1SCA104863R1001 - OT25F3C CHANGE-OVER SWITCH
ABB
SKU
AB_1SCA104863R1001
Model
OT25F3C
SGD $101.15 All prices inclusive of GST
Short description of OT25F3C
Catalog No: 1SCA104863R1001
OT25F3C CHANGE-OVER SWITCH
OT25F3C CHANGE-OVER SWITCH
Country of Origin
Finland (FI)
OT25F3C CHANGE-OVER SWITCH, Handle and shaft need to be ordered separately, Open transition
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SCA104863R1001 |
Business Area (Master Data) Name | Electrification |
Catalog Description | OT25F3C CHANGE-OVER SWITCH |
Division (Master Data) Name | Smart Power |
EAN | 6417019390062 |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 volt |
SKU ID | 1SCA104863R1001 |
TECHNICAL | |
Cable Cross-Section | 0.75 ... 10 mm² |
Conventional Free-air Thermal Current (Ith) | q = 40 °C 32 A |
Conventional Thermal Current (Ithe) | Fully Enclosed 32 A |
Distance Between Phases | Standard |
Handle Color | Black |
Handle Type | Handle and shaft not included |
Operating Mode | Front operated |
Pollution Degree | 3 |
Position Of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
Power Loss | 0.6 W |
Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 25 A (500 V) 25 A (690 V) 25 A |
Rated Short-time Withstand Current (Icw) | for 1 s 0.5 kiloampere rms |
Switches Operating Mechanism | Mechanism on Top of the Switch |
Transition Type | Open |
TECHNICAL UL/CSA | |
Ampere Rating UL/CSA | 25 A |
Horsepower Rating UL/CSA | (acc. to UL 200 V) 7.5 Hp (acc. to UL 480 V) 15 Hp (acc. to UL 240 V) 7.5 Hp (acc. to UL 208 V) 7.5 Hp (acc. to UL 600 V) 20 Hp |
ORDERING | |
Minimum Order Quantity | 1 piece |
CLASSIFICATIONS | |
E-Number (Finland) | 3601430 |
E-Number (Sweden) | 3171261 |
ETIM 5 | EC000216 - Switch disconnector |
ETIM 6 | EC000216 - Switch disconnector |
ETIM 7 | EC000216 - Switch disconnector |
ETIM 8 | EC000216 - Switch disconnector |
Object Classification Code | Q |
UNSPSC | 39122233 |
OTHER | |
Degree Of Protection | Front IP20 |
Mounting Type | Base mounting |
Number Of Poles | 3 |
Product Net Width | 70 |
Rated Impulse Withstand Voltage (Uimp) | 8 kilovolt |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 25 A (500 V) 25 A (690 V) 25 A |
Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 20 A (500 V) 20 A (690 V) 11 A |
Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 9 kW (500 V) 9 kW (690 V) 9 kW |
Rated Operational Voltage | 750 V |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |