Loading...
*All information are subjected to changes without prior notice.

2CDS283001R0325 - S203P-B32 Miniature Circuit Breaker - 3P - B - 32 A

ABB
SKU
AB_2CDS283001R0325
Model
S203P-B32

Obsolete

All prices inclusive of GST

Short description of S203P B32

Catalog No: 2CDS283001R0325
S203P-B32 Miniature Circuit Breaker - 3P - B - 32 A
Obsolete
System pro M compact S200P miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 25 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200P comply with IEC/EN 60898-1, IEC/EN 609 47-2, UL1077 and CSA 22.2 No. 235, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200P to save 50% space.
MAIN SPECIFICATION
ABB Global IDABB2CDS283001R0325
Business Area (Master Data) NameElectrification
Catalog DescriptionS203P-B32 Miniature Circuit Breaker B-Char.,15kA,32A,3P
Division (Master Data) NameSmart Buildings
EAN4016779589833
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 440 volt
SKU ID2CDS283001R0325
TECHNICAL
Accessories AvailableYes
Actuator MarkingI / O
Actuator MaterialInsulation Group II, Black, Sealable
Connecting CapacityBusbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 16 mm²
Flexible 0.75 ... 16 mm²
Rigid 0.75 ... 25 mm²
Stranded 0.75 ... 25 mm²
Contact Position IndicationRed ON / Green OFF
Dielectric Test Voltage50/60 Hz, 1 min: 2 kV
Electrical Endurance10000 AC cycle
Energy Limiting Class3
Housing MaterialInsulation Group II, RAL 7035
Installation Sizeacc. to DIN 43880 1
Mechanical Endurance (Nendu)20000 cycle
Mounting On DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting PositionAny
Number Of Protected Poles3
Overvoltage CategoryIII
Pollution Degree3
Power Loss12.6 W
at Rated Operating Conditions per Pole 4.2 W
Power Supply ConnectionArbitrary
Product NameMiniature Circuit Breaker
Product RangeS200P
Rated Frequency (f)50 / 60 Hz
Recommended Screw DriverPozidriv 2
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
StandardsCSA 22.2 No. 235
IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Terminal TypeScrew Terminals
Tightening Torque2.8 N·m
TECHNICAL UL/CSA
Connecting Capacity UL/CSABusbar 18-8 AWG
Conductor 18-4 AWG
Interrupting Rating Acc. To UL1077(480 V AC) 10 kA
(480Y / 277 V AC) 6 kA
Maximum Operating Voltage UL/CSA480Y/277 V AC
Tightening Torque UL/CSA25 in·lb
DIMENSIONS
Built-In Depth (t2)69 mm
Pole Net Weight0.14 kg
ORDERING
Minimum Order Quantity1 piece
Selling Unit Of Measurepiece
ENVIRONMENTAL
Environmental Conditions28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Reference Ambient Air Temperature30 °C
Resistance To Shock Acc. To IEC 60068-2-2725g / 2 shocks / 13 ms
Resistance To Vibrations Acc. To IEC 60068-2-65g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
CN88536 20 10
E-Number (Finland)3216101
EClassV11.0 : 27141901
EPLAN Catalog TreeElectrical engineering / Protection devices / General
EPLAN Function DefinitionCircuit breaker / Triple circuit breaker / Triple circuit breaker 1_2_3_4_5_6
ETIM 6EC000042 - Miniature circuit breaker (MCB)
ETIM 7EC000042 - Miniature circuit breaker (MCB)
ETIM 8EC000042 - Miniature circuit breaker (MCB)
Object Classification CodeF
UNSPSC39121614
WEEE B2C / B2BBusiness To Consumer
POPULAR DOWNLOADS
EPLAN Graphical Macro9AKK106713A8199
EPLAN Macro9AKK106713A8198
OTHER
Ambient Air TemperatureOperation -25 ... +55 °C
Storage -40 ... +70 °C
Degree Of ProtectionIP20
Enclosure with Cover IP40
Input Voltage TypeAC
Number Of Poles3
Operational VoltageMaximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Minimum 12 V DC
Product Net Width52.5
Rated Conditional Short-Circuit Current (Inc)(230 V) 25 kA
(400 V) 25 kA
Rated Current (In)32 A
Rated Impulse Withstand Voltage (Uimp)4 kilovolt
at 2000 m 5 kilovolt
at Sea Level 6.2 kilovolt
Rated Operational Voltageacc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 400 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(400 V AC) 11.3 kA
Rated Short-Circuit Capacity (Icn)(230 V AC) 12.5 kA
(400 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V AC) 25 kA
(400 V AC) 15 kA
Rated Voltage (Ur)400 V AC
Tripping CharacteristicB
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Width In Number Of Modular Spacings3