LC1SKGC301P7 - Mini contactor, TeSys SK, 3P(3NO), AC-3, 690V 9A, 230V AC coil
Schneider
SKU
SE_LC1SKGC301P7
Model
LC1SKGC301P7
SGD $35.71 All prices inclusive of GST
Short description of LC1SKGC301P7
LC1SKGC301P7. It is desingned with transparent protective cover at front for double security
Good adaptability: possible to insert a suppressor module
High durability & stable performance: up to 1200 cycles/hour for operating rates
Reliable in high and low temperature environment
Modularity design and compact size for easy maintenance, save time and space on installation
Good adaptability: possible to insert a suppressor module
High durability & stable performance: up to 1200 cycles/hour for operating rates
Reliable in high and low temperature environment
Modularity design and compact size for easy maintenance, save time and space on installation
TeSys SKGC mini-contactor, 3 poles (3NO), for non-inductive load applications up to 20A/690V AC-1,
and for 3-phase motor control applications up to 9A/690V AC-3 (4kW@400V).
It provides a 230V 50/60Hz AC control circuit, 1NC auxiliary contact, a transparent protective cover to prevent front face access, connection by screw terminals.
For operating rates until 1200 cycles/hour and ambient temperature -20/+50°C, it procures high reliability and durability.
For use in modular panels, compact (45mm width), clipping on 35mm DIN rail or fixing by 2 screws.
Location available to insert a suppressor module LA4SK (to be ordered separately).
Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).
and for 3-phase motor control applications up to 9A/690V AC-3 (4kW@400V).
It provides a 230V 50/60Hz AC control circuit, 1NC auxiliary contact, a transparent protective cover to prevent front face access, connection by screw terminals.
For operating rates until 1200 cycles/hour and ambient temperature -20/+50°C, it procures high reliability and durability.
For use in modular panels, compact (45mm width), clipping on 35mm DIN rail or fixing by 2 screws.
Location available to insert a suppressor module LA4SK (to be ordered separately).
Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).
MAIN | |
---|---|
Range | TeSys |
Product Name | TeSys SK |
Product Or Component Type | Mini contactor |
Device Short Name | LC1SKGC |
Contactor Application | Resistive load Motor control |
Utilisation Category | AC-3 AC-1 |
Power Pole Contact Composition | 3P |
Pole Contact Composition | 3 NO |
Auxiliary Contact Composition | 1 NC |
[Ie] Rated Operational Current | 20 A (at <50 °C) AC AC-1 9 A at <= 400 V AC AC-3 |
[Ue] Rated Operational Voltage | Power circuit: 690 V AC 50/60 Hz Signalling circuit: 690 V AC <= 400 Hz |
COMPLEMENTARY | |
Control Circuit Type | AC at 50/60 Hz |
[Uc] Control Circuit Voltage | 230 V AC 50/60 Hz |
Motor Power KW | 4 kW at 380...415 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 1.1 kW at 220...230 V AC 50/60 Hz |
[Ith] Conventional Free Air Thermal Current | 20 A (at 55 °C) for power circuit 10 A (at 55 °C) for signalling circuit |
Irms Rated Making Capacity | 85 A AC conforming to NF C 63-110 85 A AC conforming to IEC 60947 |
Rated Breaking Capacity | 68 A at <= 400 V conforming to NF C 63-110 68 A at <= 400 V conforming to IEC 60947 |
[Icw] Rated Short-time Withstand Current | 60 A 55 °C for power circuit |
Associated Fuse Rating | 20 A gI at <= 440 V for power circuit 10 A gI for signalling circuit conforming to IEC 60947 10 A gI for signalling circuit conforming to VDE 0660 |
Average Impedance | 4 mOhm - Ith 20 A 50 Hz for power circuit |
[Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to BS 5424 Power circuit: 690 V conforming to IEC 60947 Power circuit: 690 V conforming to UL 508 Power circuit: 690 V conforming to VDE 0110 group C Power circuit: 690 V conforming to CSA C22.2 No 14 |
Mounting Support | Panel Rail |
Standards | EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 |
Product Certifications | CB Scheme CE UKCA EAC cULus |
Connections - Terminals | Connector 1 cable(s) 1.5…6 mm²solid Connector 2 cable(s) 1.5…4 mm²solid Connector 1 cable(s) 0.5…6 mm²flexible without cable end Connector 2 cable(s) 0.35…2.5 mm²flexible without cable end Connector 1 cable(s) 0.35…6 mm²flexible with cable end Connector 2 cable(s) 0.35…1.5 mm²flexible with cable end |
Tightening Torque | Power circuit: 0.8 N.m - on connector - with screwdriver pozidriv No 1 |
Operating Time | 6...8 ms coil de-energisation and NO opening 7...14 ms coil energisation and NO closing 8...16 ms coil energisation and NC opening 8...10 ms coil de-energisation and NC closing |
Mechanical Durability | 10 Mcycles |
Maximum Operating Rate | 1200 cyc/h |
Control Circuit Voltage Limits | Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C) Drop-out: 0.2...0.75 Uc at 50/60 Hz (at <55 °C) |
Inrush Power In VA | 23 VA 50/60 Hz (at 20 °C) |
Hold-in Power Consumption In VA | 4.9 VA 50/60 Hz (at 20 °C) |
Heat Dissipation | 1.5 W at 50/60 Hz |
Signalling Circuit Frequency | <= 400 Hz |
ENVIRONMENT | |
IP Degree Of Protection | IP2X conforming to VDE 0106 |
Protective Treatment | TC conforming to IEC 60068 TC conforming to DIN 50015 |
Ambient Air Temperature For Operation | -20…50 °C |
Ambient Air Temperature For Storage | -50…70 °C |
Operating Altitude | 2000 m without derating |
Height | 58 mm |
Width | 45 mm |
Depth | 56 mm |
Net Weight | 0.175 kg |
PACKING UNITS | |
Unit Type Of Package 1 | PCE |
Number Of Units In Package 1 | 1 |
Package 1 Height | 4.800 cm |
Package 1 Width | 6.200 cm |
Package 1 Length | 6.000 cm |
Package 1 Weight | 167.000 g |
Unit Type Of Package 2 | S01 |
Number Of Units In Package 2 | 28 |
Package 2 Height | 15.000 cm |
Package 2 Width | 15.000 cm |
Package 2 Length | 40.000 cm |
Package 2 Weight | 4.862 kg |
CONTRACTUAL WARRANTY | |
Warranty | 18 months |