Short description of MVS22143

High current air circuit breakers up to 4000 A
Country of Origin
India
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 4 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
range of product : EasyPact MVS
-  range : EasyPact
-  product or component type : Circuit breaker
-  device application : Distribution
-  poles description : 3P
-  protected poles description : 3P 3d
-  network type : AC
-  breaking capacity code : H
-  suitability for isolation : Yes conforming to IEC 60947-2
-  utilisation category : Category B

This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS
Breaking Capacity50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity CodeH
Contacts Type And Composition1250 A at 40 °C
Control Typepush-button
Product Or Component Typecircuit breaker
Range Of ProductEasyPact MVS
[Ie] Rated Operational Currentpush-button
[Ue] Rated Operational Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Mounting Supportbase plate
Network TypeAC
Protected Poles Description3P 3d
RangeEasyPact
Range NameEasyPact MVS
Suitability For Isolationyes conforming to IEC 60947-2
Utilisation Categorycategory B
COMPLEMENTARY
Communication Network Type690 V AC 50/60 Hz conforming to IEC 60947-2
Current Transformer TypeH
Interlocked Device50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] Rated Service Breaking Capacity50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[In] Rated Current1250 A at 40 °C
Circuit Breaker CT Rating1250 A
Compatibility CodeMVS12H
Connection Pitch115 mm without spreader
Connection Positionhorizontal
vertical
Contact Position Indicatoryes
Depth297 mm
Device Applicationdistribution
Electrical Durabilitycategory B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Height352 mm
Location Of Connectionrear
Maximum Breaking Time25 ms
Maximum Closing Response Time70 ms
Mechanical Durability10000 cycles (without maintenance) conforming to IEC 60947-2
20000 cycles (with maintenance) conforming to IEC 60947-2
Mounting Modefixed
Net Weight40 kg
Network Frequency50/60 Hz
Width422 mm
[Icm] Rated Short-circuit Making Capacity105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] Rated Short-time Withstand Current36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage12 kV conforming to IEC 60947-2
[Ui] Rated Insulation Voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
ENVIRONMENT
Ambient Air Temperature For Operation-5-60 °C
Ambient Air Temperature For Storage-25-85 °C with control unit
-40-85 °C without control unit
IP Degree Of ProtectionIP40
Pollution Degree4 conforming to IEC 60664-1
Product CertificationsCCC
CCS
GOST
IEC
StandardsIEC 60947-2
OTHER
Poles Description3P