
1SAZ321201R2005 - TA75DU-63M Thermal Overload Relays
ABB
SKU
AB_1SAZ321201R2005
Model
TA75DU-63M
SGD $75.59 All prices inclusive of GST
Get 10% OFF, apply code: ABB10OFF
Min. spend $100
Min. spend $100
Short description of TA75DU 63M
Catalog No: 1SAZ321201R2005
TA75DU-63M Thermal Overload Relays
TA75DU-63M Thermal Overload Relays
Country of Origin
Bulgaria (BG)
TA75DU-63M (45.0-63.0A) thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10A. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SAZ321201R2005 |
Business Area (Master Data) Name | Electrification |
Catalog Description | TA75DU-63M Thermal overload relay Trip class 10A, 45.0-63.0A |
Division (Master Data) Name | Smart Power |
EAN | 4013614482663 |
Rated Operation Current | 63 ampere |
SKU ID | 1SAZ321201R2005 |
TECHNICAL | |
Connecting Capacity Auxiliary Circuit | Flexible 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 0.75 ... 4 mm² |
Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit NC 5 A Auxiliary Circuit NO 5 A |
Power Loss | at Rated Operating Conditions per Pole 1.9 W |
Rated Operational Current (Ie) | 63 A |
Recommended Screw Driver | Auxiliary Circuit Pozidriv 1 Main Circuit Pozidriv 2 |
Standards | CSA 22.2 No. 14 IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 508 |
Wire Stripping Length | Auxiliary Circuit 9 mm Main Circuit 14 mm |
TECHNICAL UL/CSA | |
Ampere Rating UL/CSA | 63 A |
Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-14 AWG Stranded 1/2x 18-14 AWG |
Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 8-1 AWG Stranded 1/2x 8-1 AWG |
Contact Rating UL/CSA | (NC:) B600 (NO:) C600 |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
Tightening Torque UL/CSA | Auxiliary Circuit 12 in·lb Main Circuit 40 in·lb |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
Resistance To Shock Acc. To IEC 60068-2-27 | 11 ms Pulse 12g |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
E-Number (Finland) | 3707437 |
EClass | V11.0 : 27371501 |
ETIM 5 | EC000106 - Thermal overload relay |
ETIM 6 | EC000106 - Thermal overload relay |
ETIM 7 | EC000106 - Thermal overload relay |
IDEA Granular Category Code (IGCC) | 5364 >> Overload relay |
UNSPSC | 39121520 |
OTHER | |
Ambient Air Temperature | Operation -25 ... +55 °C Operation Compensated -25 ... +55 °C Storage -40 ... +70 °C |
Degree Of Protection | Housing IP20 Main Circuit Terminals IP20 |
Product Net Width | 54 |
Suitable For | AX50 AX65 AX80 |
Write Your Own Review