1SVR730884R4300 - CM-MPS.43S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x300-500VAC
ABB
SKU
AB_1SVR730884R4300
Model
CM-MPS.43S
SGD $294.06 All prices inclusive of GST
Get 10% OFF, apply code: ABB10OFF
Min. spend $100
Min. spend $100
Short description of CM MPS.43S
Catalog No: 1SVR730884R4300
CM-MPS.43S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x300-500VAC
CM-MPS.43S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x300-500VAC
Country of Origin
Germany (DE)
The CM-MPN.43S is a multifunctional relay from the CM three-phase monitors range. It operates with a rated control supply voltage / three-phase measuring voltage of 300-500 V AC 50/60/400 Hz and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. This relay monitors all phase parameters such as over/undervoltage, phase unbalance and phase failure. The corresponding threshold values are adjustable. The CM-MPN.43S also offers selection of phase sequence monitoring, automatic phase sequence correction as well as an ON or OFF tripping delay. The output contacts can be configured as 1x2 c/o (SPDT) contacts (common signal) or 2x1 c/o (SPDT) contact (separate signal for over- and undervoltage thresholds) operation. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SVR730884R4300 |
Business Area (Master Data) Name | Electrification |
Catalog Description | CM-MPS.43S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x300-500VAC |
Division (Master Data) Name | Smart Power |
EAN | 4016779851879 |
Rated Insulation Voltage (Ui) | Input Circuit / Output Circuit 600 volt Output Circuit 1 / Output Circuit 2 300 volt |
SKU ID | 1SVR730884R4300 |
TECHNICAL | |
Connecting Capacity | Flexible with Ferrule 1x 0.5 ... 2.5 mm² Flexible with Ferrule 2x 0.5 ... 1.5 mm² Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² Flexible 1x 0.5 ... 2.5 mm² Flexible 2x 0.5 ... 1.5 mm² Rigid 1x 0.5 ... 4 mm² Rigid 2x 0.5 ... 2.5 mm² |
Electrical Durability | AC-12 100000 cycle |
Mechanical Durability | 30000000 cycle |
Minimum Switching Capacity | 24 V 10 mA |
Mounting On DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position | Any |
Overvoltage Category | III |
Pollution Degree | 3 |
Rated Frequency (f) | Supply Circuit 50/60/400 Hz |
Rated Operational Current AC-15 (Ie) | (230 V) 3 A |
Rated Operational Current DC-13 (Ie) | (24 V) 2 A |
Recommended Screw Driver | Pozidriv 1 4.5 0.8 x 4 |
Short-Circuit Protective Devices | Output Circuit NC - F Type Fuses 6 A Output Circuit NO - F Type Fuses 10 A |
Standards | CAN/CSA C22.2 No.14 IEC/EN 63000 IEC/EN 60255-27 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 508 |
Terminal Type | Screw Terminals |
Tightening Torque | 0.6 ... 0.8 N·m |
Wire Stripping Length | 8 mm |
TECHNICAL UL/CSA | |
Connecting Capacity UL/CSA | Flexible 1x 18-14 AWG Flexible 2x 18-16 AWG Rigid 1x 20-12 AWG Rigid 2x 20-14 AWG |
Contact Rating UL/CSA | B300 |
Maximum Operating Voltage UL/CSA | Output Circuit 300 V AC |
Tightening Torque UL/CSA | 7.08 in·lb |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
E-Number (Finland) | 2712280 |
E-Number (Sweden) | 3860588 |
EClass | V11.0 : 27371803 |
ETIM 4 | EC001441 - Phase monitoring relay |
ETIM 5 | EC001441 - Phase monitoring relay |
ETIM 6 | EC001441 - Phase monitoring relay |
ETIM 7 | EC001441 - Phase monitoring relay |
Object Classification Code | B |
UNSPSC | 39121536 |
OTHER | |
Ambient Air Temperature | Operation -25 ... +60 °C Storage -40 ... +85 °C |
Degree Of Protection | Housing IP50 Terminals IP20 |
Function | Phase failure detection Phase sequence monitoring Automatic phase sequence correction Over- and undervoltage monitoring Phase unbalance detection |
Measuring Range | (L-L) 300 ... 500 V AC |
Output | 2 x 1 c/o or 1 x 2 c/o contacts, configurable |
Product Net Width | 22.5 |
Rated Control Supply Voltage (Us) | (L-L) 300 ... 500 V AC |
Rated Impulse Withstand Voltage (Uimp) | Input Circuit 6 kilovolt Output Circuit 4 kilovolt |
Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
Time Range | 200 ms start-up delay 0 s or 0.1 ... 30 s tripping delay (ON or OFF) |