METSEPM3255 - PM3255 Power Meter - 2 Digital I - 2 Digital O - RS485
Short description of METSEPM3255
PM3255 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power, Total Harmonic Distortion and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. Support for two digital input and two digital outputs. The meter offers 512kB of memory for event recording with up to 15 alarms with power and energy consumption logs. Product dimensions are as follows: width 3.54 in (90 mm), depth 2.76in (70 mm), height 3.74 in (95 mm) and product weight 9.17 oz (260 g).
-  2 digital I
-  2 digital O
-  RS485.
Label :  PowerLogic PM3000 series
-  range :  PowerLogic
-  product name :  PowerLogic PM3000
-  device short name :  PM3255
-  product or component type :  power meter
-  market segment :  N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A, N/A
-  Range Presentation :  The PowerLogic PM3000 series power meters are a cost-attractive, feature
- rich range of DIN rail
- mounted power meters that offers all the measurement capabilities required to monitor an electrical installation. Ideal for power metering and network monitoring applications that seek to improve the availability and reliability of your electrical distribution system, the meters are also fully capable of supporting sub billing and cost allocation applications.
-  Range Benefits :  Improve network reliability by detecting potential problems before they occur
-  Minimize downtime by quickly discovering and understanding the cause of the crisis Optimize your energy consumption & enable energy efficiency practices
-  Collect and analyze energy consumption data from each area for each type of load or circuit
-  Gain an accurate understanding of business expenses by allocating the energy
- related costs
-  Identify savings opportunities
-  Use information to implement actions designed to reduce energy consumption Monitor the energy consumption of your tenants or customers and establish accurate invoices
-  Develop awareness and help drive energy
- efficient behavior
-  Range Application Presentation :  Cost management applications
-  Bill checking to verify that you are only charged for the energy you use
-  Sub billing individual tenants for their energy consumption, including WAGES
-  Aggregation of energy consumption, including WAGES, and allocating costs per area, per usage, per shift, or per time within the same facility
-  Energy cost and usage analysis per zone, per usage, or per time period to optimize energy usage Network management applications
-  Metering of electrical parameters to better understand the behavior of your electrical distribution system
-  Network monitoring to assess power quality issues and optimize your load profile
This product is under Green Premium products which is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 100...277 V AC 45...65 Hz 100...300 V DC 173...480 V AC 45...65 Hz |
Contacts Type And Composition | 1 A 5 A |
Control Type | 1P + N 3P 3P + N |
Display Type | backlit LCD |
Measurement Accuracy | current 0.3 % 0.5...6 A current 0.5 % 0.1...1.2 A voltage 0.3 % 50...330 V voltage 0.3 % 80...570 V |
Mounting Diameter | 2 digital 0...4 mA 11...40 V DC |
Product Or Component Type | power meter |
Web Server | 512 kB |
Communication Port Protocol | Modbus at 9.6...38.4 kbauds |
Device Short Name | PM3255 |
EAN13 | 3606480481611 |
Mounting Support | DIN rail |
Power Quality Analysis | up to the 15th harmonic |
Range | PowerLogic |
Range Name | PM3000 series |
Type Of Measurement | active and reactive power apparent power current energy frequency power factor total current harmonic distortion THD (I) total voltage harmonic distortion THD (U) voltage |
COMPLEMENTARY | |
Analogue Input Type | current 0...1 A current 0...5 A |
Analogue Output Number | backlit LCD |
Communication Gateway | 128 x 96 pixels |
Display Resolution | 128 x 96 pixels |
Memory Capacity | 512 kB |
Number Of Inputs | 2 digital 0...4 mA 11...40 V DC |
Output Voltage | current 0...1 A current 0...5 A |
Product Name | PowerLogic PM3000 |
Time Delay | current 0.3 % 0.5...6 A current 0.5 % 0.1...1.2 A voltage 0.3 % 50...330 V voltage 0.3 % 80...570 V |
[In] Rated Current | 1 A 5 A |
Accuracy Class | class 0.5S active energy conforming to IEC 62053-22 class 1 active energy conforming to IEC 62053-21 class 2 reactive energy conforming to IEC 62053-23 class C active energy conforming to EN 50470-3 |
Communication Port Support | RS485 |
Compatibility Code | PM3255 |
Data Recording | 15 alarms energy consumption logs min/max of instantaneous values power logs time stamping |
Depth | 70 mm |
Device Application | multi-tariff power monitoring sub billing |
Frequency Measurement Range | 45-65 Hz |
Height | 95 mm |
Information Displayed | tariff (4) |
Market Segment | residential small commercial buildings large building cost management: billing: sub feeder buildings large building cost management: cost allocation: sub feeder buildings medium building cost management: billing: sub feeder buildings medium building cost management: cost allocation: sub feeder buildings multi-site cost management: billing: sub feeder buildings multi-site cost management: cost allocation: sub feeder buildings small building cost management: billing: sub feeder buildings small building cost management: cost allocation: sub feeder data center cost management: billing: sub feeder data center cost management: cost allocation: sub feeder healthcare cost management: billing: sub feeder healthcare cost management: cost allocation: sub feeder industry cost management: billing: sub feeder industry cost management: cost allocation: sub feeder |
Measurement Current | 0.02-1.2 A 0.05-6 A |
Measurement Voltage | 50-330 V AC 45...65 Hz direct 50-330 V AC 45...65 Hz phase to neutral 570-999000 V AC 45...65 Hz with external VT 80-570 V AC 45...65 Hz direct 80-570 V AC 45...65 Hz phase to phase |
Mounting Mode | clip-on |
Net Weight | 0.26 kg |
Network Frequency | 50 Hz 60 Hz |
Number Of Outputs | 2 digital (static) |
Power Consumption In VA | 5 VA |
Sampling Rate | 32 samples/cycle |
Width | 90 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-55 °C |
Ambient Air Temperature For Storage | -40-85 °C |
Electromagnetic Compatibility | 1.2/50 µs shock waves immunity test level 4 conforming to IEC 61000-4-5 conducted and radiated emissions class B conforming to EN 55022 conducted RF disturbances level 3 conforming to IEC 61000-4-6 electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 electrostatic discharge level 4 conforming to IEC 61000-4-2 magnetic field at power frequency - test level: 0.5 mT conforming to IEC 61000-4-8 susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3 |
IP Degree Of Protection | IP20 body: conforming to IEC 60529 IP40 front panel: conforming to IEC 60529 |
Operating Altitude | 0...3000 m |
Overvoltage Category | III |
Pollution Degree | 2 |
Product Certifications | CE conforming to EN 61010-1 cULus conforming to UL 61010-1 UL |
Relative Humidity | 5-95 % at 50-50 °C |
Standards | EN 50470-1 EN 50470-3 EN 61010-1 EN 61557-12 IEC 61557-12 IEC 62052-11 UL 61010-1 |
OTHER | |
Poles Description | 1P + N 3P 3P + N |
[Us] Rated Supply Voltage | 100...277 V AC 45...65 Hz 100...300 V DC 173...480 V AC 45...65 Hz |