1SBL367001R1111 - AF52-30-11-11 24-60V50/60HZ 20-60VDC Contactor
ABB
SKU
AB_1SBL367001R1111
Model
AF52-30-11-11
SGD $175.69 All prices inclusive of GST
Get 10% OFF, apply code: ABB10OFF
Min. spend $100
Min. spend $100
Short description of AF52 30 11 11
Catalog No: 1SBL367001R1111
AF52-30-11-11 24-60V50/60HZ 20-60VDC Contactor
AF52-30-11-11 24-60V50/60HZ 20-60VDC Contactor
Country of Origin
France (FR)
The AF52-30-11-11 is a 3 pole - 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) or 40 hp / 480 V UL and switching power circuits up to 100 A (AC-1) or 80 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SBL367001R1111 |
Business Area (Master Data) Name | Electrification |
Catalog Description | AF52-30-11-11 24-60V50/60HZ 20-60VDC Contactor |
Division (Master Data) Name | Smart Power |
EAN | 3471523132412 |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 volt acc. to UL/CSA 600 volt |
SKU ID | 1SBL367001R1111 |
TECHNICAL | |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Rigid 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid 1/2x 1 ... 2.5 mm² |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 4 ... 35 mm² Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² Rigid 1/2x 6 ... 3 5 mm² |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A acc. to IEC 60947-5-1, q = 40 °C 16 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-15) 1200 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 1200 cycles per hour (DC-13) 900 cycles per hour |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Operate Time | Between Coil De-energization and NC Contact Closing 19 ... 105 ms Between Coil De-energization and NO Contact Opening 17 ... 100 ms Between Coil Energization and NC Contact Opening 38 ... 95 ms Between Coil Energization and NO Contact Closing 42 ... 100 ms |
Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (400 / 440 V) 3 A |
Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 1 A / 72 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.27 A / 60 W (250 V) 0.27 A / 68 W (400 V) 0.15 A / 60 W (500 V) 0.13 A / 65 W (600 V) 0.1 A / 60 W |
Rated Short-time Withstand Current (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A for 0.1 s 140 A for 1 s 100 A |
Terminal Type | Screw Terminals |
Wire Stripping Length | Main Circuit 16 mm |
TECHNICAL UL/CSA | |
General Use Rating UL/CSA | (600 V AC) 80 A |
Horsepower Rating UL/CSA | (120 V AC) Single Phase 3 hp (200 ... 208 V AC) Three Phase 15 hp (220 ... 240 V AC) Three Phase 20 hp (240 V AC) Single Phase 10 hp (440 ... 480 V AC) Three Phase 40 hp (550 ... 600 V AC) Three Phase 50 hp |
Tightening Torque UL/CSA | Auxiliary Circuit 11 IA Control Circuit 11 IA Main Circuit 35 IA |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
Maximum Operating Altitude Permissible | 3000 m |
Resistance To Shock Acc. To IEC 60068-2-27 | Closed, Shock Direction: A 25 K40 Closed, Shock Direction: B1 25 K40 Closed, Shock Direction: B2 15 K40 Closed, Shock Direction: C1 25 K40 Closed, Shock Direction: C2 25 K40 Open, Shock Direction: B1 5 K40 |
Resistance To Vibrations Acc. To IEC 60068-2-6 | 5 ... 300 Hz 3 g closed position / 3 g open position |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
E-Number (Finland) | 3707019 |
EClass | V11.0 : 27371003 |
ETIM 4 | EC000066 - Magnet contactor, AC-switching |
ETIM 5 | EC000066 - Magnet contactor, AC-switching |
ETIM 6 | EC000066 - Power contactor, AC switching |
ETIM 7 | EC000066 - Power contactor, AC switching |
Object Classification Code | Q |
UNSPSC | 39121529 |
OTHER | |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C Close to Contactor without Thermal O/L Relay -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C |
Degree Of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
Number Of Auxiliary Contacts NC | 1 |
Number Of Auxiliary Contacts NO | 1 |
Number Of Main Contacts NO | 3 |
Product Net Width | 67 |
Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V 50 Hz / 60 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation 20 ... 60 V |
Rated Impulse Withstand Voltage (Uimp) | 6 kilovolt |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 100 No unit (690 V) 60 °C 80 ampere (690 V) 70 °C 70 No unit |
Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 53 A (440 V) 60 °C 53 A (500 V) 60 °C 45 A (690 V) 60 °C 35 A (380 / 400 V) 60 °C 53 A (220 / 230 / 240 V) 60 °C 53 A |
Rated Operational Power AC-3 (Pe) | (400 V) 22 kW (415 V) 30 kW (440 V) 30 kW (500 V) 30 kW (690 V) 30 kW (380 / 400 V) 22 kW (220 / 230 / 240 V) 15 kW |
Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V |