AF09-30-10-11 24-60V50/60HZ 20-60VDC Contactor

ABB
SKU
AB_1SBL137001R1110
Model
AF09-30-10-11
SGD $20.47

Short description of AF09 30 10 11

AF09-30-10-11 24-60V50/60HZ 20-60VDC Contactor
Country of Origin
France (FR)
-
+

UOM: Piece

In stock
In Stock 236
Backorder Leadtime: 2 To 4 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
The AF09-30-10-11 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
MAIN SPECIFICATION
ABB Global IDABB1SBL137001R1110
Business Area (Master Data) NameElectrification
Catalog DescriptionAF09-30-10-11 24-60V50/60HZ 20-60VDC Contactor
Division (Master Data) NameSmart Power
EAN3471523110014
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 volt
acc. to UL/CSA 600 volt
SKU ID1SBL137001R1110
TECHNICAL
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 6 mm²
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Rated Operational Current AC-15 (Ie)(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Short-time Withstand Current (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
StandardsIEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Terminal TypeScrew Terminals
Wire Stripping LengthAuxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
TECHNICAL UL/CSA
General Use Rating UL/CSA(600 V AC) 25 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 3/4 hp
(200 ... 208 V AC) Three Phase 2 hp
(220 ... 240 V AC) Three Phase 2 hp
(240 V AC) Single Phase 1-1/2 hp
(440 ... 480 V AC) Three Phase 5 hp
(550 ... 600 V AC) Three Phase 7-1/2 hp
Tightening Torque UL/CSAAuxiliary Circuit 11 IA
Control Circuit 11 IA
Main Circuit 13 IA
ORDERING
Minimum Order Quantity1 piece
ENVIRONMENTAL
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible3000 m
Resistance To Shock Acc. To IEC 60068-2-27Closed, Shock Direction: B1 25 K40
Open, Shock Direction: B1 5 K40
Shock Direction: A 30 K40
Shock Direction: B2 15 K40
Shock Direction: C1 25 K40
Shock Direction: C2 25 K40
Resistance To Vibrations Acc. To IEC 60068-2-65 ... 300 Hz 4 g closed position / 2 g open position
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
E-Number (Finland)3705800
E-Number (Sweden)3210016
EClassV11.0 : 27371003
ETIM 4EC000066 - Magnet contactor, AC-switching
ETIM 5EC000066 - Magnet contactor, AC-switching
ETIM 6EC000066 - Power contactor, AC switching
ETIM 7EC000066 - Power contactor, AC switching
Object Classification CodeQ
OTHER
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air -40 ... +70 °C
Degree Of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Number Of Auxiliary Contacts NO1
Number Of Main Contacts NO3
Product Net Width45
Rated Control Circuit Voltage (Uc)50 Hz 24 ... 60 V
50 Hz / 60 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Rated Impulse Withstand Voltage (Uimp)6 kilovolt
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 25 No unit
(690 V) 60 °C 25 ampere
(690 V) 70 °C 22 No unit
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Power AC-3 (Pe)(400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 690 V
Write Your Own Review