ATV212HU22N4 - Variable Speed Drive ATV212 - 2.2kW - 3hp - 480V - 3ph - EMC - IP21
Short description of ATV212HU22N4
ATV212 2,2KW 3HP 480V TRI CEM IP20
This Altivar 212 variable speed drive can feed 3-phase asynchronous motors. Its protection index is IP21 and it has a built-in EMC filter. It works at a rated power up to 2.2kW / 3hp and a rated voltage from 380V to 480V AC. Its design is based on eco-energy with a reduction in energy consumption of up to 70% compared to a conventional control system. Thanks to its cable temperature rise reduction technology, the Altivar 212 drive offers immediate, disturbance-free operation avoiding additional options such as a line choke or DC choke to deal with current harmonics. It weighs 2kg and its dimensions are, 107mm wide, 143mm high, 150mm deep. It is specifically designed for the most common fluid management applications in tertiary sector buildings (HVAC) like heating, ventilation, air conditioning and pumping. It conforms to international standards IEC/EN 61800-5-1 and IEC/EN 61800-3 (immunity and conducted and radiated EMC emissions). It is also CE, UL, CSA, C-Tick and NOM certified. The Altivar 212 offers optional motor chokes which can increase the maximum cable lengths between the drive and the motor and limit disturbance at the motor terminals. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. It can also be mounted directly on a 35 mm wide DIN rail, thanks to the kit VW3A31852, to order separately. The Altivar 212 drive can easily be adapted to all building management systems thanks to its numerous functions and communication protocols integrated as standard, Modbus, METASYS N2, APOGEE FLN P1 and BACnet. It is labeled Green Premium and complies with directives such as RoHS, WEEE, and REACh relating to environmental protection.
-  2.2kW
-  3hp
-  480V
-  3ph
-  EMC
-  IP21.
Label :  Altivar 212
-  range of product :  Altivar 212
-  [Us] rated supply voltage :  380...480 V
-  15...10 %
-  supply voltage limits :  323-528 V
-  supply frequency :  50...60 Hz
-  5...5 %
-  network frequency :  47.5...63 Hz
-  EMC filter :  Class C2 EMC filter integrated
-  line current :  3.6 A at 480 V, 4.6 A at 380 V
-  product or component type :  variable speed drive
-  device short name :  ATV212
-  product destination :  asynchronous motors
-  product specific application :  pumps and fans in HVAC
-  assembly style :  with heat sink
-  network number of phases :  3 phases
-  motor power kW :  2.2 kW
-  motor power hp :  3 hp
-  Range Presentation :  The Altivar 212 is a variable speed drive for 3-phase asynchronous motors from 0.75 kW to 75 kW. It is specifically intended for the most commonly encountered fluid management applications in tertiary sector buildings (HVAC) :  heating, ventilation, air conditioning and pumping. Due to its eco
- energy based design, energy savings of up to 70% can be achieved compared to a traditional control system.Characteristics : 
-  Altivar 212 covers motor powers between 0.75 kW and 75 kW on the following supplies : 
•200…240V 3-phase, from 0.75 kW to 30 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, UL Type 12/IP 55
-  Speed range :  1 : 50
-  Transient overtorque :  110%
-  60 s.
-  Integrated EMC filters, categories C1 to C3 depending on model
-  Communication bus most commonly used on the market integrated :  Modbus, METASYS N2®, APOGEE FLN P1® and BACnet®. Optional :  LonWorks
-  Complies to international standards and certifications :  UL, CSA, C
- Tick and NOM
-  Antiharmonic technology enables a THDI
-  Range Benefits :  Centred on Centralised Technical Management
-  Instant viewing of the energy consumption.
-  Detection of failures for quick intervention :  belt breakage, pump running dry, phase failure, supply fault, etc.
-  Preventative maintenance for reducing costs and optimising the equipment :  fault alert, operating time, etc.
-  Connection to building supervision network using embedded protocols.
Centred on user-friendliness
-  Tools for installing, parametering and viewing the installation (remote graphic terminal in 6 languages, Multi-Loader, Bluetooth and SoMove Mobile).
-  Compact size.
-  Simple maintenance.
Centred on protection
-  Continuity of service assured.
-  Dedicated “Building” series functions (fire mode, register monitoring, mechanical protection function, etc.
-  Integrated EMC filter, antiharmonic technology (THDI ˜ 30%).
-  Range Application Presentation :  Ventilation : 
-  Less noise pollution (airdraulic noise, motor noise, etc.).
-  Detection of transmission component breakage.
-  Smoke extraction :  forced start with fault inhibition.
-  Automatic restart.
-  Allows register management. Heating and Air conditioning : 
-  Optimise control in fluid processing.
-  Use of PID controller (temperature, flow rate, pressure, etc.).
-  Adjustable flow rates for better energy management.
-  Suppression of mechanical resonance. Pumping : 
-  Detection of underload/overload, pump running dry.
-  Multi-motor configuration.
-  Limitation of operating time at low speed.
-  Sleep/Wake function.
-  Pressure surge suppression for prolonging the life of the installation.
MAIN SPECIFICATIONS | |
---|---|
Analog/digital Conversion | FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits |
Analogue Input Number | 2 |
Analogue Input Range | 2 |
Discrete Output Type | configurable relay logic: (FLA, FLC) NO - 100000 cycles configurable relay logic: (FLB, FLC) NC - 100000 cycles configurable relay logic: (RY, RC) NO - 100000 cycles |
Display Type | 2-wire RS 485 |
Measurement Accuracy | 1 open style 1 RJ45 |
Physical Interface | 2-wire RS 485 |
Product Or Component Type | variable speed drive |
Range Of Product | Altivar 212 |
Communication Port Protocol | APOGEE FLN BACnet LonWorks METASYS N2 Modbus |
Device Short Name | ATV212 |
EAN13 | 3606480322464 |
EMC Filter | Class C2 EMC filter integrated |
Line Current | 3.6 A at 480 V 4.6 A at 380 V |
Motor Power Hp | 3 hp |
Network Number Of Phases | 3 phases |
Product Specific Application | pumps and fans in HVAC |
Range Name | Altivar 212 |
Speed Range | 1-10 |
COMPLEMENTARY | |
Analogue Input Type | VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits |
Analogue Output Number | 1 |
Analogue Output Type | FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits |
Connector Type | 1 open style 1 RJ45 |
Discrete Output Number | 2 |
Output Voltage | <= power supply voltage |
Port Ethernet | 2 |
[Ics] Rated Service Breaking Capacity | configurable relay logic: (FLA, FLC) NO - 100000 cycles configurable relay logic: (FLB, FLC) NC - 100000 cycles configurable relay logic: (RY, RC) NO - 100000 cycles |
Acceleration And Deceleration Ramps | automatic based on the load linear adjustable separately from 0.01 to 3200 s |
Accuracy | +/- 0.6 % (VIA) for a temperature variation 60 °C +/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C |
Air Flow | 35 m3/h |
Apparent Power | 3.9 kVA at 380 V |
Assembly Style | with heat sink |
Asynchronous Motor Control Profile | flux vector control without sensor, standard voltage/frequency ratio - Energy Saving, quadratic U/f voltage/frequency ratio, 2 points voltage/frequency ratio, 5 points voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) |
Braking To Standstill | by DC injection |
Communication Service | monitoring inhibitable read device identification (43) read holding registers (03) 2 words maximum time out setting from 0.1 to 100 s write multiple registers (16) 2 words maximum write single register (06) |
Continuous Output Current | 5.1 A at 380 V 5.1 A at 460 V |
Data Format | 8 bits, 1 stop, odd even or no configurable parity |
Depth | 150 mm |
Discrete Input Logic | negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1) |
Discrete Input Type | F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm |
Electrical Connection | L1/R, L2/S, L3/T: terminal 6-6 mm² / AWG 10 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5-2.5 mm² / AWG 14 |
Frequency Resolution | analog input: 0.024/50 Hz display unit: 0.1 Hz |
Functionality | mid |
Height | 143 mm |
Insulation Resistance | >= 1 mOhm 500 V DC for 1 minute |
Isolation | electrical between power and control |
Linearity Error | FM: +/- 0.2 % for output VIA: +/- 0.15 % of maximum value for input VIB: +/- 0.15 % of maximum value for input |
Local Signalling | 1 LED (red) for DC bus energized |
Marking | CE |
Maximum Switching Current | 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) |
Maximum Transient Current | 5.6 A for 60 s |
Minimum Switching Current | 3 mA at 24 V DC for configurable relay logic |
Motor Power KW | 2.2 kW |
Motor Slip Compensation | adjustable automatic whatever the load not available in voltage/frequency ratio motor control |
Motor Starter Type | variable speed drive |
Net Weight | 2 kg |
Network Frequency | 47.5...63 Hz |
Nominal Switching Frequency | 12 kHz |
Number Of Addresses | 1-247 |
Operating Position | vertical +/- 10 degree |
Option Card | communication card for LonWorks |
Power Dissipation In W | 103 W |
Power Range | 2.2-3 kW at 380-440 V 3 phases 2.2-3 kW at 480-500 V 3 phases |
Product Destination | asynchronous motors |
Prospective Line Isc | 5 kA |
Protection Type | against exceeding limit speed: drive against input phase loss: drive break on the control circuit: drive input phase breaks: drive line supply overvoltage and undervoltage: drive line supply undervoltage: drive motor phase break: motor overcurrent between output phases and earth: drive overheating protection: drive overvoltages on the DC bus: drive short-circuit between motor phases: drive thermal power stage: drive thermal protection: motor with PTC probes: motor |
Response Time | FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FM 2 ms, tolerance +/- 0.5 ms for analog output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
Sampling Duration | 2 ms +/- 0.5 ms F discrete 2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 22 ms +/- 0.5 ms VIB analog 3.5 ms +/- 0.5 ms VIA analog |
Specific Application | HVAC |
Speed Accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
Speed Drive Output Frequency | 0.5-200 Hz |
Supply | internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection internal supply: 24 V DC (21-27 V), <200 A, protection type: overload and short-circuit protection |
Supply Frequency | 50...60 Hz - 5...5 % |
Supply Voltage Limits | 323-528 V |
Switching Frequency | 12...16 kHz with derating factor 6...16 kHz adjustable |
Tightening Torque | 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) 1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T) |
Torque Accuracy | +/- 15 % |
Transient Overtorque | 120-120 % of nominal motor torque +/- 10 % for 60 s |
Transmission Frame | RTU |
Transmission Rate | 9600 bps or 19200 bps |
Type Of Cable | with UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR |
Type Of Polarization | no impedance |
Width | 107 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -10-40 °C (without derating) 40-50 °C (with derating factor) |
Ambient Air Temperature For Storage | -25-70 °C |
Dielectric Strength | 3535 V DC between earth and power terminals 5092 V DC between control and power terminals |
Electromagnetic Compatibility | 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
Environmental Characteristic | classes 3C1 conforming to IEC 60721-3-3 classes 3S2 conforming to IEC 60721-3-3 |
IP Degree Of Protection | IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP21 |
Noise Level | 51 dB conforming to 86/188/EEC |
Operating Altitude | <= 1000 m without derating 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m |
Pollution Degree | 3 conforming to IEC 61800-5-1 |
Product Certifications | CSA C-Tick NOM 117 UL |
Regulation Loop | adjustable PI regulator |
Relative Humidity | 5-95 % without condensation conforming to IEC 60068-2-3 5-95 % without dripping water conforming to IEC 60068-2-3 |
Shock Resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Standards | EN 55011 class A group 1 EN 61800-3 EN 61800-3 category C2 EN 61800-3 category C3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 EN 61800-5-1 IEC 61800-3 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 UL type 1 |
Vibration Resistance | 1 gn (f= 13-200 Hz) conforming to EN/IEC 60068-2-8 1.5 mm (f= 3-13 Hz) conforming to EN/IEC 60068-2-6 |
OTHER | |
Poles Description | variable speed drive |
[Us] Rated Supply Voltage | 380...480 V - 15...10 % |