LADR0 - TeSys D - Time Delay Auxiliary Contact Block - 1 NO + 1 NC Screw Clamp Terminals

Schneider
SKU
SE_LADR0
Model
LADR0
SGD $70.19 All prices inclusive of GST

Short description of LADR0

LADR0. New modern look & feel of all machines
Designed to meet the requirements of industrial and HVAC applications
Easier to install and operate with multi-standard screws
With IEC60335-1 compliance, improved fire resistance, and dustproof auxiliaries
Digital customer experience for technical documents
Country of Origin
France
-
+

UOM: Piece

In stock
In Stock 68
Backorder Leadtime: 2 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

TeSys Deca time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD.
It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 0.3-3s, connection by screw clamp terminals.
Clip-on front mounting, it procures high reliability and durability.
Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).
MAIN
RangeTeSys
TeSys Deca
Product NameTeSys Deca
Product Or Component TypeTime delay auxiliary contact block
Range CompatibilityTeSys Deca CAD
TeSys Deca LC1D
TeSys F LC1F
TeSys F CR1F
Mounting LocationFront
Pole Contact Composition1 NO + 1 NC
Contacts OperationTime delay
Timer TypeOff delay
Time Delay Range0.3...3 s
[Ue] Rated Operational Voltage690 V AC 25...400 Hz
[Ie] Rated Operational Current6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[Ui] Rated Insulation Voltage690 V conforming to IEC 60947-5-1
600 V conforming to UL 60947-5-1
600 V conforming to CSA C22.2 No 60947-5-1
[Ith] Conventional Free Air Thermal Current10 A (at 60 °C)
StandardsEN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
EN 50012
IEC 60335-1:Clause 30.2
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
Product CertificationsIECEE CB Scheme
UL
CSA
CCC
EAC
UKCA
COMPLEMENTARY
Irms Rated Making Capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
Permissible Short-time Rating100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
Protection TypeGG fuse 10 A
Mechanical Durability5 Mcycles
Minimum Switching Current5 mA
Minimum Switching Voltage17 V
Non-overlap Time1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
Insulation Resistance> 10 MOhm
Connections - TerminalsScrew clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid
Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid
Screw clamp terminals
Tightening Torque1.7 N.m - with screwdriver flat Ø 6 mm
1.7 N.m - with screwdriver Philips No 2
1.7 N.m - with screwdriver pozidriv No 2
Height48 mm
Width44 mm
Depth61 mm
ColourDark grey
ENVIRONMENT
Environmental CharacteristicNormal environment
IP Degree Of ProtectionIP20 conforming to IEC 60529
Protective TreatmentTH conforming to IEC 60068
Ambient Air Temperature For Storage-60…80 °C
Ambient Air Temperature For Operation-40…70 °C
Operating Altitude3000 m
PACKING UNITS
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height5.200 cm
Package 1 Width6.500 cm
Package 1 Length5.000 cm
Package 1 Weight75.000 g
Unit Type Of Package 2S03
Number Of Units In Package 2140
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight11.070 kg
Unit Type Of Package 3P06
Number Of Units In Package 31120
Package 3 Height75.000 cm
Package 3 Width60.000 cm
Package 3 Length80.000 cm
Package 3 Weight99.324 kg
CONTRACTUAL WARRANTY