A9XMZA08 - Acti9 Smartlink SI B - Modbus TCP/IP and Wireless Communication Module.
Schneider
SKU
SE_A9XMZA08
Model
A9XMZA08
SGD $810.81 All prices inclusive of GST
Short description of A9XMZA08
A9XMZA08. Monitor and control your large business electrical equipment via your supervision system
Country of Origin
France
range of product : Acti 9
-  product name : Acti 9 Smartlink
-  product or component type : Smart communication module
-  device short name : Smartlink SI B Ethernet
-  Application type : Basic energy metering EImproved load monitoring E, U, I, P, PfLoad alarmingLoad controlBreaker status monitoring
-  Number max of connected devices : Up to 7 wired devicesUp to 20 wireless devices
-  group of channels : 1 group of 7 digital channels1 group of 1 analog channel
-  maximum supply current : 1.5 A
-  [Us] rated supply voltage : 24 V DC +/- 20 %
-  connectivity to devices : Analog inputDigital input and outputPulse output meterWireless energy sensor
-  communication service : Ethernet Modbus TCP/IP serverWeb server
-  web server : BMS controller compatibleEmbedded web page
-  transmission support medium : Radio frequency 2.4…2.4835 GHz PowerTag 20
-  web services : Web page
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
-  product name : Acti 9 Smartlink
-  product or component type : Smart communication module
-  device short name : Smartlink SI B Ethernet
-  Application type : Basic energy metering EImproved load monitoring E, U, I, P, PfLoad alarmingLoad controlBreaker status monitoring
-  Number max of connected devices : Up to 7 wired devicesUp to 20 wireless devices
-  group of channels : 1 group of 7 digital channels1 group of 1 analog channel
-  maximum supply current : 1.5 A
-  [Us] rated supply voltage : 24 V DC +/- 20 %
-  connectivity to devices : Analog inputDigital input and outputPulse output meterWireless energy sensor
-  communication service : Ethernet Modbus TCP/IP serverWeb server
-  web server : BMS controller compatibleEmbedded web page
-  transmission support medium : Radio frequency 2.4…2.4835 GHz PowerTag 20
-  web services : Web page
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 24 V DC +/- 20 % |
Power Supply Output Current | BMS controller compatible embedded web page |
Product Or Component Type | smart communication module |
Range Of Product | Acti 9 |
Web Server | BMS controller compatible embedded web page |
[Uc] Control Circuit Voltage | Ethernet Modbus TCP/IP server RJ45 10/100 Mbit/s RS485 Modbus RTU master SUB-D 9 9.6...19.2 kbauds |
Connected Auxiliaries | up to 20 wireless devices up to 7 wired devices |
Connectivity To Devices | analog input digital input and output pulse output meter wireless energy sensor |
Device Short Name | Smartlink SI B Ethernet |
Group Of Channels | 1 group of 1 analog channel 1 group of 7 digital channels |
Range | Acti 9 |
Range Compatibility | Acti 9 C40 Acti 9 DT40 Acti 9 DT60 Acti 9 iCT auxiliary Acti 9 iDPN Acti 9 I-NA Acti 9 Reflex iC60 Ti24 connector Acti9 iC60 Acti9 iDPN Vigi Acti9 iID Acti9 iSW-NA Acti9 ITG40 C60 iACT24 iATL24 iOF+SD 24 iTL auxiliary Linergy FM Modbus meter PowerTag wireless energy sensor pulse output meter RCA iC60 |
Range Name | Acti 9 Smartlink SI B |
Transmission Support Medium | radio frequency 2.4-2.4835 GHz PowerTag 20 |
COMPLEMENTARY | |
Communication Network Type | Ethernet Modbus TCP/IP server RJ45 10/100 Mbit/s RS485 Modbus RTU master SUB-D 9 9.6...19.2 kbauds |
Product Name | Acti 9 Smartlink |
9 Mm Pitches | 0 useful |
Absolute Accuracy Error | +/- 1 % of full scale for analog input 12 bits |
Application Specific I/O | pulse converter pulse totalising counter |
Clamping Connection Capacity | 1 x 0.5...1 x 1.5 mm², flexible with cable end for control 1 x 0.5...1 x 1.5 mm², flexible without cable end for control 1 x 0.5...1 x 1.5 mm², rigid with cable end for control 1 x 0.5...1 x 1.5 mm², rigid without cable end for control 2 x 0.2...2 x 1.5 mm², flexible with cable end for supply circuit 2 x 0.2...2 x 1.5 mm², flexible without cable end for supply circuit 2 x 0.2...2 x 1.5 mm², rigid with cable end for supply circuit 2 x 0.2...2 x 1.5 mm², rigid without cable end for supply circuit 2 x 0.25 mm² for twisted shielded pairs cable, flexible with cable end for communication bus 2 x 0.25 mm² for twisted shielded pairs cable, flexible without cable end for communication bus 2 x 0.25 mm² for twisted shielded pairs cable, rigid with cable end for communication bus 2 x 0.25 mm² for twisted shielded pairs cable, rigid without cable end for communication bus 2 x 0.25...2 x 1.5 mm² for twisted shielded pairs cable, flexible with cable end for analog input 2 x 0.25...2 x 1.5 mm² for twisted shielded pairs cable, flexible without cable end for analog input 2 x 0.25...2 x 1.5 mm² for twisted shielded pairs cable, rigid with cable end for analog input 2 x 0.25...2 x 1.5 mm² for twisted shielded pairs cable, rigid without cable end for analog input |
Colour | white (RAL 9003) |
Commissioning Interface | ECOREACH web page |
Communication Service | Ethernet Modbus TCP/IP server web server |
Compatibility Code | Acti 9 Smartlink IP |
Connections - Terminals | plug-in connector qty: 1 for analog input plug-in connector qty: 1 for communication bus plug-in connector qty: 1 for supply circuit RJ45 connector qty: 1 for ETHERNET, ordered separately spring-loaded terminal Ti24 qty: 7 for digital input/output, ordered separately |
Depth | 42 mm |
Device Application | basic energy metering E breaker status monitoring improved load monitoring E, U, I, P, Pf load alarming load control |
Electronic Filtering Time | 2 ms for analog input from state 0 to state 1 2 ms for digital input from state 0 to state 1 |
Height | 22.5 mm |
Immunity To Microbreaks | 10 ms |
Input Type | current for analog input, 4...20 mA current sink for digital input, 24 V DC +/- 20 % at 2.5 mA voltage for analog input, 0...10 V DC |
Input/output Type | 2 inputs + 1 output per digital channel 2 inputs per analog channel |
Inrush Current | 0.5 A for digital output 3 A for power supply |
Local Signalling | communication (LK/ACT 10/100): 1 LED (green and yellow) communication: 1 LED (yellow) NS (Network Status): 1 LED (green, orange and red) status: 1 LED (green, orange and red) |
Location Of Connection | front |
Maximum Permanent Current | 0.005 A for digital input |
Maximum Supply Current | 1.5 A |
Maximum Voltage Drop | <1 V at state 1 digital output |
Mounting Position | horizontal and vertical on DIN rail |
Net Weight | 180 g |
Output Type | logic current source: 24 V - DC - 100 mA |
Protection Type | against reverse polarity for auxiliary supply against reverse polarity for input overvoltage at 33 V DC for digital output short-circuit protection for analog input |
Provided Equipment | set of 1 bus connector set of 1 connector set of 1 power supply connector set of 2 locking clips |
Reset | factory reset on front face |
Web Services | web page |
Width | 359 mm |
Wire Stripping Length | analog input: 7 mm communication bus: 7 mm control: 10 mm supply circuit: 7 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-60 °C |
Ambient Air Temperature For Storage | -40-80 °C |
Electromagnetic Compatibility | communication bus: resistance to fast transient, 1 kV, conforming to IEC 61000-4-4 conducted EMC (0.15...80 MHz), 10 V, conforming to IEC 61000-4-6 conducted emission (0.15...30 MHz), class A, conforming to IEC 61131-2 immunity to magnetic fields at network frequency, 30 A/m, conforming to IEC 61000-4-8 input/output: resistance to fast transient, 1 kV, conforming to IEC 61000-4-4 power supply: resistance to fast transient (5...100 kHz), 2 kV, conforming to IEC 61000-4-4 radiated emission (30...1000 MHz), class A, conforming to IEC 61131-3 Ed.3 resistance to electrostatic discharge (air discharge), 8 kV, conforming to IEC 61000-4-2 resistance to electrostatic discharge (contact discharge), 4 kV, conforming to IEC 61000-4-2 resistance to radiated electromagnetic fields (80 MHz...3 GHz), 10 V/m, conforming to IEC 61000-4-3 |
Environmental Characteristic | corrosive 3C2 conforming to IEC 60721-3-3 salt mist 2 conforming to IEC 60068-2-52 |
Fire Resistance | on connection terminals: 960 °C ( 30 s ) conforming to IEC 60695-2-10 other parts: 650 °C ( 30 s ) conforming to IEC 60695-2-10 |
IP Degree Of Protection | IP20 |
Operating Altitude | 0...2000 m |
Pollution Degree | 3 |
Relative Humidity | 93-93 % at 40-40 °C |
Shock Resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Tropicalisation | 2 |
Vibration Resistance | 1 gn, amplitude = 3.5 mm (f = 5-300 Hz)10 cycles conforming to IEC 60068-2-6 |
OTHER | |
Poles Description | smart communication module |
[Us] Rated Supply Voltage | 24 V DC +/- 20 % |
Write Your Own Review