C25B34V160 - Circuit Breaker ComPacT NSX250B, 25kA At 415VAC, MicroLogic 4.2 Vigi Trip Unit 160A, 3 Poles 3d

Schneider
SKU
SE_C25B34V160
Model
C25B34V160
SGD $2,652.95 All prices inclusive of GST

Short description of C25B34V160

C25B34V160. NSX250B 25kA AC 3P3D 160A 4.2
Country of Origin
China

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 4 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

This ComPacT NSX250B is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity.
It is an optimal choice for all standard and specific applications.
The breaking capacity (Icu) is 25kA rms at 415VAC 50/60Hz.
The operational voltage is 440VAC 50/60Hz.
This product embeds a 160A rating electronic MicroLogic 4.2 Vigi trip unit, with an integrated adjustable earth-leakage protection.
MicroLogic 4.2 Vigi provides also adjustable long time and short time protections, and a fixed instantaneous protection.
This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories.
It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.
ComPacT NSX250B is part of Schneider Electric EcoStruxure Power architecture.
MAIN
RangeComPacT
Product NameComPacT NSX
Device Short NameNSX250B
Product Or Component TypeEarth leakage circuit breaker
Device ApplicationDistribution
Poles Description3P
Protected Poles Description3D
[In] Rated Current160 A at 40 °C
[Ue] Rated Operational Voltage440 V AC 50/60 Hz
Network TypeAC
Network Frequency50/60 Hz
Suitability For IsolationYes conforming to EN/IEC 60947-2
Utilisation CategoryCategory A
[Icu] Rated Ultimate Short-circuit Breaking Capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Performance LevelB 25 kA 415 V AC
Trip Unit NameMicroLogic 4.2
Trip Unit TechnologyElectronic
Trip Unit Protection FunctionsLSoIR
Control TypeToggle
Circuit Breaker Mounting ModeFixed
COMPLEMENTARY
[Ui] Rated Insulation Voltage500 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ics] Rated Service Short-circuit Breaking Capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability20000 cycles
Electrical Durability20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V In
Power Dissipation Per Pole25 W N
25 W L1 and L3
20.6 W L2
Mounting SupportBackplate
Mounting PositionHorizontal and vertical
Flat on the back
Upside ConnectionFront
Downside ConnectionFront
Connection Pitch35 mm
Protection TypeL : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
R : for earth-leakage protection
Trip Unit Rating160 A at 40 °C
Long-time Pick-up Adjustment Type Ir (thermal Protection)Adjustable 9 settings
[Ir] Long-time Protection Pick-up Adjustment Range63...160 A
Long-time Protection Delay Adjustment Type TrFixed
[tr] Long-time Protection Delay Adjustment Range400 s at 1.5 x Ir
16 s at 6 x Ir
11 s at 7.2 x Ir
Thermal Memory20 minutes before and after tripping
Short-time Protection Pick-up Adjustment Type IsdAdjustable
[Isd] Short-time Protection Pick-up Adjustment Range1.5...10 x Ir
Short-time Protection Delay Adjustment Type TsdFixed
Instantaneous Protection Pick-up Adjustment Type IiFixed
[Ii] Instantaneous Protection Pick-up Adjustment Range2400 A
Earth-leakage ProtectionIntegrated
Earth-leakage Protection ClassClass A
Earth-leakage Protection Sensitity Adjustment Type IΔnAdjustable
[IΔn] Earth-leakage Protection Sensitivity Adjustment Range30 mA
100 mA
300 mA
500 mA
1 A
3 A
5 A
Earth-leakage Protection Specific ModeOFF using the IΔn rotary switch
Earth-leakage Protection Time Delay Adjustement Type ΔtAdjustable
[Δt] Earth-leakage Protection Time Delay Adjustment Range0 ms
60 ms
150 ms
500 ms
1 s
Zone Selective Interlocking ZSIWithout
Number Of Slots For Electrical Auxiliaries5 slot(s)
Local SignallingFlashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
Net Weight2.4 kg
ENVIRONMENT
StandardsEN/IEC 60947-2
Overvoltage CategoryClass II
Electrical Shock Protection ClassClass II
Pollution Degree3 conforming to IEC 60664-1
IP Degree Of ProtectionIP40 conforming to IEC 60529
IK Degree Of ProtectionIK07 conforming to IEC 62262
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-50…85 °C
Relative Humidity0…95 %
Operating Altitude0...2000 m without derating
2000 m...5000 m with derating
PACKING UNITS
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height14 cm
Package 1 Width11.5 cm
Package 1 Length19 cm
Package 1 Weight2.38 kg
Unit Type Of Package 2S03
Number Of Units In Package 28
Package 2 Height30 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight19.04 kg
Write Your Own Review
You're reviewing:C25B34V160 - Circuit Breaker ComPacT NSX250B, 25kA At 415VAC, MicroLogic 4.2 Vigi Trip Unit 160A, 3 Poles 3d
Your Rating