1SDA071474R1 - E1.2N 1250 Ekip Touch LI 4p F F
ABB
SKU
AB_1SDA071474R1
Model
E1.2N-1250-Ekip-Touch-LI-4p-F-F
SGD $5,738.09 All prices inclusive of GST
Short description of E1.2N 1250 Ekip Touch LI 4p F F
Catalog No: 1SDA071474R1
E1.2N 1250 Ekip Touch LI 4p F F
E1.2N 1250 Ekip Touch LI 4p F F
Country of Origin
Italy (IT)
C.BREAKER SACE EMAX2 E1.2N 1250 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP/TOUCH-LI R 1250 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SDA071474R1 |
Business Area (Master Data) Name | Electrification |
Catalog Description | E1.2N 1250 Ekip Touch LI 4p F F |
Division (Master Data) Name | Smart Power |
EAN | 8015644753245 |
Rated Insulation Voltage (Ui) | AC 1000 volt |
SKU ID | 1SDA071474R1 |
TECHNICAL | |
Current Type | AC |
Electrical Durability | Ue =< 440 V 8000 cycle Ue = 500 ... 690 V 6500 cycle 30 cycles per hour |
Mechanical Durability | 20000 cycle 60 cycles per hour |
Neutral Pole Current ([%Iu]) | 100 % |
Power Loss | 122 W |
Product Name | Air Circuit Breaker |
Product Type | Air Circuit Breaker |
Rated Service Short-Circuit Breaking Capacity, In % Of Icu (Ics) | 100 % |
Rated Short-time Withstand Current (Icw) | for 1 s 50 kA for 3 s 30 kA |
Rated Uninterrupted Current (Iu) | 1250 A |
Release Type | EL |
Standards | IEC |
Sub-type | E1.2 |
Terminal Connection Type | Front |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
CLASSIFICATIONS | |
ETIM 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q |
OTHER | |
Number Of Poles | 4 |
Product Net Width | 280 |
Rated Current (In) | 1250 A |
Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kilovolt |
Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 66 kA (230 V AC) 66 kA (380 V AC) 66 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 50 kA (660 V AC) 50 kA (690 V AC) 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA (415 V AC) 66 kA (440 V AC) 66 kA (500 V AC) 50 kA (525 V AC) 50 kA (690 V AC) 50 kA |
Rated Voltage (Ur) | 690 V |
Release | Ekip Touch LI |
Short-Circuit Performance Level | N |
Version | F |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Write Your Own Review