Earth-leakage Relay RH99P with Manual Reset - 0.03..30 A - 0..4.5 S - 240 V
Schneider
SKU
SE_56273
Model
56273
SGD $297.17 All prices inclusive of GST
Short description of 56273
EARTHLEAKAGE RELAY RH99P WITH MANUAL RES
Country of Origin
France
Earth
- leakage relay RH99P with manual reset
-  0.03..30 A
-  0..4.5 s
-  240 V.
Label :  Vigirex RH10MP
- RH21MP
- RH99MP
- RH197-RHU
-  range :  Vigirex
-  range of product :  Vigirex
-  device short name :  RH99P
-  product or component type :  residual current protection relay
-  range compatibility :  ,
-  relay application :  residual current protection relay
-  Range Presentation : 
-  Earth leakage protection and/or indication function
-  Supply voltage : up to 525 V AC, 12 to 48 V DC
-  Available in DIN format and flush-mounted (format 72X72)
-  Wide setting and operating range
-  Operation guaranteed in less than 40 ms
-  Reduced tripping tolerance :  between 0.8 and 1xIΔn
-  RMS measurement of earth leakage currents
-  Surge category :  level IV
-  Class 2 device on the front panel
-  Test and reset buttons on the front panel of the device
-  Optional live testing with or without tripping
-  Extended range of compatible sensors up to 3200 A :  A type closed toroids, OA type split toroids and rectangular sensors
-  High electromagnetic immunity (EMC)
-  Compliance with international standards IEC 60947-2 and 5-1 and IEC 60755, IEC 60364, IEC 61000, IEC 60664, CISPR 11 and UL1053
-  Range Benefits :  Monitor and act in greater safetyDesigned to be adapted to all installation types, Vigirex is a comprehensive range of earth leakage protection and indication devices. With Vigirex, all measures are taken for absolute safety, in complete peace of mind.
-  Range Application Presentation :  The Vigirex residual current relays, combined with a toroid, provide protection against earth leakage currents for all LV electrical network types less than 1000 V, regardless of the type of earthing system (IT, TT or TNS). They protect equipment and people against direct and indirect contact, and equipment against fire hazards.
Specific applications : 
-  Air bases (400 Hz)
-  Telephone relays
-  Radio relays
- leakage relay RH99P with manual reset
-  0.03..30 A
-  0..4.5 s
-  240 V.
Label :  Vigirex RH10MP
- RH21MP
- RH99MP
- RH197-RHU
-  range :  Vigirex
-  range of product :  Vigirex
-  device short name :  RH99P
-  product or component type :  residual current protection relay
-  range compatibility :  ,
-  relay application :  residual current protection relay
-  Range Presentation : 
-  Earth leakage protection and/or indication function
-  Supply voltage : up to 525 V AC, 12 to 48 V DC
-  Available in DIN format and flush-mounted (format 72X72)
-  Wide setting and operating range
-  Operation guaranteed in less than 40 ms
-  Reduced tripping tolerance :  between 0.8 and 1xIΔn
-  RMS measurement of earth leakage currents
-  Surge category :  level IV
-  Class 2 device on the front panel
-  Test and reset buttons on the front panel of the device
-  Optional live testing with or without tripping
-  Extended range of compatible sensors up to 3200 A :  A type closed toroids, OA type split toroids and rectangular sensors
-  High electromagnetic immunity (EMC)
-  Compliance with international standards IEC 60947-2 and 5-1 and IEC 60755, IEC 60364, IEC 61000, IEC 60664, CISPR 11 and UL1053
-  Range Benefits :  Monitor and act in greater safetyDesigned to be adapted to all installation types, Vigirex is a comprehensive range of earth leakage protection and indication devices. With Vigirex, all measures are taken for absolute safety, in complete peace of mind.
-  Range Application Presentation :  The Vigirex residual current relays, combined with a toroid, provide protection against earth leakage currents for all LV electrical network types less than 1000 V, regardless of the type of earthing system (IT, TT or TNS). They protect equipment and people against direct and indirect contact, and equipment against fire hazards.
Specific applications : 
-  Air bases (400 Hz)
-  Telephone relays
-  Radio relays
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 220...240 V AC 50/60 Hz 55...110 % |
Product Or Component Type | residual current protection relay |
Device Short Name | RH99P |
EAN13 | 3303430562733 |
Earth-leakage Protection Class | type A |
Mounting Support | front panel |
Range | VigiPacT |
Range Compatibility | A earth leakage current sensor L earth leakage current sensor TOA earth leakage current sensor |
Range Name | Vigirex RH10MP, RH21MP, RH99MP, RH197, RHU |
Relay Application | protection relay |
Type Of Measurement | earth fault current internal measurement, range: 80...100 % |
[Ithe] Conventional Enclosed Thermal Current | 8 A |
COMPLEMENTARY | |
Time Delay Range | 0.03-30 A |
Compatibility Code | RH99P |
Connections - Terminals | auxiliary power supply: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 auxiliary power supply: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 auxiliary power supply: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 fault: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 fault: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 fault: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 relay test and fault reset: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 relay test and fault reset: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 relay test and fault reset: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 sensor: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 sensor: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 sensor: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 voltage presence: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 voltage presence: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 voltage presence: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 |
Cut-out Dimensions | 68 x 68 mm |
Depth | 78 mm |
Earthing System | IT TN-S TT |
Height | 72 mm |
Mechanical Robustness | fire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 vibrations 13.2...100 Hz: 0.7 g vibrations 2...13.2 Hz: +/- 1 mm |
Minimum Load | 10 mA at 12 V |
Monitoring | electronics (continuous) power supply (continuous) relay/sensor link (continuous) |
Net Weight | 0.3 kg |
Network Rated Voltage | 1000-1000 V - AC at 400 Hz (maximum) 1000-1000 V - AC at 50/60 Hz (maximum) |
Power Consumption In VA | 4 VA |
Reset | manual reset |
Residual Earth-leakage Sensitity Adjustment Type | adjustable 9 settings |
Residual Earth-leakage Time Delay Adjustment Type | adjustable 9 settings 0-4.5 s for 0.03-30 A instantaneous for 0.03-0.03 A |
Tamperproof Of Settings | protected by sealable cover |
Test Function | local remote test |
Tightening Torque | auxiliary power supply: 0.6-0.6 N.m fault: 0.6-0.6 N.m relay test and fault reset: 0.6-0.6 N.m sensor: 0.6-0.6 N.m voltage presence: 0.6-0.6 N.m |
Type Of Setting | selector |
Width | 72 mm |
Wire Stripping Length | auxiliary power supply: 7 mm fault: 7 mm relay test and fault reset: 7 mm sensor: 7 mm voltage presence: 7 mm |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -35-70 °C |
Ambient Air Temperature For Storage | -55-85 °C |
Electrical Shock Protection Class | class II |
Electromagnetic Compatibility | conducted and radiated emissions: , B, conforming to CISPR 11 conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 high-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 radiated susceptibility: , 3, conforming to IEC 61000-4-3 |
IK Degree Of Protection | IK07 conforming to EN 50102 |
IP Degree Of Protection | IP20 on connection terminals: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP40 on front face: conforming to EN/IEC 60529 |
Overvoltage Category | IV |
Pollution Degree | 3 conforming to IEC 60664-1 |
Relative Humidity | 95-95 % at 55-55 °C |
OTHER | |
Earth Leakage Current | 0.03-30 A |
Poles Description | residual current protection relay |
[Us] Rated Supply Voltage | 220...240 V AC 50/60 Hz 55...110 % |