METSEPM2110 - EasyLogic PM2110, Power & Energy Meter, Total Harmonic, LED, Pulse, Class 1
Schneider
SKU
SE_METSEPM2110
Model
METSEPM2110
SGD $344.66 All prices inclusive of GST
Short description of METSEPM2110
METSEPM2110. EasyLogic VAF P & E meter THD POP CL 1
Country of Origin
India
EasyLogic PM2110
-  Power & Energy meter
-  Total Harmonic
-  7S
-  Pulse
-  class 1.
Label :  EasyLogic PM2000 series
-  range :  EasyLogic
-  product name :  EasyLogic PM2100
-  device short name :  PM2110
-  product or component type :  power meter
-  Range Presentation :  The EasyLogic PM2000 series energy and power meters provide all the measurement capabilities required to monitor an electrical installation in a single 96x96 mm unit. Two variants are available with LED and LCD display options.
-  Range Benefits :  The easy choice...
-  for quality
-  Designed and manufactured in ISO
- certified Schneider Electric facilities
-  for value
-  The right balance of features and price
-  for peace of mind
-  Reliable performance where you need itLeaner, more efficient order management thanks to field settable CT or PT ratios, modularity
Fast and efficient installation & commissioning
Safety marks for CE and UL compliance in accordance with latest IEC/UL 61010-1 Ed
- 3 standard
-  Range Application Presentation :  Cost management application
-  Electrical installation remote monitoring
-  Energy accounting, balancing, and management
-  Tenant and sub
- billing
-  Panel instrumentationNetwork management applications
-  Power quality analysis of THD and individual harmonics up to 15th and 31st order for Volts and Amps, per
- phase
-  Measurement of True PF and Displacement PF
-  Recording Min/Max values of instantaneous parameters with date & timestamp
-  Calculates % unbalance for voltage & current
-  Load management by simultaneous display of peak demands of all the four demand parameters (W, VA, VAR, Amps) with date and time of occurrence
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
-  Power & Energy meter
-  Total Harmonic
-  7S
-  Pulse
-  class 1.
Label :  EasyLogic PM2000 series
-  range :  EasyLogic
-  product name :  EasyLogic PM2100
-  device short name :  PM2110
-  product or component type :  power meter
-  Range Presentation :  The EasyLogic PM2000 series energy and power meters provide all the measurement capabilities required to monitor an electrical installation in a single 96x96 mm unit. Two variants are available with LED and LCD display options.
-  Range Benefits :  The easy choice...
-  for quality
-  Designed and manufactured in ISO
- certified Schneider Electric facilities
-  for value
-  The right balance of features and price
-  for peace of mind
-  Reliable performance where you need itLeaner, more efficient order management thanks to field settable CT or PT ratios, modularity
Fast and efficient installation & commissioning
Safety marks for CE and UL compliance in accordance with latest IEC/UL 61010-1 Ed
- 3 standard
-  Range Application Presentation :  Cost management application
-  Electrical installation remote monitoring
-  Energy accounting, balancing, and management
-  Tenant and sub
- billing
-  Panel instrumentationNetwork management applications
-  Power quality analysis of THD and individual harmonics up to 15th and 31st order for Volts and Amps, per
- phase
-  Measurement of True PF and Displacement PF
-  Recording Min/Max values of instantaneous parameters with date & timestamp
-  Calculates % unbalance for voltage & current
-  Load management by simultaneous display of peak demands of all the four demand parameters (W, VA, VAR, Amps) with date and time of occurrence
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 44...277 V AC 45...65 Hz +/- 10 % 44...277 V DC +/- 10 % |
Contacts Type And Composition | 1 A 5 A |
Control Type | 3 x button |
Display Type | 7 segments LED |
Measurement Accuracy | active energy +/- 1 % active power +/- 1 % apparent power +/- 1 % current +/- 0.5 % frequency +/- 0.05 % power factor +/- 0.01 reactive energy +/- 1 % voltage +/- 0.5 % |
Physical Interface | pulse: 20 ms (5...40 V DC, 20 mA max)1...9999000 pulse/ k_h (kWh, kVAh, kVARh) |
Pixel Resolution | red |
Product Or Component Type | power meter |
[Ie] Rated Operational Current | 3 x button |
Communication Port Protocol | POP |
Device Short Name | PM2110 |
EAN13 | 3606480800139 |
Mounting Support | framework |
Power Quality Analysis | total harmonic distortion |
Range | EasyLogic |
Range Name | PM2000 series |
Type Of Measurement | active and reactive energy total active and reactive power total apparent energy total apparent power total current average frequency average power factor average total current harmonic distortion THD (I) per phase total voltage harmonic distortion THD (U) per phase voltage average |
COMPLEMENTARY | |
Analogue Input Type | current (impedance <= 0.3 mOhm) voltage (impedance > 5 MOhm) |
Analogue Output Number | 7 segments LED |
Display Colour | red |
Output Voltage | pulse: 20 ms (5...40 V DC, 20 mA max)1...9999000 pulse/ k_h (kWh, kVAh, kVARh) |
Product Name | EasyLogic PM2100 |
Time Delay | active energy +/- 1 % active power +/- 1 % apparent power +/- 1 % current +/- 0.5 % frequency +/- 0.05 % power factor +/- 0.01 reactive energy +/- 1 % voltage +/- 0.5 % |
[In] Rated Current | 1 A 5 A |
Accuracy Class | class 1 active energy conforming to IEC 62053-21 class 1 reactive energy conforming to IEC 62053-24 |
Communication Service | remote monitoring |
Compatibility Code | PM2110 |
Connections - Terminals | current transformer: screw connection (bottom) 6 voltage inputs: screw connection (top) 4 |
Cybersecurity | enable/disable communication ports |
Depth | 61.64 mm embedded: 76.09 mm total: |
Device Application | power monitoring sub billing |
Display Digits | 12 digit(s) - 14.2 mm in height |
Electrical Insulation Class | class II double insulation |
Flame Retardance | V-0 conforming to UL 94 |
Frequency Measurement Range | 45-65 Hz |
Height | 96 mm |
Impulse Duration | 20 ms |
Information Displayed | active power apparent power current demand current (past value) demand current (present value) demand power (past value) demand power (present value) energy consumption frequency harmonic distortion power factor reactive power unbalanced in % voltage |
Local Signalling | green LED: module operating (RUN) red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) |
Material | polycarbonate |
Maximum Power Consumption In VA | 6 VA at 277 V AC |
Maximum Power Consumption In W | 2 W at 277 V (power lines (DC)) 3.3 W (power lines (AC)) |
Measurement Current | 5-6000 mA |
Measurement Voltage | 20-277 V AC 50/60 Hz between phase and neutral 35-480 V AC 50/60 Hz between phases 480-999000 V AC 50/60 Hz with external VT |
Metering Type | active power P, P1, P2, P3 active, reactive, apparent energy (signed, four quadrant) apparent power S, S1, S2, S3 calculated neutral current current I, I1, I2, I3 demand power P, Q, S peak demand currents peak demand power PM, QM, SM reactive power Q, Q1, Q2, Q3 unbalance current voltage U, U21, U32, U13, V, V1, V2, V3 |
Mounting Mode | clip-on |
Mounting Position | vertical |
Net Weight | 300 g |
Network Frequency | 50 Hz 60 Hz |
Number Of Outputs | 1 pulse |
Provided Equipment | 1 x installation guide |
Refresh Time | configurable from 1 to 60 min |
Sampling Rate | 64 samples/cycle |
Service Life | 7 year(s) |
Tamperproof Of Settings | protected by access code |
Width | 96 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -10-60 °C |
Ambient Air Temperature For Storage | -25-70 °C |
Electromagnetic Compatibility | conducted RF disturbances conforming to IEC 61000-4-6 electrical fast transient/burst immunity test conforming to IEC 61000-4-4 electrostatic discharge conforming to IEC 61000-4-2 emission tests conforming to FCC part 15 class A magnetic field at power frequency conforming to IEC 61000-4-8 radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 surge immunity test conforming to IEC 61000-4-5 voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
IP Degree Of Protection | IP30 body: conforming to IEC 60529 IP54 front: conforming to IEC 60529 |
Measurement Category | category II 480-600 V category III 480-480 V |
Messages Display Capacity | 3 fields of 4 characters |
Operating Altitude | <= 2000 m |
Overvoltage Category | III |
Pollution Degree | 2 |
Product Certifications | CE conforming to IEC 61010-1 C-Tick cULus conforming to CSA C22.2 No 61010-1 cULus conforming to UL 61010-1 EAC RCM |
Relative Humidity | 5-95 % at 50-50 °C |
OTHER | |
Poles Description | power meter |
[Us] Rated Supply Voltage | 44...277 V AC 45...65 Hz +/- 10 % 44...277 V DC +/- 10 % |
Write Your Own Review