  Zelio Control
-  range of product :  Zelio Control
-  switching capacity in VA :  1250 VA
-  minimum switching current :  10 mA at 5 V DC
-  maximum switching current :  5 A AC/DC
-  maximum power consumption in VA :  5 VA AC
-  product or component type :  modular measurement and control relays
-  measurement range :  1...10 A AC
-  relay type :  pump control relays
-  product specific application :  for 3-phase and single-phase pump
-  relay name :  RM35BA
-  relay monitored parameters :  overcurrent and undercurrent control,phase sequence on 3-phase supply,phase failure on 3-phase supply
-  utilisation category :  AC
- 12 conforming to IEC 60947-5-1, AC
- 13 conforming to IEC 60947-5-1, AC
- 14 conforming to IEC 60947-5-1, AC
- 15 conforming to IEC 60947-5-1, DC
- 12 conforming to IEC 60947-5-1, DC
- 13 conforming to IEC 60947-5-1
-  time delay type :  adjustable 1...60 s, +/- 10 % Ti on energisation, fixed 0.3 s reset on terminal Y2, adjustable 0.1...10 s, +/- 10 % Tt on crossing the threshold
-  Range Presentation :  They can monitor power supplies (phases, voltage, current, frequency) to protect motors and other equipment or control physical values such as level, speed and temperature.
-  Phase control relay Detects all possible faults occurring in the phases
-  Voltage & current control relays Ensure your equipment is powered with proper values
-  Frequency control relay Monitors frequency variation from your power generation set
-  Level control relay Filling or emptying, adapts to all kinds of materials
-  Pump control relay Controls and protects your pump from dry running or overloading
-  Speed control relay Picks up the improper rhythm of your process
-  Temperature control relay for lift application Dedicated to lift temperature monitoring (EN81)
-  Temperature control relays Dedicated to temperature regulation (heating, cooling or heating/cooling of processes)
-  Range Benefits :  Monitoring of your equipmentSimple and accurate adjustments are a sure-fire way to achieve quick and easy setup. These relays can satisfy all the monitoring requirements of mobile process control or network equipment.
-  Range Application Presentation : 
-  Industry and domestic :  switchboards in simple machines, motors and process monitoring
-  Start-up and monitoring of water treatment equipment
-  Packaging, textile, HVAC
-  range 1..10 A.
Label :  Zelio Control
-  range of product :  Zelio Control
-  switching capacity in VA :  1250 VA
-  minimum switching current :  10 mA at 5 V DC
-  maximum switching current :  5 A AC/DC
-  maximum power consumption in VA :  5 VA AC
-  product or component type :  modular measurement and control relays
-  measurement range :  1...10 A AC
-  relay type :  pump control relays
-  product specific application :  for 3-phase and single-phase pump
-  relay name :  RM35BA
-  relay monitored parameters :  overcurrent and undercurrent control,phase sequence on 3-phase supply,phase failure on 3-phase supply
-  utilisation category :  AC
- 12 conforming to IEC 60947-5-1, AC
- 13 conforming to IEC 60947-5-1, AC
- 14 conforming to IEC 60947-5-1, AC
- 15 conforming to IEC 60947-5-1, DC
- 12 conforming to IEC 60947-5-1, DC
- 13 conforming to IEC 60947-5-1
-  time delay type :  adjustable 1...60 s, +/- 10 % Ti on energisation, fixed 0.3 s reset on terminal Y2, adjustable 0.1...10 s, +/- 10 % Tt on crossing the threshold
-  Range Presentation :  They can monitor power supplies (phases, voltage, current, frequency) to protect motors and other equipment or control physical values such as level, speed and temperature.
-  Phase control relay Detects all possible faults occurring in the phases
-  Voltage & current control relays Ensure your equipment is powered with proper values
-  Frequency control relay Monitors frequency variation from your power generation set
-  Level control relay Filling or emptying, adapts to all kinds of materials
-  Pump control relay Controls and protects your pump from dry running or overloading
-  Speed control relay Picks up the improper rhythm of your process
-  Temperature control relay for lift application Dedicated to lift temperature monitoring (EN81)
-  Temperature control relays Dedicated to temperature regulation (heating, cooling or heating/cooling of processes)
-  Range Benefits :  Monitoring of your equipmentSimple and accurate adjustments are a sure-fire way to achieve quick and easy setup. These relays can satisfy all the monitoring requirements of mobile process control or network equipment.
-  Range Application Presentation : 
-  Industry and domestic :  switchboards in simple machines, motors and process monitoring
-  Start-up and monitoring of water treatment equipment
-  Packaging, textile, HVAC
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 208...480 V AC 3 phases 230 V AC 1 phase 230 V AC single phase |
Contacts Type And Composition | 1 C/O |
Discrete Input Number | 1 C/O |
Measurement Accuracy | +/- 10 % of the full scale value |
Product Or Component Type | pump control relay |
Range Of Product | Harmony Control Relays |
[Uc] Control Circuit Voltage | 208...480 V 230 V |
EAN13 | 3389119405195 |
Measurement Range | 1...10 A AC |
Mounting Support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
Product Specific Application | for 3-phase and single-phase pump |
Range Name | Zelio Control |
Relay Monitored Parameters | overcurrent and undercurrent control phase failure on 3-phase supply phase sequence on 3-phase supply |
Relay Name | RM35BA |
Relay Type | pump control relays |
Time Delay Type | adjustable 0.1...10 s, +/- 10 % Tt on crossing the threshold adjustable 1...60 s, +/- 10 % Ti on energisation fixed 0.3 s reset on terminal Y2 |
Utilisation Category | AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
COMPLEMENTARY | |
Output Contacts | 1 C/O |
System Requirements | 1 C/O |
Time Delay | +/- 10 % of the full scale value |
[In] Rated Current | 5 A |
Compatibility Code | RM3 |
Connections - Terminals | screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw connectors |
Control Circuit Voltage Limits | - 15 % + 10 % Un |
Electrical Durability | 100000 cycles |
Housing Material | self-extinguishing plastic |
Hysteresis | 5-5 % of threshold |
Immunity To Microbreaks | 500 ms |
Input Current | 11 A permanent at 25 °C E1-L2 terminals 50 A non repetitive < 1 s at 25 °C E1-L2 terminals |
Insulation Resistance | > 1 MOhm at 500 V DC between supply and measurement conforming to 60255-5 > 1 MOhm at 500 V DC between supply and measurement conforming to 60664-1 > 500 MOhm at 500 V DC between measurement and relay output conforming to 60255-5 > 500 MOhm at 500 V DC between measurement and relay output conforming to 60664-1 > 500 MOhm at 500 V DC between supply and relay output conforming to 60255-5 > 500 MOhm at 500 V DC between supply and relay output conforming to 60664-1 |
Marking | CE : 73/23/EEC CE : EMC 89/336/EEC |
Maximum Measuring Cycle | 140 ms as true rms value |
Maximum Power Consumption In VA | 5 VA AC |
Maximum Switching Current | 5 A AC/DC |
Maximum Switching Voltage | 250 V AC/DC |
Measurement Error | +/- 0.05 %/°C 1 % by volt over the whole range |
Mechanical Durability | 30000000 cycles |
Minimum Switching Current | 10 mA at 5 V DC |
Nominal Output Current | 5 A |
Operating Position | any position |
Operating Rate | <= 360 operations/hour full load |
Repeat Accuracy | +/- 1 % for input and measurement circuit +/- 1 % for time delay |
Reset Time | 2000 ms |
Resistance Across Terminals | 0.01 Ohm at E1-L2 terminals |
Response Time | < 300 ms (in the event of a fault) |
Run-up Delay At Power-up | 0.5 s |
Status LED | 1 LED green for power ON 1 LED yellow for fault 1 LED yellow for relay ON |
Supply Frequency | 50/60 Hz +/- 10 % |
Supply Voltage Limits | 183-528 V AC |
Switching Capacity In VA | 1250 VA |
Tightening Torque | 0.6-1 N.m conforming to IEC 60947-1 |
Width | 35 mm |
[Ui] Rated Insulation Voltage | 400 V conforming to IEC 60664-1 |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -20-50 °C |
Ambient Air Temperature For Storage | -40-70 °C |
Dielectric Strength | 2 kV AC 50 Hz (shock wave 4 kV) |
Electromagnetic Compatibility | emission standard for industrial environments conforming to EN/IEC 61000-6-4 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
IP Degree Of Protection | IP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529 |
Overvoltage Category | III conforming to IEC 60664-1 |
Pollution Degree | 3 conforming to IEC 60664-1 |
Product Certifications | CSA C-Tick GL GOST UL |
Relative Humidity | 95-95 % at 55-55 °C conforming to IEC 60068-2-30 |
Shock Resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
Standards | EN/IEC 60255-6 |
Vibration Resistance | 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 |
OTHER | |
Poles Description | pump control relay |
[Us] Rated Supply Voltage | 208...480 V AC 3 phases 230 V AC 1 phase 230 V AC single phase |