Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

MCB,2P,10A,CURVE K,10KA

ABB
SKU
AB_2CDS272337R0427
Model
2CDS272337R0427
SGD $102.94

Short description of 2CDS272337R0427

SU202M-K10 Miniature Circuit Breaker - 2P - K - 10 A
Country of Origin
Bulgaria
-
+

UOM: Piece

In stock
In Stock 10
Backorder Leadtime: 5 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
SU202M-K10 Miniature Circuit Breaker K-Char., 10kA, 10A, 2P UL489
TECHNICAL
Accessories AvailableYes
Actuator MarkingI / O
Actuator MaterialInsulation Group II, Black, Sealable
Connecting CapacityBusbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Contact Position IndicationRed ON / Green OFF
Dielectric Test Voltage50/60 Hz, 1 min: 2 kV
Electrical Endurance20000 AC cycle
Energy Limiting Class3
Housing MaterialInsulation Group I, RAL 7035
Installation Sizeacc. to DIN 43880 3
Mechanical Endurance (Nendu)20000 cycle
Mounting On DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting PositionAny
Number Of Protected Poles2
Overvoltage CategoryIII
Power Loss4.2 W
at Rated Operating Conditions per Pole 2.1 W
Power Supply ConnectionArbitrary
Rated Frequency (f)50 / 60 Hz
DC
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 440 V
Recommended Screw DriverPozidriv 2
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
StandardsCSA 22.2 No. 5
IEC/EN 60947-2
UL 489
Terminal TypeDouble Clamp
Tightening Torque2.8 N·m
TECHNICAL UL/CSA
Connecting Capacity UL/CSABusbar 18-8 AWG
Conductor 18-4 AWG
Interrupting Rating Acc. To UL489(240 V AC) 10 kA
(480Y / 277 V AC) 10 kA
(96 V DC) 10 kA
Maximum Operating Voltage UL/CSA480Y / 277 V AC
96 V DC
DIMENSIONS
Built-In Depth (t2)69 mm
Pole Net Weight0.125 kg
Product Net Depth / Length69 mm
Product Net Height111 mm
Product Net Weight0.25 kg
ORDERING
E-Number (Sweden)2100099
Minimum Order Quantity1 piece
ENVIRONMENTAL
Environmental Conditions28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Environmental Information9AKK107680A9140
Pollution Degree3
Reference Ambient Air Temperature30 °C
Resistance To Shock Acc. To IEC 60068-2-2725g / 2 shocks / 13 ms
Resistance To Vibrations Acc. To IEC 60068-2-65g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
CN88536 20 10
EClassV11.0 : 27141901
EPLAN Catalog TreeElectrical engineering / Protection devices / General
EPLAN Function DefinitionCircuit breaker / Double circuit-breaker / Double circuit breaker 1_2_3_4
ETIM 7EC000042 - Miniature circuit breaker (MCB)
ETIM 8EC000042 - Miniature circuit breaker (MCB)
UNSPSC39121614
WEEE B2C / B2BBusiness To Consumer
CERTIFICATES AND DECLARATIONS
Certification AgencyCSA
EN
IEC
UL
Declaration Of Conformity - CE2CDK400595D2705
Instructions And Manuals2CDC002177D0202
RoHS Information2CDK400595D2705
OTHER
Ambient Air TemperatureOperation -25 ... +55 °C
Storage -40 ... +70 °C
Degree Of ProtectionIP20
Enclosure with Cover IP40
Input Voltage TypeAC/DC
Number Of Poles2
Product Net Width35 mm
Rated Conditional Short-Circuit Current (Inc)(400 V) 15 kA
Rated Current (In)10 A
Rated Impulse Withstand Voltage (Uimp)4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Rated Operational Voltageacc. to IEC 60898-1 440 V AC
acc. to IEC 60947-2 400 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(400 V AC) 11.2 kA
Rated Short-Circuit Capacity (Icn)(400 V AC) 11.2 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 15 kA
Tripping CharacteristicK
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Width In Number Of Modular Spacings2
EAN4016779932714
Write Your Own Review
You're reviewing:MCB,2P,10A,CURVE K,10KA
Your Rating