LUB320 - Advanced Power Base, TeSys U, 3P, 32A/690V.
Schneider
SKU
SE_LUB320
Model
LUB320
SGD $246.11 All prices inclusive of GST
Short description of LUB320
LUB320. All-in-one motor starters up to 38 A (18.5 kW / 400 V)
Country of Origin
France
range : TeSys
-  product name : TeSys U
-  device short name : LUB
-  product or component type : Non reversing power base
-  device application : Motor controlMotor protection
-  poles description : 3P
-  suitability for isolation : Yes
-  [Ue] rated operational voltage : 690 V AC for power circuit
-  network frequency : 40...60 Hz
-  [Ith] conventional free air thermal current : 32 A
-  [Ie] rated operational current : 28.5 A at - utilisation category : AC
- 43AC
- 44AC
- 41
-  [Ics] rated service breaking capacity : 50 kA at 230 V50 kA at 440 V10 kA at 500 V4 kA at 690 V
-  auxiliary contact composition : 1 NO + 1 NC
-  auxiliary contacts type : type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1 type mirror contact (1 NC) conforming to IEC 60947-1
-  [Uc] control circuit voltage : 24 V AC 50/60 Hz24 V DC48...72 V AC 50/60 Hz48...72 V DC110...240 V AC 50/60 Hz110...220 V DC
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
-  product name : TeSys U
-  device short name : LUB
-  product or component type : Non reversing power base
-  device application : Motor controlMotor protection
-  poles description : 3P
-  suitability for isolation : Yes
-  [Ue] rated operational voltage : 690 V AC for power circuit
-  network frequency : 40...60 Hz
-  [Ith] conventional free air thermal current : 32 A
-  [Ie] rated operational current : 28.5 A at - utilisation category : AC
- 43AC
- 44AC
- 41
-  [Ics] rated service breaking capacity : 50 kA at 230 V50 kA at 440 V10 kA at 500 V4 kA at 690 V
-  auxiliary contact composition : 1 NO + 1 NC
-  auxiliary contacts type : type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1 type mirror contact (1 NC) conforming to IEC 60947-1
-  [Uc] control circuit voltage : 24 V AC 50/60 Hz24 V DC48...72 V AC 50/60 Hz48...72 V DC110...240 V AC 50/60 Hz110...220 V DC
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Breaking Capacity Code | 10 kA at 500 V 4 kA at 690 V 50 kA at 230 V 50 kA at 440 V |
Control Type | 3P |
Product Or Component Type | non reversing power base |
Range Of Product | TeSys U |
[Ie] Rated Operational Current | 21 A at 690 V 23 A at 500 V 28.5 A at <= 440 V |
[Uc] Control Circuit Voltage | 110...220 V DC 110...240 V AC 50/60 Hz 24 V AC 50/60 Hz 24 V DC 48...72 V AC 50/60 Hz 48...72 V DC |
[Ue] Rated Operational Voltage | 690 V AC for power circuit |
Device Short Name | LUB |
Range | TeSys |
Range Name | TeSys U |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Suitability For Isolation | yes |
Utilisation Category | AC-41 AC-43 AC-44 |
COMPLEMENTARY | |
Communication Network Type | 690 V AC for power circuit |
Product Name | TeSys U |
[Ics] Rated Service Breaking Capacity | 10 kA at 500 V 4 kA at 690 V 50 kA at 230 V 50 kA at 440 V |
Auxiliary Contact Composition | 1 NO + 1 NC |
Auxiliary Contacts Type | type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1 type mirror contact (1 NC) conforming to IEC 60947-1 |
Compatibility Code | LUB |
Connections - Terminals | control circuit: without connection power circuit: screw clamp terminals 1 cable(s) 1-10 mm² rigid power circuit: screw clamp terminals 1 cable(s) 1-6 mm² flexible with cable end power circuit: screw clamp terminals 1 cable(s) 2.5-10 mm² flexible without cable end power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end power circuit: screw clamp terminals 2 cable(s) 1-6 mm² flexible with cable end power circuit: screw clamp terminals 2 cable(s) 1-6 mm² rigid |
Depth | 126 mm |
Device Application | motor control motor protection |
Fixing Mode | clipped (DIN rail) screw-fixed (plate) |
Height | 154 mm |
Immunity To Microbreaks | 3 ms for control circuit |
Maximum Operating Rate | 3600 cyc/h |
Mechanical Durability | 15 Mcycles |
Net Weight | 0.865 kg |
Network Frequency | 40...60 Hz |
Operating Time | 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit 50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD for control circuit 60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD for control circuit 65 ms closing with LUCM for control circuit 70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD for control circuit |
Safe Separation Of Circuit | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N |
Tightening Torque | control circuit: 0.8-1.2 N.m flat screwdriver 5 mm control circuit: 0.8-1.2 N.m Philips no 1 screwdriver 5 mm power circuit: 1.9-2.5 N.m flat screwdriver 6 mm power circuit: 1.9-2.5 N.m Philips No 2 screwdriver 6 mm |
Typical Current Consumption | 200 mA at 24 V DC I maximum while closing with LUCM 220 mA at 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD 220 mA at 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD 25 mA at 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 25 mA at 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD 280 mA at 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD 280 mA at 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD 280 mA at 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD 280 mA at 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD 45 mA at 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD 45 mA at 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 75 mA at 24 V DC I rms sealed with LUCM 80 mA at 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 90 mA at 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD |
Width | 45 mm |
[Ith] Conventional Free Air Thermal Current | 32 A |
[Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947-6-2 |
[Ui] Rated Insulation Voltage | 600 V conforming to CSA C22.2 No 60947-4-1 600 V conforming to UL 60947-4-1 690 V conforming to IEC 60947-6-2 (pollution degree 3) |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-60 °C with LUCM -25-70 °C with LUCA, LUCB, LUCC, LUCD |
Ambient Air Temperature For Storage | -40-85 °C |
Fire Resistance | 650 °C conforming to IEC 60695-2-12 960 °C parts supporting live components conforming to IEC 60695-2-12 |
Heat Dissipation | 1.8-1.8 W for control circuit with LUCM 3-3 W for control circuit with LUCA, LUCB, LUCC, LUCD |
Immunity To Radioelectric Fields | 10 V conforming to IEC 61000-4-6 |
Immunity To Voltage Dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
IP Degree Of Protection | IP20 conforming to IEC 60947-1 (front panel and wired terminals) IP20 conforming to IEC 60947-1 (other faces) IP40 conforming to IEC 60947-1 (front panel outside connection zone) |
Non-dissipating Shock Wave | 1 kV serial mode 24...240 V AC conforming to IEC 60947-6-2 1 kV serial mode 48...220 V DC conforming to IEC 60947-6-2 2 kV common mode 24...240 V AC conforming to IEC 60947-6-2 2 kV common mode 48...220 V DC conforming to IEC 60947-6-2 |
Operating Altitude | 2000 m |
Product Certifications | ASEFA ATEX CCC CE CSA EAC Marine UL |
Protective Treatment | TH conforming to IEC 60068 |
Resistance To Electrostatic Discharge | 8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2 |
Resistance To Fast Transients | 2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
Resistance To Radiated Fields | 10 V/m 3 conforming to IEC 61000-4-3 |
Shock Resistance | 10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27 |
Standards | CSA C22.2 No 60947-4-1, with phase barrier EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier |
Vibration Resistance | 2 gn (f= 5-300 Hz) power poles open conforming to IEC 60068-2-27 4 gn (f= 5-300 Hz) power poles closed conforming to IEC 60068-2-27 |
OTHER | |
Poles Description | 3P |
[Us] Rated Supply Voltage | TeSys U |
Write Your Own Review