Short description of LV432100

LV432100. Circuit-breakers, to protect lines carrying up to 630A
Obsolete
range : ComPact
-  range of product : ComPact NSX400...630
-  product or component type : Trip unit
-  trip unit name : Micrologic 5.3 E
-  trip unit technology : Electronic
-  range compatibility : ComPact NSX400ComPact NSX630
-  device application : Distribution
-  Number of poles : 4P
-  protected poles description : 3t + N/24t3t + OSN3t
-  neutral position : Left
-  trip unit protection functions : LSI
-  protection type : L  :  for overload protection (long time)S  :  for short time short-circuit protectionI  :  for instantaneous short-circuit protection
-  Trip unit rated current : 400 A at 40 °C
-  [Ue] rated operational voltage : 690 V AC 50/60 Hz
-  network type : AC
-  network frequency : 50/60 Hz
MAIN SPECIFICATIONS
Control Type4P
Display TypeLCD display
Product Or Component Typetrip unit
Range Of ProductComPact NSX400...630
Trip Unit NameMicrologic 5.3 E
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Network TypeAC
Neutral Positionleft
Protected Poles Description3t
3t + N/2
3t + OSN
4t
Rangecompact
Range CompatibilityComPact NSX400
ComPact NSX630
Range NameComPact NSX
Trip Unit Protection FunctionsLSI
Trip Unit Technologyelectronic
Type Of Measurementenergy meter
COMPLEMENTARY
Analogue Output NumberLCD display
Communication Network Type690 V AC 50/60 Hz
Product NameMicrologic
Communication Of Datademand current and power
energy metering
instantaneous and demand values
maintenance indicators
maximeters/minimeters
power quality
protection and alarm settings
time-stamped histories and event tables
Device Applicationdistribution
Earth-leakage Protectionwithout
Electrical Data Recordingmaintenance indicators
Instantaneous Pick-up Adjustment Range1.5...12 x In
Instantaneous Pick-up Adjustment Type Iiadjustable
Long Time Delay Adjustment Typeadjustable
Long Time Pick-up Adjustment Range160...400 A
Long Time Pick-up Adjustment Type Iradjustable 9 settings
Network Frequency50/60 Hz
Neutral Protection Setting0.5 x Ir (3t + N/2)
1 x Ir (4t)
1.6 x Ir (3t + OSN)
no protection (3t)
Protection TypeI : for instantaneous short-circuit protection
L : for overload protection (long time)
S : for short time short-circuit protection
Short-time Delay Adjustment Typeadjustable
Short-time Pick-up Adjustment Type Isdadjustable 9 settings
Thermal Memory20 minutes before and after tripping
Zone Selective Interlocking ZSIwith
[Isd] Short-time Pick-up Adjustment Range1.5...10 x Ir
[tr] Long-time Delay Adjustment Range0.35-11 s at 7.2 x Ir
0.5-16 s at 6 x Ir
15-400 s at 1.5 x Ir
[tsd] Short-time Delay Adjustment Range0.1-0.4 s I²t=on
0-0.4 s I²t=off
ENVIRONMENT
Ambient Air Temperature For Operation-25-70 °C
Ambient Air Temperature For Storage-40-85 °C
Product CertificationsCCC
EAC
Marine
StandardsEN/IEC 60947-2
UL 508
OTHER
Earth Leakage CurrentMicrologic 5.3 E
Poles Description4P
[Us] Rated Supply VoltageComPact NSX400...630