METSEPM5350 PM5350 Power Monitor Schneider Electric
Short description of METSEPM5350
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. Include a non-volatile memory for several parameters and alarms. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 85 to 265 VAC and 100 to 300 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20V AC to 480V AC, CAT III or 20V AC to 690V AC, CAT II at 45 Hz to 70 Hz. The range of measurement voltage between Phase and Neutral is 20V AC to 277V AC, CAT III or 20V AC to 400V AC, CAT II at 45 Hz to 70 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has four digital inputs and dual relay outputs. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.24 inches (57 millimetres), height 3.78 inches (96 millimetres) and product weight 8.8 onces (250 g).
Label :  PM5350 Monitoring system
-  range :  PowerLogic
-  product name :  PowerLogic PM5350
-  device short name :  PM5350
-  product or component type :  power meter
-  market segment :  , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,
-  Range Presentation- 
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 100...300 V DC 85...265 V AC 45...65 Hz |
Contacts Type And Composition | 1 A 5 A |
Control Type | 1P + N 3P 3P + N |
Display Type | backlit LCD |
Measurement Accuracy | current 0.3 % frequency 0.05 % power factor +/- 0.005 voltage 0.3 % |
Mounting Diameter | 4 digital |
Product Or Component Type | power meter |
Communication Port Protocol | JBUS Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds |
Device Short Name | PM5350 |
EAN13 | 3606480284311 |
Power Quality Analysis | total demand distortion total harmonic distortion |
Range | PowerLogic |
Range Name | PM5350 Monitoring system |
Type Of Measurement | active power apparent power current energy frequency phase angle power factor reactive power voltage |
COMPLEMENTARY | |
Analogue Input Type | current 0.05...9 A (impedance <= 0.3 Ohm) |
Analogue Output Number | backlit LCD |
Communication Gateway | 6 lines |
Display Resolution | 6 lines |
Number Of Inputs | 4 digital |
Output Voltage | current 0.05...9 A (impedance <= 0.3 Ohm) |
Product Name | PowerLogic PM5350 |
Time Delay | current 0.3 % frequency 0.05 % power factor +/- 0.005 voltage 0.3 % |
[In] Rated Current | 1 A 5 A |
Accuracy Class | class 0.5 active energy conforming to IEC 61557-12 class 0.5 power conforming to IEC 61557-12 class 0.5S active energy conforming to IEC 62053-22 class 2 reactive energy conforming to IEC 61557-12 class 3 reactive energy conforming to IEC 62053-23 |
Communication Port Support | terminal block: RS485 |
Compatibility Code | PM5350 |
Connections - Terminals | control circuit: screw terminal block2 current transformer: screw terminal block6 Ethernet network: RJ45 connector input/output circuit: screw terminal block6 relay output: screw terminal block4 voltage circuit: screw terminal block4 |
Data Recording | alarms min/max of instantaneous values |
Depth | 44 mm |
Device Application | power monitoring |
Frequency Measurement Range | 45-70 Hz |
Height | 96 mm |
Information Displayed | tariff (4) |
Market Segment | buildings large building cost management: billing: main incomer buildings large building cost management: billing: sub feeder buildings large building cost management: cost allocation: main incomer buildings large building cost management: cost allocation: sub feeder buildings large building network management: sub feeder buildings medium building cost management: billing: main incomer buildings medium building cost management: billing: sub feeder buildings medium building cost management: cost allocation: main incomer buildings medium building cost management: cost allocation: sub feeder buildings medium building network management: main incomer buildings medium building network management: sub feeder buildings multi-site cost management: billing: main incomer buildings multi-site cost management: billing: sub feeder buildings multi-site cost management: cost allocation: main incomer buildings multi-site cost management: cost allocation: sub feeder buildings multi-site network management: sub feeder buildings small building cost management: billing: main incomer buildings small building cost management: billing: sub feeder buildings small building cost management: cost allocation: main incomer buildings small building cost management: cost allocation: sub feeder buildings small building network management: main incomer buildings small building network management: sub feeder data center cost management: billing: main incomer data center cost management: billing: sub feeder data center cost management: cost allocation: main incomer data center cost management: cost allocation: sub feeder data center network management: sub feeder healthcare cost management: billing: main incomer healthcare cost management: billing: sub feeder healthcare cost management: cost allocation: main incomer healthcare cost management: cost allocation: sub feeder healthcare network management: sub feeder industry cost management: billing: main incomer industry cost management: billing: sub feeder industry cost management: cost allocation: main incomer industry cost management: cost allocation: sub feeder industry network management: sub feeder |
Maximum Power Consumption In VA | 9.6 VA |
Measurement Current | 0-1 A 0-5 A |
Measurement Voltage | 20-400 V AC phase to neutral 20-690 V AC phase to phase |
Mounting Mode | flush-mounted |
Net Weight | 0.25 kg |
Network Frequency | 50 Hz 60 Hz |
Number Of Outputs | 2 relay |
Ride-through Time | 100 ms 230 V AC typical 100 ms 415 V AC typical 80 ms 120 V AC typical |
Sampling Rate | 32 samples/cycle |
Type Of Installation | indoor installation |
Width | 96 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -40-85 °C |
Ambient Air Temperature For Storage | -25-70 °C |
Electromagnetic Compatibility | 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 conducted and radiated emissions class A conforming to EN 55011 conducted RF disturbances conforming to IEC 61000-4-6 electrical fast transient/burst immunity test conforming to IEC 61000-4-4 electrostatic discharge conforming to IEC 61000-4-2 immunity to impulse waves conforming to IEC 61000-4-12 limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 limits for harmonic current emissions conforming to IEC 61000-3-2 susceptibility to electromagnetic fields conforming to IEC 61000-4-3 |
IP Degree Of Protection | IP30 back: conforming to IEC 60529 IP51 front face: conforming to IEC 60529 |
Operating Altitude | 0...3000 m |
Overvoltage Category | III |
Pollution Degree | 2 |
Product Certifications | CE cULus |
Relative Humidity | 0-95 % at 50-50 °C |
Standards | IEC 61010-1 |
OTHER | |
Poles Description | 1P + N 3P 3P + N |
[Us] Rated Supply Voltage | 100...300 V DC 85...265 V AC 45...65 Hz |