LV429762 - Circuit Breaker Compact NSX100H - MA - 25 A - 3 Poles 3d.

Schneider
SKU
SE_LV429762
Model
LV429762

Obsolete

All prices inclusive of GST

Short description of LV429762

LV429762. Circuit-breakers, to protect lines carrying up to 630A
Obsolete
range : ComPact
-  product name : ComPact NSX
-  range of product : ComPact NSX100...250
-  device short name : NSX100H
-  product or component type : Circuit breaker
-  device application : Motor
-  Number of poles : 3P
-  protected poles description : 3t
-  [In] rated current : 25 A at 65 °C
-  [Ue] rated operational voltage : 690 V AC 50/60 Hz
-  network type : AC
-  network frequency : 50/60 Hz
-  suitability for isolation : Yes conforming to EN/IEC 60947-2
-  utilisation category : Category A
-  [Icu] rated ultimate short-circuit breaking capacity : 10 kA at 600 V AC 50/60 Hz conforming to UL 50885 kA at 240 V AC 50/60 Hz conforming to UL 50865 kA at 480 V AC 50/60 Hz conforming to UL 50810 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-270 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
-  Performance level : H 70 kA 415 V AC
-  trip unit name : MA
-  trip unit technology : Magnetic
-  trip unit protection functions : I
-  control type : Toggle
-  Circuit breaker mounting mode : Fixed
MAIN SPECIFICATIONS
Breaking Capacity10 kA at 600 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 480 V AC 50/60 Hz conforming to UL 508
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 240 V AC 50/60 Hz conforming to UL 508
Breaking Capacity CodeH 70 kA 415 V AC
Contacts Type And Composition25 A at 65 °C
Control Typetoggle
Product Or Component Typecircuit breaker
Range Of ProductComPact NSX100...250
Trip Unit NameMA
[Ie] Rated Operational Currenttoggle
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Device Short NameNSX100H
Mounting Supportbackplate
Network TypeAC
Protected Poles Description3t
RangeComPact
Range NameComPact NSX
Suitability For Isolationyes conforming to EN/IEC 60947-2
Trip Unit Protection FunctionsI
Trip Unit Technologymagnetic
Utilisation Categorycategory A
COMPLEMENTARY
Communication Network Type690 V AC 50/60 Hz
Current Transformer TypeH 70 kA 415 V AC
Interlocked Device10 kA at 600 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 480 V AC 50/60 Hz conforming to UL 508
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 240 V AC 50/60 Hz conforming to UL 508
Product NameComPact NSX
[Ics] Rated Service Breaking Capacity10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
[In] Rated Current25 A at 65 °C
Compatibility CodeNSX100
Connection Pitch35 mm
Depth86 mm
Device Applicationmotor
Downside Connectionfront
Earth-leakage Protectionwithout
Electrical Durability10000 cycles at 690 V In
20000 cycles at 690 V In/2
30000 cycles at 440 V In
50000 cycles at 440 V In/2
Height161 mm
Mechanical Durability50000 cycles
Mounting Modefixed
Net Weight2.05 kg
Network Frequency50/60 Hz
Number Of Slots5 slot(s)
Protection TypeI : for short-circuit protection (magnetic)
Short-time Pick-up Adjustment Type Isdadjustable 9 settings
Trip Unit Rating25-25 A at 65 °C
Upside Connectionfront
Width105 mm
[Isd] Short-time Pick-up Adjustment Range6...14 x In
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
ENVIRONMENT
Ambient Air Temperature For Operation-25-70 °C
Ambient Air Temperature For Storage-50-85 °C
Electrical Shock Protection Classclass II
IK Degree Of ProtectionIK07 conforming to IEC 62262
IP Degree Of ProtectionIP40 conforming to IEC 60529
Operating Altitude0...2000 m without derating
2000 m...5000 m with derating
Overvoltage Categoryclass II
Pollution Degree3 conforming to IEC 60664-1
Product CertificationsCCC
EAC
Marine
Relative Humidity0-95 %
StandardsEN/IEC 60947
OTHER
Earth Leakage CurrentMA
Poles Description3P
[Us] Rated Supply VoltageComPact NSX100...250