Loading...
*All information are subjected to changes without prior notice.

LV438694 - Circuit Breaker ComPact NSX250N AC, 25 KA At 240 VAC, TMD Trip Unit 200 A, 1 Pole 1d.

Schneider
SKU
SE_LV438694
Model
LV438694

Obsolete

All prices inclusive of GST

Short description of LV438694

LV438694. Circuit-breakers, to protect lines carrying up to 630A
Obsolete
range : ComPact
-  product name : ComPact NSX
-  range of product : ComPact NSX100...250
-  device short name : NSX250N
-  product or component type : Circuit breaker
-  device application : Distribution
-  Number of poles : 1P
-  protected poles description : 1t
-  [In] rated current : 200 A at 40 °C
-  [Ue] rated operational voltage : 277 V AC 50/60 Hz
-  network type : AC
-  network frequency : 50/60 Hz
-  suitability for isolation : Yes conforming to EN/IEC 60947-2
-  utilisation category : Category A
-  [Icu] rated ultimate short-circuit breaking capacity : 25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
-  Performance level : N 25 kA 240 V AC
-  trip unit name : TM
- D
-  trip unit technology : Thermal
- magnetic
-  control type : Toggle
-  Circuit breaker mounting mode : Fixed
MAIN SPECIFICATIONS
Breaking Capacity25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity CodeN 25 kA 240 V AC
Contacts Type And Composition200 A at 40 °C
Control Typetoggle
Product Or Component Typecircuit breaker
Range Of ProductComPact NSX100...250
Trip Unit NameTM-D
[Ie] Rated Operational Currenttoggle
[Ue] Rated Operational Voltage277 V AC 50/60 Hz
Device Short NameNSX250N
Mounting Supportbackplate
Network TypeAC
Protected Poles Description1t
Rangecompact
Range NameComPact NSX
Suitability For Isolationyes conforming to EN/IEC 60947-2
Trip Unit Technologythermal-magnetic
Utilisation Categorycategory A
COMPLEMENTARY
Communication Network Type277 V AC 50/60 Hz
Current Transformer TypeN 25 kA 240 V AC
Interlocked Device25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Product NameComPact NSX
[Ics] Rated Service Breaking Capacity25 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[In] Rated Current200 A at 40 °C
Compatibility CodeNSX250
Connection Pitch35 mm
Depth86 mm
Device Applicationdistribution
Downside Connectionfront
Earth-leakage Protectionwithout
Electrical Durability10000 cycles at 440 V In/2
5000 cycles at 440 V In
Height161 mm
Long Time Pick-up Adjustment Range1 In
Long Time Pick-up Adjustment Type Irfixed
Magnetic Tripping Current850-850 A
Mechanical Durability10000 cycles
Mounting Modefixed
Network Frequency50/60 Hz
Protection Type for overload protection (thermal)
for short-circuit protection (magnetic)
Trip Unit Rating200-200 A at 40 °C
Upside Connectionfront
Width35 mm
[Uimp] Rated Impulse Withstand Voltage8 kV conforming to IEC 60947-2
[Ui] Rated Insulation Voltage750 V AC 50/60 Hz conforming to IEC 60947-2
ENVIRONMENT
Ambient Air Temperature For Operation-25-70 °C
Ambient Air Temperature For Storage-50-85 °C
Electrical Shock Protection Classclass II
IK Degree Of ProtectionIK07 conforming to IEC 62262
IP Degree Of ProtectionIP40 conforming to IEC 60529
Operating Altitude0...2000 m without derating
2000 m...5000 m with derating
Overvoltage Categoryclass II
Pollution Degree3 conforming to IEC 60664-1
Product CertificationsCCC
EAC
Marine
Relative Humidity0-95 %
StandardsEN/IEC 60947
OTHER
Earth Leakage CurrentTM-D
Poles Description1P
[Us] Rated Supply VoltageComPact NSX100...250