ATV212H075N4 - Variable Speed Drive ATV212 - 0.75kW - 1hp - 480V - 3ph - EMC - IP21
Schneider
SKU
SE_ATV212H075N4
Model
ATV212H075N4
SGD $457.79 All prices inclusive of GST
Short description of ATV212H075N4
ATV212H075N4. ATV212 0,75KW 1HP 480V TRI CEM IP20
Country of Origin
Indonesia
variable speed drive ATV212
-  0.75kW
-  1hp
-  480V
-  3ph
-  EMC
-  IP21.
Label :  Altivar 212
-  range of product :  Altivar 212
-  [Us] rated supply voltage :  380...480 V
-  15...10 %
-  supply voltage limits :  323-528 V
-  supply frequency :  50...60 Hz
-  5...5 %
-  network frequency :  47.5...63 Hz
-  EMC filter :  Class C2 EMC filter integrated
-  line current :  1.4 A at 480 V, 1.7 A at 380 V
-  product or component type :  variable speed drive
-  device short name :  ATV212
-  product destination :  asynchronous motors
-  product specific application :  pumps and fans in HVAC
-  assembly style :  with heat sink
-  network number of phases :  3 phases
-  motor power kW :  0.75 kW
-  motor power hp :  1 hp
-  Range Presentation :  The Altivar 212 is a variable speed drive for 3-phase asynchronous motors from 0.75 kW to 75 kW. It is specifically intended for the most commonly encountered fluid management applications in tertiary sector buildings (HVAC) :  heating, ventilation, air conditioning and pumping. Due to its eco
- energy based design, energy savings of up to 70% can be achieved compared to a traditional control system.Characteristics : 
-  Altivar 212 covers motor powers between 0.75 kW and 75 kW on the following supplies : 
•200…240V 3-phase, from 0.75 kW to 30 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, UL Type 12/IP 55
-  Speed range :  1 : 50
-  Transient overtorque :  110%
-  60 s.
-  Integrated EMC filters, categories C1 to C3 depending on model
-  Communication bus most commonly used on the market integrated :  Modbus, METASYS N2®, APOGEE FLN P1® and BACnet®. Optional :  LonWorks
-  Complies to international standards and certifications :  UL, CSA, C
- Tick and NOM
-  Antiharmonic technology enables a THDI 30% to be achieved
-  Range Benefits :  Centred on Centralised Technical Management
-  Instant viewing of the energy consumption.
-  Detection of failures for quick intervention :  belt breakage, pump running dry, phase failure, supply fault, etc.
-  Preventative maintenance for reducing costs and optimising the equipment :  fault alert, operating time, etc.
-  Connection to building supervision network using embedded protocols.
Centred on user-friendliness
-  Tools for installing, parametering and viewing the installation (remote graphic terminal in 6 languages, Multi-Loader, Bluetooth and SoMove Mobile).
-  Compact size.
-  Simple maintenance.
Centred on protection
-  Continuity of service assured.
-  Dedicated “Building” series functions (fire mode, register monitoring, mechanical protection function, etc.
-  Integrated EMC filter, antiharmonic technology (THDI ˜ 30%).
-  Range Application Presentation :  Ventilation : 
-  Less noise pollution (airdraulic noise, motor noise, etc.).
-  Detection of transmission component breakage.
-  Smoke extraction :  forced start with fault inhibition.
-  Automatic restart.
-  Allows register management. Heating and Air conditioning : 
-  Optimise control in fluid processing.
-  Use of PID controller (temperature, flow rate, pressure, etc.).
-  Adjustable flow rates for better energy management.
-  Suppression of mechanical resonance. Pumping : 
-  Detection of underload/overload, pump running dry.
-  Multi-motor configuration.
-  Limitation of operating time at low speed.
-  Sleep/Wake function.
-  Pressure surge suppression for prolonging the life of the installation.
-  0.75kW
-  1hp
-  480V
-  3ph
-  EMC
-  IP21.
Label :  Altivar 212
-  range of product :  Altivar 212
-  [Us] rated supply voltage :  380...480 V
-  15...10 %
-  supply voltage limits :  323-528 V
-  supply frequency :  50...60 Hz
-  5...5 %
-  network frequency :  47.5...63 Hz
-  EMC filter :  Class C2 EMC filter integrated
-  line current :  1.4 A at 480 V, 1.7 A at 380 V
-  product or component type :  variable speed drive
-  device short name :  ATV212
-  product destination :  asynchronous motors
-  product specific application :  pumps and fans in HVAC
-  assembly style :  with heat sink
-  network number of phases :  3 phases
-  motor power kW :  0.75 kW
-  motor power hp :  1 hp
-  Range Presentation :  The Altivar 212 is a variable speed drive for 3-phase asynchronous motors from 0.75 kW to 75 kW. It is specifically intended for the most commonly encountered fluid management applications in tertiary sector buildings (HVAC) :  heating, ventilation, air conditioning and pumping. Due to its eco
- energy based design, energy savings of up to 70% can be achieved compared to a traditional control system.Characteristics : 
-  Altivar 212 covers motor powers between 0.75 kW and 75 kW on the following supplies : 
•200…240V 3-phase, from 0.75 kW to 30 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, UL Type 12/IP 55
-  Speed range :  1 : 50
-  Transient overtorque :  110%
-  60 s.
-  Integrated EMC filters, categories C1 to C3 depending on model
-  Communication bus most commonly used on the market integrated :  Modbus, METASYS N2®, APOGEE FLN P1® and BACnet®. Optional :  LonWorks
-  Complies to international standards and certifications :  UL, CSA, C
- Tick and NOM
-  Antiharmonic technology enables a THDI
-  Range Benefits :  Centred on Centralised Technical Management
-  Instant viewing of the energy consumption.
-  Detection of failures for quick intervention :  belt breakage, pump running dry, phase failure, supply fault, etc.
-  Preventative maintenance for reducing costs and optimising the equipment :  fault alert, operating time, etc.
-  Connection to building supervision network using embedded protocols.
Centred on user-friendliness
-  Tools for installing, parametering and viewing the installation (remote graphic terminal in 6 languages, Multi-Loader, Bluetooth and SoMove Mobile).
-  Compact size.
-  Simple maintenance.
Centred on protection
-  Continuity of service assured.
-  Dedicated “Building” series functions (fire mode, register monitoring, mechanical protection function, etc.
-  Integrated EMC filter, antiharmonic technology (THDI ˜ 30%).
-  Range Application Presentation :  Ventilation : 
-  Less noise pollution (airdraulic noise, motor noise, etc.).
-  Detection of transmission component breakage.
-  Smoke extraction :  forced start with fault inhibition.
-  Automatic restart.
-  Allows register management. Heating and Air conditioning : 
-  Optimise control in fluid processing.
-  Use of PID controller (temperature, flow rate, pressure, etc.).
-  Adjustable flow rates for better energy management.
-  Suppression of mechanical resonance. Pumping : 
-  Detection of underload/overload, pump running dry.
-  Multi-motor configuration.
-  Limitation of operating time at low speed.
-  Sleep/Wake function.
-  Pressure surge suppression for prolonging the life of the installation.
MAIN SPECIFICATIONS | |
---|---|
Analog/digital Conversion | FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits |
Analogue Input Number | 2 |
Analogue Input Range | 2 |
Discrete Output Type | configurable relay logic: (FLA, FLC) NO - 100000 cycles configurable relay logic: (FLB, FLC) NC - 100000 cycles configurable relay logic: (RY, RC) NO - 100000 cycles |
Display Type | 2-wire RS 485 |
Measurement Accuracy | 1 open style 1 RJ45 |
Physical Interface | 2-wire RS 485 |
Product Or Component Type | variable speed drive |
Range Of Product | Altivar 212 |
Communication Port Protocol | APOGEE FLN BACnet LonWorks METASYS N2 Modbus |
Device Short Name | ATV212 |
EAN13 | 3606480322440 |
EMC Filter | Class C2 EMC filter integrated |
Line Current | 1.4 A at 480 V 1.7 A at 380 V |
Motor Power Hp | 1 hp |
Network Number Of Phases | 3 phases |
Product Specific Application | pumps and fans in HVAC |
Range Name | Altivar 212 |
Speed Range | 1-10 |
COMPLEMENTARY | |
Analogue Input Type | VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits |
Analogue Output Number | 1 |
Analogue Output Type | FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits |
Connector Type | 1 open style 1 RJ45 |
Discrete Output Number | 2 |
Output Voltage | <= power supply voltage |
Port Ethernet | 2 |
[Ics] Rated Service Breaking Capacity | configurable relay logic: (FLA, FLC) NO - 100000 cycles configurable relay logic: (FLB, FLC) NC - 100000 cycles configurable relay logic: (RY, RC) NO - 100000 cycles |
Acceleration And Deceleration Ramps | automatic based on the load linear adjustable separately from 0.01 to 3200 s |
Accuracy | +/- 0.6 % (VIA) for a temperature variation 60 °C +/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C |
Air Flow | 19 m3/h |
Apparent Power | 1.6 kVA at 380 V |
Assembly Style | with heat sink |
Asynchronous Motor Control Profile | flux vector control without sensor, standard voltage/frequency ratio - Energy Saving, quadratic U/f voltage/frequency ratio, 2 points voltage/frequency ratio, 5 points voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) |
Braking To Standstill | by DC injection |
Communication Service | monitoring inhibitable read device identification (43) read holding registers (03) 2 words maximum time out setting from 0.1 to 100 s write multiple registers (16) 2 words maximum write single register (06) |
Continuous Output Current | 2.2 A at 380 V 2.2 A at 460 V |
Data Format | 8 bits, 1 stop, odd even or no configurable parity |
Depth | 150 mm |
Discrete Input Logic | negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1) |
Discrete Input Type | F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm |
Electrical Connection | L1/R, L2/S, L3/T: terminal 6-6 mm² / AWG 10 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5-2.5 mm² / AWG 14 |
Frequency Resolution | analog input: 0.024/50 Hz display unit: 0.1 Hz |
Functionality | mid |
Height | 143 mm |
Insulation Resistance | >= 1 mOhm 500 V DC for 1 minute |
Isolation | electrical between power and control |
Linearity Error | FM: +/- 0.2 % for output VIA: +/- 0.15 % of maximum value for input VIB: +/- 0.15 % of maximum value for input |
Local Signalling | 1 LED (red) for DC bus energized |
Marking | CE |
Maximum Switching Current | 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) |
Maximum Transient Current | 2.4 A for 60 s |
Minimum Switching Current | 3 mA at 24 V DC for configurable relay logic |
Motor Power KW | 0.75 kW |
Motor Slip Compensation | adjustable automatic whatever the load not available in voltage/frequency ratio motor control |
Motor Starter Type | variable speed drive |
Net Weight | 2 kg |
Network Frequency | 47.5...63 Hz |
Nominal Switching Frequency | 12 kHz |
Number Of Addresses | 1-247 |
Operating Position | vertical +/- 10 degree |
Option Card | communication card for LonWorks |
Power Dissipation In W | 55 W |
Power Range | 0.55-1 kW at 380-440 V 3 phases 0.55-1 kW at 480-500 V 3 phases |
Product Destination | asynchronous motors |
Prospective Line Isc | 5 kA |
Protection Type | against exceeding limit speed: drive against input phase loss: drive break on the control circuit: drive input phase breaks: drive line supply overvoltage and undervoltage: drive line supply undervoltage: drive motor phase break: motor overcurrent between output phases and earth: drive overheating protection: drive overvoltages on the DC bus: drive short-circuit between motor phases: drive thermal power stage: drive thermal protection: motor with PTC probes: motor |
Response Time | FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FM 2 ms, tolerance +/- 0.5 ms for analog output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
Sampling Duration | 2 ms +/- 0.5 ms F discrete 2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 22 ms +/- 0.5 ms VIB analog 3.5 ms +/- 0.5 ms VIA analog |
Specific Application | HVAC |
Speed Accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
Speed Drive Output Frequency | 0.5-200 Hz |
Supply | internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection internal supply: 24 V DC (21-27 V), <200 A, protection type: overload and short-circuit protection |
Supply Frequency | 50...60 Hz - 5...5 % |
Supply Voltage Limits | 323-528 V |
Switching Frequency | 12...16 kHz with derating factor 6...16 kHz adjustable |
Tightening Torque | 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) 1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T) |
Torque Accuracy | +/- 15 % |
Transient Overtorque | 120-120 % of nominal motor torque +/- 10 % for 60 s |
Transmission Frame | RTU |
Transmission Rate | 9600 bps or 19200 bps |
Type Of Cable | with UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR |
Type Of Polarization | no impedance |
Width | 107 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -10-40 °C (without derating) 40-50 °C (with derating factor) |
Ambient Air Temperature For Storage | -25-70 °C |
Dielectric Strength | 3535 V DC between earth and power terminals 5092 V DC between control and power terminals |
Electromagnetic Compatibility | 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
Environmental Characteristic | classes 3C1 conforming to IEC 60721-3-3 classes 3S2 conforming to IEC 60721-3-3 |
IP Degree Of Protection | IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP21 |
Noise Level | 51 dB conforming to 86/188/EEC |
Operating Altitude | <= 1000 m without derating 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m |
Pollution Degree | 2 conforming to IEC 61800-5-1 |
Product Certifications | CSA C-Tick NOM 117 UL |
Regulation Loop | adjustable PI regulator |
Relative Humidity | 5-95 % without condensation conforming to IEC 60068-2-3 5-95 % without dripping water conforming to IEC 60068-2-3 |
Shock Resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Standards | EN 55011 class A group 1 EN 61800-3 EN 61800-3 category C2 EN 61800-3 category C3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 EN 61800-5-1 IEC 61800-3 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 UL type 1 |
Vibration Resistance | 1 gn (f= 13-200 Hz) conforming to EN/IEC 60068-2-8 1.5 mm (f= 3-13 Hz) conforming to EN/IEC 60068-2-6 |
OTHER | |
Poles Description | variable speed drive |
[Us] Rated Supply Voltage | 380...480 V - 15...10 % |