AX25-30-01-80 220-230V50Hz/230-240V60Hz Contactor

ABB
SKU
AB_1SBL931074R8001
Model
AX25-30-01-80
SGD $38.76

Short description of AX25 30 01 80

AX25-30-01-80 220-230V50Hz/230-240V60Hz Contactor
Country of Origin
Bulgaria (BG)
-
+

UOM: Piece

In stock
In Stock 49
Backorder Leadtime: 2 To 4 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
AX09...AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
MAIN SPECIFICATION
ABB Global IDABB1SBL931074R8001
Business Area (Master Data) NameElectrification
Catalog DescriptionAX25-30-01-80 220-230V50Hz/230-240V60Hz Contactor
Division (Master Data) NameSmart Power
EAN3471522398802
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 volt
SKU ID1SBL931074R8001
TECHNICAL
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 32 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Operate TimeBetween Coil De-energization and NC Contact Closing 9 ... 16 ms
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NC Contact Opening 7 ... 21 ms
Between Coil Energization and NO Contact Closing 10 ... 26 ms
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Rated Operational Current AC-15 (Ie)(220 / 240 V) 4 A
(24 / 127 V) 6 A
(400 / 440 V) 2 A
(500 V) 2 A
(690 V) 2 A
(380 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)(110 V) 1.1 A / 121 W
(220 V) 0.55 A / 121 W
(400 V) 2.8 A / 134 W
(500 V) 2 A / 144 W
(125 V) 1.1 A / 138 W
(24 V) 6 A / 144 W
(250 V) 0.55 A / 138 W
Rated Short-time Withstand Current (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 32 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 85 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 105 A
for 0.1 s 140 A
for 1 s 100 A
Terminal TypeScrew Terminals
TECHNICAL UL/CSA
General Use Rating UL/CSA(600 V AC) 30 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 2 Hp
(240 V AC) Single Phase 3 Hp
(200 ... 208 V AC) Three Phase 7.5 Hp
(220 ... 240 V AC) Three Phase 7.5 Hp
(440 ... 480 V AC) Three Phase 15 Hp
(550 ... 600 V AC) Three Phase 15 Hp
Tightening Torque UL/CSAAuxiliary Circuit 9 in·lb
Control Circuit 9 in·lb
Main Circuit 11 in·lb
ORDERING
Minimum Order Quantity1 piece
ENVIRONMENTAL
Climatic Withstandacc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible3000 m
RoHS StatusFollowing EU Directive 2002/95/EC August 18, 2005 and amendment
CLASSIFICATIONS
E-Number (Finland)3707329
ETIM 6EC000066 - Power contactor, AC switching
ETIM 7EC000066 - Power contactor, AC switching
IDEA Granular Category Code (IGCC)4755 >> Contactors
Object Classification CodeQ
UNSPSC39121529
OTHER
Ambient Air TemperatureClose to Contactor for Storage -60 ... +80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Near Contactor for Operation in Free Air -40 ... +70 °C
Degree Of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Number Of Auxiliary Contacts NC1
Number Of Main Contacts NO3
Product Net Width44
Rated Control Circuit Voltage (Uc)50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Rated Impulse Withstand Voltage (Uimp)6 kilovolt
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 32 ampere
(690 V) 70 °C 23 ampere
(220 / 240 V) 55 °C 27 ampere
Rated Operational Current AC-3 (Ie)(220 / 230 / 240 V) 55 °C 25 A
(380 / 400 V) 55 °C 25 A
(415 V) 55 °C 25 A
(440 V) 55 °C 16 A
(500 V) 55 °C 14 A
(690 V) 55 °C 10 A
Rated Operational Power AC-3 (Pe)(220 / 230 / 240 V) 6.5 kW
(380 / 400 V) 11 kW
(415 V) 11 kW
(440 V) 9 kW
(500 V) 9 kW
(690 V) 9 kW
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 690 V
Write Your Own Review
You're reviewing:AX25-30-01-80 220-230V50Hz/230-240V60Hz Contactor
Your Rating