A9L16182 - Modular surge arrester, Acti9 iPRD1 12.5r , 1 P, 230 V, with remote transfert
Schneider
SKU
SE_A9L16182
Model
A9L16182
SGD $155.88 All prices inclusive of GST
Short description of A9L16182
A9L16182. This Acti9 iPRD1 12.5r surge arrester protects 1P residential and small commercial buildings installations against direct and indirect transient overvoltages. This type 1+2 device autoprotected by an integrated circuit-breaker is recommanded for high risk level in incoming panel board. It offers remote reporting of the "cartridge must be changed" message. This prewired surge arrester allows quick replacement of withdrawable cartridges when they are damaged. It incorporates its end of life safety disconnector. This Acti9 iPRD1 12.5r is compatible with TN-C earthing system. Associated with Compact NSXm H TM80D the breaking capacity is 70kA. The Imax maximum discharge current is 50kA. The In nominal discharge current is 20kA. The Uc maximum continuous operating voltage in common mode is 350VAC between phase and earth. The Up Voltage protection level is 1.5kV type 1+2. The Ue rated operational voltage is 230VAC. The operating frequency is 50Hz. The dimensions are (W) 18mm x (H) 89mm x (D) 69mm. The width in 9mm pitches is 2. The weight is 171g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to +60°C. The storage temperature is -40°C to +80°C. This product is complies with EN 61643-11 2012 and IEC 61643-11 2011 standards.
Country of Origin
China
MAIN | |
---|---|
Range Of Product | Acti9 |
Product Name | Acti9 iPRD1 |
Product Or Component Type | Surge arrester |
Device Short Name | iPRD1 12.5 |
Device Application | Distribution |
Standards | EN 61643-11:2012 IEC 61643-11:2011 |
Quality Labels | CE EAC VDE |
Poles Description | 1P |
Remote Signalling | With |
Signal Contacts Composition | 1 SD (1 C/O) |
Surge Arrester Type | Electrical distribution network |
Earthing System | TN-C |
COMPLEMENTARY | |
Surge Arrester Class Type | Type 1 + 2 |
Surge Arrester Technology | MOV + GDT |
[Ue] Rated Operational Voltage | 230 V AC (+/- 10 %) at 50...60 Hz |
[In] Nominal Discharge Current | 20 kA |
[Imax] Maximum Discharge Current | 50 kA |
[Iimp] Impulse Current | Common mode: 12.5 kA L/PE |
[Uc] Maximum Continuous Operating Voltage | Common mode: 350 V L/PE |
Maximum [Up] Voltage Protection Level | <1.5 kV type 1 + 2 |
Residual Current | 0.9 mA L/PE |
[Ut] Temporary Overvoltage | 442 V L/PE 120 min withstand 1455 V L/PE 200 ms safe failure mode |
Disconnector Device Type | Associated fuse gG 160 A 120 kA standard Associated circuit breaker Compact NSX160E 80 A 25 kA standard |
Local Signalling | Operating: mechanical indicator (white) End of life: mechanical indicator (red) |
Mounting Mode | Clip-on (DIN rail) |
9 Mm Pitches | 2 |
Height | 89 mm |
Width | 18 mm |
Depth | 69 mm |
Net Weight | 171 g |
Colour | White (RAL 9003) |
Material | PA6 |
Connections - Terminals | Tunnel type terminal (phase) 10…25 mm² flexible Tunnel type terminal (phase) 10…35 mm² rigid Tunnel type terminal (earth) 16…25 mm² flexible Tunnel type terminal (earth) 16…35 mm² rigid |
Wire Stripping Length | 14 mm |
Tightening Torque | 3.5 N.m |
ENVIRONMENT | |
IK Degree Of Protection | IK05 conforming to IEC 62262 |
Pollution Degree | 3 |
Relative Humidity | 5…95 % |
Operating Altitude | 2000 m |
Ambient Air Temperature For Operation | -25…60 °C |
Ambient Air Temperature For Storage | -40…80 °C |