ATV630U75N4 - Variable Speed Drive, Altivar Process ATV600, ATV630, 7.5kW/10 Hp, 380...480 V, IP21/UL Type 1
Schneider
SKU
SE_ATV630U75N4
Model
ATV630U75N4
SGD $1,691.04 All prices inclusive of GST
Short description of ATV630U75N4
ATV630U75N4. VARIABLE SPEED DRIVE IP21 7,5KW 400V/480
Country of Origin
Indonesia
variable speed drive ATV630
-  7.5kW/10HP
-  380...480V
-  IP21/UL type 1.
Label :  Altivar Process ATV600
-  range of product :  Altivar Process ATV600
-  degree of protection :  UL type 1 conforming to UL 508C
-  type of cooling :  forced convection
-  supply frequency :  50...60 Hz
-  5...5 %
-  network number of phases :  3 phases
-  [Us] rated supply voltage :  380...480 V
-  15...10 %
-  motor power kW :  7.5 kW (normal duty), 5.5 kW (heavy duty)
-  motor power hp :  10 hp normal duty, 7.5 hp heavy duty
-  line current :  13.8 A at 380 V (normal duty), 11.9 A at 480 V (normal duty), 10.5 A at 380 V (heavy duty), 9.2 A at 480 V (heavy duty)
-  prospective line Isc :  50 kA
-  apparent power :  9.9 kVA at 480 V (normal duty), 7.6 kVA at 480 V (heavy duty)
-  product or component type :  variable speed drive
-  continuous output current :  16.5 A at 4 kHzfor normal duty, 12.7 A at 4 kHzfor heavy duty
-  maximum transient current :  18.2 A during 60 s (normal duty), 19.1 A during 60 s (heavy duty)
-  asynchronous motor control profile :  variable torque standard,optimized torque mode,constant torque standard
-  synchronous motor control profile :  permanent magnet motor
-  output frequency :  0.0001-0.5 kHz
-  speed drive output frequency :  0.1-599 Hz
-  nominal switching frequency :  4 kHz
-  switching frequency :  2...12 kHz adjustable, 4...12 kHz with derating factor
-  safety function :  STO (safe torque off) SIL 3
-  product specific application :  process and utilities
-  discrete input logic :  16 preset speeds
-  communication port protocol :  Ethernet,Modbus serial,Modbus TCP
-  option card :  N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A
-  device short name :  ATV630
-  variant :  standard version
-  product destination :  synchronous motors,asynchronous motors
-  mounting mode :  wall mount
-  EMC filter :  integrated conforming to EN/IEC 61800-3 category C2 with 50 m, integrated conforming to EN/IEC 61800-3 category C3 with 150 m
-  IP degree of protection :  N/A, N/A
-  Range Presentation :  Altivar Process is a Services Oriented Drive designed to reduce OPEX in Process & Utilities installations, thanks to embedded digital services
Altivar Process also provides unique engineered drive solutionsThe first Services Oriented Drive with -  Embedded Power measurement and Energy dashboard
-  Embedded process monitoring and control
-  Embedded Pump curves embedded (easy to set 5 points curve)
-  Low Harmonics (THDi 48% at 80% load or THDi 5% with low harmonic offer)
-  Start & Stop function to reduce consumption at stop.
-  Asset monitoring & protection
-  Drift monitoring
-  Easy maintenance (Dynamic QR
- Code)
-  Seamless integration with embedded Ethernet
-  From device to process control with the Smart Process Object
-  From data to insights with the embedded Web Server
Unique Engineered Drives -  Proven technical cooling and harmonics solutions
-  Modular and compact design
-  Easy grid integration
-  Embedded Control (PLC, RTU, HMI)
-  A full set of control option
-  Range Benefits :  Services Oriented Drives
This new concept of drives meets the major needs of the process and utilities in terms of over equipment efficiency and Total Cost of ownership by supporting the energy management, asset management and also the overall performances of the process.
-  Sustainable cost savings thanks to predictive condition
- based maintenance
-  Up to 20% downtime reduction without additional investment
Unique Engineered Drives
Schneider Electric’s expertise in design and application services delivers solution
- specific designs dedicated to your process requirements for seamless plant integration.
-  Minimize design and delivery risks
-  Reduces the commissioning and adaptation time
Enhanced Drives specifications
Compact and modular, suitable even in harsh environments, Altivar Process is perfect for upgrades, retrofits, or new installations.
-  Withstand the severe conditions of use both electrical as environmental
-  Range Application Presentation :  Altivar Process drives have been specifically designed for industrial processes, such as : 
WWW :  Pumping station, boosting station, borehole pump, lifting station, aeration, as compression, sludge conveying…
O&G :  Electrically submersible pump, jack pumps, oil line pump, swapping pump, water injection pump, regasification compressor... Refinery :  pumps, fans, compressors…MMM  : 
-  Mining :  Floatation & thickening, de
- watering and filtration, mine shaft pumps…
-  Cement :  Pre
- heater fan, kiln waste gas fan, cooler exhaust fan, vertical roller mill, pump for water supply…
-  Metal :  blast furnace blower, water distribution pump system, draught fan, dedusting fan, coke machine (Oven)… F&B :  dairy (pumping pipe distribution, milk powder drying, centrifugal pump…), sugar (pumps, blower for drying…)
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
-  7.5kW/10HP
-  380...480V
-  IP21/UL type 1.
Label :  Altivar Process ATV600
-  range of product :  Altivar Process ATV600
-  degree of protection :  UL type 1 conforming to UL 508C
-  type of cooling :  forced convection
-  supply frequency :  50...60 Hz
-  5...5 %
-  network number of phases :  3 phases
-  [Us] rated supply voltage :  380...480 V
-  15...10 %
-  motor power kW :  7.5 kW (normal duty), 5.5 kW (heavy duty)
-  motor power hp :  10 hp normal duty, 7.5 hp heavy duty
-  line current :  13.8 A at 380 V (normal duty), 11.9 A at 480 V (normal duty), 10.5 A at 380 V (heavy duty), 9.2 A at 480 V (heavy duty)
-  prospective line Isc :  50 kA
-  apparent power :  9.9 kVA at 480 V (normal duty), 7.6 kVA at 480 V (heavy duty)
-  product or component type :  variable speed drive
-  continuous output current :  16.5 A at 4 kHzfor normal duty, 12.7 A at 4 kHzfor heavy duty
-  maximum transient current :  18.2 A during 60 s (normal duty), 19.1 A during 60 s (heavy duty)
-  asynchronous motor control profile :  variable torque standard,optimized torque mode,constant torque standard
-  synchronous motor control profile :  permanent magnet motor
-  output frequency :  0.0001-0.5 kHz
-  speed drive output frequency :  0.1-599 Hz
-  nominal switching frequency :  4 kHz
-  switching frequency :  2...12 kHz adjustable, 4...12 kHz with derating factor
-  safety function :  STO (safe torque off) SIL 3
-  product specific application :  process and utilities
-  discrete input logic :  16 preset speeds
-  communication port protocol :  Ethernet,Modbus serial,Modbus TCP
-  option card :  N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A
-  device short name :  ATV630
-  variant :  standard version
-  product destination :  synchronous motors,asynchronous motors
-  mounting mode :  wall mount
-  EMC filter :  integrated conforming to EN/IEC 61800-3 category C2 with 50 m, integrated conforming to EN/IEC 61800-3 category C3 with 150 m
-  IP degree of protection :  N/A, N/A
-  Range Presentation :  Altivar Process is a Services Oriented Drive designed to reduce OPEX in Process & Utilities installations, thanks to embedded digital services
Altivar Process also provides unique engineered drive solutionsThe first Services Oriented Drive with -  Embedded Power measurement and Energy dashboard
-  Embedded process monitoring and control
-  Embedded Pump curves embedded (easy to set 5 points curve)
-  Low Harmonics (THDi
-  Start & Stop function to reduce consumption at stop.
-  Asset monitoring & protection
-  Drift monitoring
-  Easy maintenance (Dynamic QR
- Code)
-  Seamless integration with embedded Ethernet
-  From device to process control with the Smart Process Object
-  From data to insights with the embedded Web Server
Unique Engineered Drives -  Proven technical cooling and harmonics solutions
-  Modular and compact design
-  Easy grid integration
-  Embedded Control (PLC, RTU, HMI)
-  A full set of control option
-  Range Benefits :  Services Oriented Drives
This new concept of drives meets the major needs of the process and utilities in terms of over equipment efficiency and Total Cost of ownership by supporting the energy management, asset management and also the overall performances of the process.
-  Sustainable cost savings thanks to predictive condition
- based maintenance
-  Up to 20% downtime reduction without additional investment
Unique Engineered Drives
Schneider Electric’s expertise in design and application services delivers solution
- specific designs dedicated to your process requirements for seamless plant integration.
-  Minimize design and delivery risks
-  Reduces the commissioning and adaptation time
Enhanced Drives specifications
Compact and modular, suitable even in harsh environments, Altivar Process is perfect for upgrades, retrofits, or new installations.
-  Withstand the severe conditions of use both electrical as environmental
-  Range Application Presentation :  Altivar Process drives have been specifically designed for industrial processes, such as : 
WWW :  Pumping station, boosting station, borehole pump, lifting station, aeration, as compression, sludge conveying…
O&G :  Electrically submersible pump, jack pumps, oil line pump, swapping pump, water injection pump, regasification compressor... Refinery :  pumps, fans, compressors…MMM  : 
-  Mining :  Floatation & thickening, de
- watering and filtration, mine shaft pumps…
-  Cement :  Pre
- heater fan, kiln waste gas fan, cooler exhaust fan, vertical roller mill, pump for water supply…
-  Metal :  blast furnace blower, water distribution pump system, draught fan, dedusting fan, coke machine (Oven)… F&B :  dairy (pumping pipe distribution, milk powder drying, centrifugal pump…), sugar (pumps, blower for drying…)
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Analog/digital Conversion | software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits software-configurable current DQ-, DQ+: 100 mA software-configurable current DQ-, DQ+: 30 V DC software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
Analogue Input Number | 3 |
Analogue Input Range | 3 |
Discrete Input Number | 8 |
Discrete Output Type | relay outputs R1A, R1B, R1C 250 V AC 3000 mA relay outputs R1A, R1B, R1C 30 V DC 3000 mA relay outputs R2A, R2C 250 V AC 5000 mA relay outputs R2A, R2C 30 V DC 5000 mA relay outputs R3A, R3C 250 V AC 5000 mA relay outputs R3A, R3C 30 V DC 5000 mA |
Display Type | 2-wire RS 485 Ethernet |
Measurement Accuracy | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial |
Physical Interface | 2-wire RS 485 Ethernet |
Product Or Component Type | variable speed drive |
Range Of Product | Altivar Process ATV600 |
Communication Port Protocol | Ethernet Modbus serial Modbus TCP |
Degree Of Protection | UL type 1 conforming to UL 508C |
Design Of Frequency Changer | U converter |
Device Short Name | ATV630 |
EAN13 | 3606480758157 |
EMC Filter | integrated with 150 m conforming to EN/IEC 61800-3 category C3 integrated with 50 m conforming to EN/IEC 61800-3 category C2 |
Line Current | 10.5 A at 380 V (heavy duty) 11.9 A at 480 V (normal duty) 13.8 A at 380 V (normal duty) 9.2 A at 480 V (heavy duty) |
Method Of Access | slave Modbus TCP |
Motor Power Hp | 10 hp normal duty 7.5 hp heavy duty |
Network Number Of Phases | 3 phases |
Number Of Input Phases | 3 |
Number Of Output Phases | 3 |
Product Specific Application | process and utilities |
Range Name | Altivar Process ATV600 |
Relative Symmetric Mains Voltage Tolerance | 10 % |
COMPLEMENTARY | |
Analogue Input Type | AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
Analogue Output Number | 2 |
Analogue Output Type | software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits software-configurable current DQ-, DQ+: 100 mA software-configurable current DQ-, DQ+: 30 V DC software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
Connector Type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial |
Discrete Output Number | 2 |
Output Voltage | <= power supply voltage |
[Ics] Rated Service Breaking Capacity | relay outputs R1A, R1B, R1C 250 V AC 3000 mA relay outputs R1A, R1B, R1C 30 V DC 3000 mA relay outputs R2A, R2C 250 V AC 5000 mA relay outputs R2A, R2C 30 V DC 5000 mA relay outputs R3A, R3C 250 V AC 5000 mA relay outputs R3A, R3C 30 V DC 5000 mA |
1 Phase Low Current Possible | false |
4 Quadrant Operation Possible | false |
Acceleration And Deceleration Ramps | linear adjustable separately from 0.01...9999 s |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
Apparent Power | 7.6 kVA at 480 V (heavy duty) 9.9 kVA at 480 V (normal duty) |
Application In Domestic And Commercial Area Permitted | false |
Application In Industrial Area Permitted | true |
Asynchronous Motor Control Profile | constant torque standard optimized torque mode variable torque standard |
Base Load Current At High Overload | 12.7 A |
Base Load Current At Low Overload | 16.5 A |
Brake Chopper Integrated | false |
Braking To Standstill | by DC injection |
Capacity Of DC Link | 1000 µF |
Computer Port | true |
Continuous Output Current | 12.7 A at 4 kHz for heavy duty 16.5 A at 4 kHz for normal duty |
Data Format | 8 bits, configurable odd, even or no parity |
Depth | 233 mm |
Discrete Input Logic | negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1) positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) 16 preset speeds |
Discrete Input Type | DI7, DI8 programmable as pulse input: 0-30 kHz, 24 V DC (<= 30 V) |
Electrical Connection | control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 line side: screw terminal 4...6 mm²/AWG 12...AWG10 motor: screw terminal 6...10 mm²/AWG 10...AWG 8 |
EMC Limit Value (complied) | true |
Enclosure Mounting | wall mounted |
Exchange Mode | half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
Frequency Resolution | analog input: 0.012/50 Hz display unit: 0.1 Hz |
Height | 409 mm |
Housing Material | plastic |
Input Compatibility | DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2 |
Insulation Resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Isolation | between power and control terminals |
Linearity Error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AO1, AO2: +/- 0.2 % for analog output |
Local Signalling | 1 LED (red) for presence of voltage 3 LEDs (dual colour) for embedded communication status 3 LEDs for local diagnostic 4 LEDs (dual colour) for communication module status |
Marking | CE |
Maximum Associated Fuse Rating | 25 A |
Maximum Input Current | 13.8 A |
Maximum Output Frequency | 500 kHz |
Maximum Output Voltage | 480 V |
Maximum Switching Current | relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 250 V AC relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 30 V DC |
Maximum Transient Current | 18.2 A during 60 s (normal duty) 19.1 A during 60 s (heavy duty) |
Minimum Switching Current | relay output R1, R2, R3: 5 mA at 24 V DC |
Motor Power KW | 5.5 kW (heavy duty) 7.5 kW (normal duty) |
Motor Slip Compensation | adjustable automatic whatever the load can be suppressed not available in permanent magnet motor law |
Motor Starter Type | variable speed drive |
Mounting Mode | wall mount |
Net Weight | 7.7 kg |
Network Frequency | 50...60 Hz |
Nominal Output Current | 16.5 A |
Nominal Output Power | 7.5 kW |
Nominal Switching Frequency | 4 kHz |
Number Of Addresses | 1-247 for Modbus serial |
Number Of HW Interfaces Industrial Ethernet | 1 |
Number Of HW Interfaces Serial RS485 | 1 |
Operating Element Present | true |
Operating Position | vertical +/- 10 degree |
Optical Interface Present | false |
Option Card | communication module, BACnet MS/TP communication module, Ethernet Powerlink slot A/slot B: digital and analog I/O extension module slot A/slot B: output relay extension module slot A: communication module, CANopen daisy chain RJ45 slot A: communication module, CANopen screw terminals slot A: communication module, CANopen SUB-D 9 slot A: communication module, DeviceNet slot A: communication module, Ethernet IP/Modbus TCP/MD-Link slot A: communication module, Modbus TCP/EtherNet/IP slot A: communication module, Profibus DP V1 slot A: communication module, Profinet |
Permissible Temporary Current Boost | 1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty) |
Power Dissipation In W | forced convection: 44 W at 380 V, switching frequency 4 kHz natural convection: 172 W at 380 V, switching frequency 4 kHz |
Power Loss Per Device Current Dependent | 259 W |
Power Loss Static Current Independent | 17 W |
Power Range | 7-11 kW at 380-440 V 3 phases 7-11 kW at 480-500 V 3 phases |
Product Destination | asynchronous motors synchronous motors |
Prospective Line Isc | 50 kA |
Protection Type | break on the control circuit: drive line supply overvoltage: drive line supply phase loss: drive line supply undervoltage: drive motor phase break: drive motor phase break: motor overcurrent between output phases and earth: drive overheating: drive overload of output voltage: drive overspeed: drive overvoltages on the DC bus: drive safe torque off: drive safe torque off: motor short-circuit protection: drive thermal protection: drive thermal protection: motor |
Quantity Per Set | 1 |
Refresh Time | relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Relative Symmetric Network Frequency Tolerance | 5 % |
Relay Output Number | 3 |
Relay Output Type | configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles configurable relay logic R2: sequence relay NO electrical durability 100000 cycles configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Safety Function | STO (safe torque off) SIL 3 |
Sampling Duration | 10 ms +/- 1 ms (AO1) - analog output 2 ms +/- 0.5 ms (DI1...DI4) - discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 5 ms +/- 1 ms (DI5, DI6) - discrete input |
Specific Application | utility |
Speed Drive Output Frequency | 0.1-500 Hz |
Supply | external supply for digital inputs: 24 V DC (19-30 V), <1.25 mA, protection type: overload and short-circuit protection internal supply for digital inputs and STO: 24 V DC (21-27 V), <200 mA, protection type: overload and short-circuit protection internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
Supply Frequency | 50...60 Hz - 5...5 % |
Supporting Protocol For AS-Interface Safety At Work | false |
Supporting Protocol For ASI | false |
Supporting Protocol For BACnet | false |
Supporting Protocol For CAN | true |
Supporting Protocol For Data-Highway | false |
Supporting Protocol For DeviceNet | false |
Supporting Protocol For DeviceNet Safety | false |
Supporting Protocol For EtherNet/IP | true |
Supporting Protocol For Foundation Fieldbus | false |
Supporting Protocol For INTERBUS | false |
Supporting Protocol For INTERBUS-Safety | false |
Supporting Protocol For KNX | false |
Supporting Protocol For LON | false |
Supporting Protocol For MODBUS | true |
Supporting Protocol For Other Bus Systems | false |
Supporting Protocol For PROFIBUS | true |
Supporting Protocol For PROFINET CBA | true |
Supporting Protocol For PROFINET IO | true |
Supporting Protocol For PROFIsafe | false |
Supporting Protocol For SafetyBUS P | false |
Supporting Protocol For SERCOS | false |
Supporting Protocol For SUCONET | false |
Supporting Protocol For TCP/IP | true |
Switching Frequency | 2...12 kHz adjustable 4...12 kHz with derating factor |
Synchronous Motor Control Profile | permanent magnet motor synchronous reluctance motor |
Transmission Frame | RTU |
Transmission Rate | 10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Type Of Cooling | forced convection |
Type Of Polarization | no impedance |
Width | 171 mm |
With Safety Function Safe Brake Management (SBC/SBT) | false |
With Safety Function Safe Direction (SDI) | false |
With Safety Function Safe Operating Stop (SOS) | false |
With Safety Function Safe Position (SP) | false |
With Safety Function Safe Programmable Logic | false |
With Safety Function Safe Speed Monitor (SSM) | false |
With Safety Function Safe Stop 1 (SS1) | false |
With Safety Function Safe Torque Off (STO) | true |
With Safety Function Safely Limited Position (SLP) | false |
With Safety Function Safely Limited Speed (SLS) | false |
With Sft Fct Safe Stop 2 (SS2) | false |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -15-50 °C (without derating) -15-60 °C 50-60 °C (with derating factor) |
Ambient Air Temperature For Storage | -40-70 °C |
Ambient Air Transport Temperature | -40-70 °C |
Electromagnetic Compatibility | 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 |
Environmental Class (during Operation) | class 3C3 according to IEC 60721-3-3 class 3S3 according to IEC 60721-3-3 |
Environmental Class (during Storage) | class 1C3 according to EN 60721-3-1 class 1S2 according to EN 60721-3-1 |
Environmental Class (during Transport) | class 2C3 according to EN 60721-3-2 class 2S1 according to EN 60721-3-2 |
IP Degree Of Protection | IP21 IP21 conforming to IEC 60529 IP21 conforming to IEC 61800-5-1 |
Maximum Acceleration Under Shock Impact (during Operation) | 150 m/s² at 11 ms |
Maximum Acceleration Under Shock Load (during Storage) | 150 m/s² at 11 ms |
Maximum Acceleration Under Shock Load (during Transport) | 150 m/s² at 11 ms |
Maximum Acceleration Under Vibrational Stress (during Operation) | 10 m/s² at 13...200 Hz |
Maximum Acceleration Under Vibratory Load (during Storage) | 10 m/s² at 13...200 Hz |
Maximum Acceleration Under Vibratory Load (during Transport) | 10 m/s² at 13...200 Hz |
Maximum Deflection Under Vibratory Load (during Operation) | 1.5 mm at 2...13 Hz |
Maximum Deflection Under Vibratory Load (during Storage) | 1.5 mm at 2...13 Hz |
Maximum Deflection Under Vibratory Load (during Transport) | 1.5 mm at 2...13 Hz |
Maximum THDI | <48 % from 80...100 % of load conforming to IEC 61000-3-12 |
NEMA Degree Of Protection | NEMA 1 |
Noise Level | 56 dB 56 dB conforming to 86/188/EEC |
Operating Altitude | <= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m |
Overvoltage Category | III |
Permitted Relative Humidity (during Operation) | class 3K5 according to EN 60721-3 |
Permitted Relative Humidity (during Storage) | class 1K5 according to EN 60721-3 |
Permitted Relative Humidity (during Transport) | class 2K5 according to EN 60721-3 |
Pollution Degree | 2 2 conforming to EN/IEC 61800-5-1 |
Product Certifications | ATEX INERIS ATEX zone 2/22 CSA DNV-GL TÜV UL |
Regulation Loop | adjustable PID regulator |
Relative Humidity | 5-95 % without condensation conforming to IEC 60068-2-3 |
Shock Resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Standards | EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 13849-1 IEC 60721-3 IEC 61000-3-12 IEC 61508 UL 508C EN/IEC 61800-3 EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-5-1 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-3 IEC 13849-1 IEC 60721-3 IEC 61000-3-12 IEC 61508 UL 508C |
Vibration Resistance | 1 gn (f= 13-200 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f= 2-13 Hz) conforming to IEC 60068-2-6 |
Volume Of Cooling Air | 103 m3/h |
OTHER | |
Poles Description | variable speed drive |
[Us] Rated Supply Voltage | 380...480 V 380...480 V - 15...10 % |
Write Your Own Review