
METSECT5GG025 - PowerLogic Split Core Current Transformer - Type GG, for Bar - 0250A / 5A.
Schneider
SKU
SE_METSECT5GG025
Model
METSECT5GG025
SGD $856.29 All prices inclusive of GST
Short description of METSECT5GG025
METSECT5GG025. Current transformers from 40A to 6000A
Country of Origin
Hungary
range : PowerLogic
-  product name : CT
-  product or component type : Current transformer
-  secondary current : 5 A
-  accuracy class : Class 1 at 1.5 VA
-  [In] rated current : 250 A
-  product name : CT
-  product or component type : Current transformer
-  secondary current : 5 A
-  accuracy class : Class 1 at 1.5 VA
-  [In] rated current : 250 A
MAIN SPECIFICATIONS | |
---|---|
Contacts Type And Composition | 250 A |
Diameter | split core standard for busbar |
Product Or Component Type | current transformer |
[Ue] Rated Operational Voltage | < 720 V 50 Hz |
Mounting Support | DIN rail fastened onto a surface with screws |
Range | PowerLogic |
Range Name | Current transformer T1 |
COMPLEMENTARY | |
Communication Network Type | < 720 V 50 Hz |
Current Transformer Type | split core standard for busbar |
Product Name | CT |
[In] Rated Current | 250 A |
Accuracy Class | class 1 at 1.5 VA |
Current Transformer Ratio | 250/5 |
Depth | 58 mm |
Electrical Insulation Class | class E |
Height | 125 mm inner: 198.15 mm outside: |
Maximum Safety Factor | 5 |
Mounting Mode | by screws |
Opening Of Bars | 80 x 120 |
Permissible Current | 15000 A during 1 s |
Secondary Current | 5 A |
Width | 155 mm outside: 85 mm inner: |
[Ith] Conventional Free Air Thermal Current | 250 A |
[Ui] Rated Insulation Voltage | 3 kV |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -5-40 °C |
Ambient Air Temperature For Storage | -25-70 °C |
Standards | DIN 42600-2 DIN EN 61869-1 DIN EN 61869-2 VDE 0414 |
OTHER | |
Poles Description | current transformer |
Write Your Own Review