2CSF204001R2630 - F204 AC-63/0.1 Residual Current Circuit Breaker
ABB
SKU
AB_2CSF204001R2630
Model
F204-AC-63/0.1
SGD $232.30 All prices inclusive of GST
Get 10% OFF, apply code: ABB10OFF
Min. spend $100
Min. spend $100
Short description of F204 AC 63/0.1
Catalog No: 2CSF204001R2630
F204 AC-63/0.1 Residual Current Circuit Breaker
F204 AC-63/0.1 Residual Current Circuit Breaker
Country of Origin
Italy (IT)
The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications.
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB2CSF204001R2630 |
Business Area (Master Data) Name | Electrification |
Catalog Description | F204 AC-63/0,1 Residual Current Circuit Breaker |
Division (Master Data) Name | Smart Buildings |
EAN | 8012542781707 |
Rated Insulation Voltage (Ui) | 500 volt |
SKU ID | 2CSF204001R2630 |
TECHNICAL | |
Accessories Available | Yes |
Connecting Capacity | Busbar 10 mm² Rigid 25 ... 25 mm² Flexible 25 ... 25 mm² |
Electrical Endurance | 10000 cycle |
Maximum Surge Current | 0.25 kA |
Operating Characteristic | Instantaneous |
Options Provided | None |
Pollution Degree | 2 |
Position Of Neutral Terminals | Right |
Power Loss | at Rated Operating Conditions per Pole 4.4 W |
Power Supply Connection | Arbitrary |
Product Name | Residual Current Circuit Breaker |
Rated Cross-Section | 4 - Multi-Wired 0...25 mm² 1 - Solid-Core 25...25 mm² |
Rated Frequency (f) | 50 / 60 Hz |
Standards | IEC/EN 61008 UL 1053 |
TECHNICAL UL/CSA | |
Maximum Operating Voltage UL/CSA | 480Y / 277 V AC |
Short-Circuit Current Rating (SCCR) | 0.1 A |
DIMENSIONS | |
Built-In Depth (t2) | 69 mm |
ORDERING | |
Minimum Order Quantity | 1 piece |
Selling Unit Of Measure | piece |
ENVIRONMENTAL | |
Ambient Temperature | -25...55 °C |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
CN8 | 85363030 |
EPLAN Catalog Tree | Electrical engineering / Protection devices / Ground fault current circuit breaker |
EPLAN Function Definition | Ground fault current circuit-breaker / Ground fault current circuit breakers, 8 connection points / Ground fault current circuit breaker, four-pole 1_2_3_4_5_6_N_N. |
ETIM 6 | EC000003 - Residual current circuit breaker (RCCB) |
ETIM 7 | EC000003 - Residual current circuit breaker (RCCB) |
ETIM 8 | EC000003 - Residual current circuit breaker (RCCB) |
Object Classification Code | F |
WEEE B2C / B2B | Business To Consumer |
OTHER | |
Ambient Air Temperature | Operation -25...55 °C |
Degree Of Protection | IP2X |
Leakage Current Type | AC |
Mounting Type | DIN rail |
Number Of Poles | 4 |
Product Net Width | 0.07 |
Rated Conditional Short-Circuit Current (Inc) | 10 kA |
Rated Current (In) | 63 A |
Rated Impulse Withstand Voltage (Uimp) | 4 kilovolt |
Rated Operational Voltage | 230/400 V |
Rated Residual Current | 100 mA |
Rated Service Short-Circuit Breaking Capacity (Ics) | 1 kA |
Rated Voltage (Ur) | 230/400 V |
Type Of Residual Current | AC type |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Width In Number Of Modular Spacings | 4 |