Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

CM-ESS.MS Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC

ABB
SKU
AB_1SVR730830R0500
Model
CM-ESS.MS
SGD $245.61

Short description of CM ESS.MS

CM-ESS.MS Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC
Country of Origin
Germany (DE)
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 5 To 7 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
The CM-ESS.MS is a multifunctional voltage monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 24 - 240 V AC / DC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC voltages with 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V. The CM-ESS.MS offers selection of over- or undervoltage monitoring, open- or closed-circuit operating principle, with or without latching function. The hysteresis is adjustable within a range of 3 to 30 % of the threshold value. The tripping delay and the start-up delay are adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
MAIN SPECIFICATION
ABB Global IDABB1SVR730830R0500
Business Area (Master Data) NameElectrification
Catalog DescriptionCM-ESS.MS Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC
Division (Master Data) NameSmart Power
EAN4016779852173
Rated Insulation Voltage (Ui)Measuring Circuit / Output Circuit 600 volt
Output Circuit 1 / Output Circuit 2 250 volt
Supply Circuit / Measuring Circuit 600 volt
Supply Circuit / Output Circuit 250 volt
SKU ID1SVR730830R0500
TECHNICAL
Connecting CapacityFlexible with Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Electrical DurabilityAC-12 100000 cycle
Mechanical Durability30000000 cycle
Minimum Switching Capacity24 V
10 mA
Mounting On DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting PositionAny
Overvoltage CategoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Recommended Screw DriverPozidriv 1
4.5
0.8 x 4
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 10 A
Output Circuit NO - F Type Fuses 10 A
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Terminal TypeScrew Terminals
Tightening Torque0.6 ... 0.8 N·m
Wire Stripping Length8 mm
TECHNICAL UL/CSA
Connecting Capacity UL/CSAFlexible 1x 18-14 AWG
Flexible 2x 18-16 AWG
Rigid 1x 20-12 AWG
Rigid 2x 20-14 AWG
Contact Rating UL/CSAB300
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Tightening Torque UL/CSA7.08 in·lb
ORDERING
Minimum Order Quantity1 piece
ENVIRONMENTAL
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
E-Number (Finland)2712254
E-Number (Sweden)3860620
EClassV11.0 : 27371801
ETIM 4EC001438 - Voltage monitoring relay
ETIM 5EC001438 - Voltage monitoring relay
ETIM 6EC001438 - Voltage monitoring relay
ETIM 7EC001438 - Voltage monitoring relay
Object Classification CodeB
UNSPSC39121514
OTHER
Ambient Air TemperatureOperation -20 ... +60 °C
Storage -40 ... +85 °C
Degree Of ProtectionHousing IP50
Terminals IP20
FunctionOver- or undervoltage monitoring
Measuring Range3 ... 30 V
6 ... 60 V
30 ... 300 V
60 ... 600 V
Output2 c/o (SPDT) contact
operating principle selectable
Product Net Width22.5
Rated Control Supply Voltage (Us)24 ... 240 V AC/DC
Rated Impulse Withstand Voltage (Uimp)Measuring Circuit / Output Circuit 6 kilovolt
Output Circuit 1 / Output Circuit 2 4 kilovolt
Supply Circuit / Measuring Circuit 6 kilovolt
Supply Circuit / Output Circuit 4 kilovolt
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Time Range0 s or 0.1 ... 30 s tripping delay (ON)
Write Your Own Review
You're reviewing:CM-ESS.MS Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC