Loading...
*All information are subjected to changes without prior notice.

C25N3TM200 - Circuit Breaker ComPacT NSX250N, 50kA At 415VAC, TMD Trip Unit 200A, 3 Poles 3d

Schneider
SKU
SE_C25N3TM200
Model
C25N3TM200
SGD $743.47 All prices inclusive of GST

Short description of C25N3TM200

C25N3TM200. NSX250N 50kA AC 3P3D 200A TMD
Country of Origin
India
-
+

UOM: Piece

In stock
In Stock 2
Backorder Leadtime: 4 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

This ComPacT NSX250N is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity.
It is an optimal choice for all standard and specific applications.
The breaking capacity (Icu) is 50kA rms at 415VAC 50/60Hz.
The operational voltage is 690VAC 50/60Hz.
This product embeds a 200A rating thermal-magnetic trip unit (TMD).
TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection.
This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories.
It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.
ComPacT NSX250N is part of Schneider Electric EcoStruxure Power architecture.
MAIN
RangeComPacT
Product NameComPacT NSX
Device Short NameNSX250N
Product Or Component TypeCircuit breaker
Device ApplicationDistribution
Poles Description3P
Protected Poles Description3D
[In] Rated Current200 A at 40 °C
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Network TypeAC
Network Frequency50/60 Hz
Suitability For IsolationYes conforming to EN/IEC 60947-2
Utilisation CategoryCategory A
[Icu] Rated Ultimate Short-circuit Breaking Capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1
50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1
15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Performance LevelN 50 kA 415 V AC
Trip Unit NameTM-D
Trip Unit TechnologyThermal-magnetic
Trip Unit Protection FunctionsLI
Control TypeToggle
Circuit Breaker Mounting ModeFixed
COMPLEMENTARY
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ics] Rated Service Short-circuit Breaking Capacity90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability20000 cycles
Electrical Durability20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V In
Power Dissipation Per Pole15.4 W
Mounting SupportBackplate
Mounting PositionHorizontal and vertical
Flat on the back
Upside ConnectionFront
Downside ConnectionFront
Connection Pitch35 mm
Protection TypeL : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip Unit Rating200 A at 40 °C
Long-time Pick-up Adjustment Type Ir (thermal Protection)Adjustable
[Ir] Long-time Protection Pick-up Adjustment Range0.7...1 x In
Long-time Protection Delay Adjustment Type TrFixed
[tr] Long-time Protection Delay Adjustment Range120…400 s at 1.5 x In
15 s at 6 x Ir
Instantaneous Protection Pick-up Adjustment Type IiAdjustable
[Ii] Instantaneous Protection Pick-up Adjustment Range5...10 x In
Earth-leakage ProtectionWithout
Number Of Slots For Electrical Auxiliaries5 slot(s)
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
Net Weight2.4 kg
ENVIRONMENT
StandardsEN/IEC 60947-2
Overvoltage CategoryClass II
Electrical Shock Protection ClassClass II
Pollution Degree3 conforming to IEC 60664-1
IP Degree Of ProtectionIP40 conforming to IEC 60529
IK Degree Of ProtectionIK07 conforming to IEC 62262
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-50…85 °C
Relative Humidity0…95 %
Operating Altitude0...2000 m without derating
2000 m...5000 m with derating
PACKING UNITS
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height14.000 cm
Package 1 Width11.500 cm
Package 1 Length19.000 cm
Package 1 Weight2.006 kg
Unit Type Of Package 2S03
Number Of Units In Package 24
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight8.402 kg
Write Your Own Review
You're reviewing:C25N3TM200 - Circuit Breaker ComPacT NSX250N, 50kA At 415VAC, TMD Trip Unit 200A, 3 Poles 3d
Your Rating