C10B3TM025 - Circuit Breaker ComPacT NSX100B, 25kA At 415VAC, TMD Trip Unit 25A, 3 Poles 3d
Schneider
SKU
SE_C10B3TM025
Model
C10B3TM025
SGD $237.60 All prices inclusive of GST
Short description of C10B3TM025
C10B3TM025. NSX100B 25kA AC 3P3D 25A TMD
Country of Origin
India
MAIN SPECIFICATIONS | |
---|---|
Breaking Capacity | 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking Capacity Code | B 25 kA 415 V AC |
Contacts Type And Composition | 25 A at 40 °C |
Control Type | toggle |
Product Or Component Type | circuit breaker |
Range Of Product | ComPacT NSX100...250 new generation |
Trip Unit Name | TM-D |
[Ie] Rated Operational Current | toggle |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
Device Short Name | NSX100B |
EAN13 | 3606481996145 |
Mounting Support | backplate |
Network Type | AC |
Protected Poles Description | 3t |
Range | ComPacT new generation |
Range Name | ComPacT NSX (2021) |
Suitability For Isolation | yes conforming to EN/IEC 60947-2 |
Trip Unit Protection Functions | LI |
Trip Unit Technology | thermal-magnetic |
Utilisation Category | category A |
COMPLEMENTARY | |
Communication Network Type | 690 V AC 50/60 Hz |
Current Transformer Type | B 25 kA 415 V AC |
Interlocked Device | 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Product Name | ComPacT NSX new generation |
[Ics] Rated Service Breaking Capacity | 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
[In] Rated Current | 25 A at 40 °C |
Compatibility Code | NSX100 |
Connection Pitch | 35 mm |
Depth | 86 mm |
Device Application | distribution |
Downside Connection | front |
Earth-leakage Protection | without |
Electrical Durability | 10000 cycles at 690 V In 20000 cycles at 690 V In/2 30000 cycles at 440 V In 50000 cycles at 440 V In/2 |
Height | 161 mm |
Long Time Delay Adjustment Type | fixed |
Long Time Pick-up Adjustment Range | 0.7...1 x In |
Long Time Pick-up Adjustment Type Ir | adjustable |
Mechanical Durability | 50000 cycles |
Mounting Mode | fixed |
Net Weight | 2.05 kg |
Network Frequency | 50/60 Hz |
Number Of Slots | 5 slot(s) |
Power Losses | 4.01 W |
Protection Type | I : for short-circuit protection (magnetic) L : for overload protection (thermal) |
Short-time Delay Adjustment Type | fixed |
Short-time Pick-up Adjustment Type Isd | fixed |
Trip Unit Rating | 25-25 A at 40 °C |
Upside Connection | front |
Width | 105 mm |
[Isd] Short-time Pick-up Adjustment Range | 300 A |
[tr] Long-time Delay Adjustment Range | 120-400 s at 1.5 x In 15-15 s at 6 x Ir |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
[Ui] Rated Insulation Voltage | 800 V AC 50/60 Hz |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-70 °C |
Ambient Air Temperature For Storage | -50-85 °C |
Electrical Shock Protection Class | class II |
IK Degree Of Protection | IK07 conforming to IEC 62262 |
IP Degree Of Protection | IP40 conforming to IEC 60529 |
Operating Altitude | 0...2000 m without derating 2000 m...5000 m with derating |
Overvoltage Category | class II |
Pollution Degree | 3 conforming to IEC 60664-1 |
Product Certifications | CCC EAC Marine |
Relative Humidity | 0-95 % |
Standards | EN/IEC 60947 |
OTHER | |
Earth Leakage Current | TM-D |
Poles Description | 3P |
[Us] Rated Supply Voltage | ComPacT NSX100...250 new generation |
Write Your Own Review