Harmony, Modular 1-phase Current Control Relay, 5 A, 2 CO, 0.15…15 A,, 24…240 V AC/DC

Schneider
SKU
SE_RM35JA32MR
Model
RM35JA32MR
SGD $118.16

Short description of RM35JA32MR

CURRENT CONTROL RELAY RM35-JA - RANGE 0,
Country of Origin
Indonesia
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 2 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
Current control relay 0.15A…15A, 2 C/O.
Label :  Zelio Control
-  range of product :  Zelio Control
-  switching capacity in VA :  2000 VA
-  product or component type :  modular measurement and control relays
-  measurement range :  0.15...1.5 A E1-M terminals, 0.5...5 A E2-M terminals, 1.5...15 A E3-M terminals, 150 mA...15 A current AC/DC 50/60 Hz
-  relay type :  current control relay
-  relay name :  RM35JA
-  relay monitored parameters :  overcurrent or undercurrent in window mode,overcurrent or undercurrent detection
-  time delay type :  adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
-  Range Presentation :  They can monitor power supplies (phases, voltage, current, frequency) to protect motors and other equipment or control physical values such as level, speed and temperature.

-  Phase control relay Detects all possible faults occurring in the phases
-  Voltage & current control relays Ensure your equipment is powered with proper values
-  Frequency control relay Monitors frequency variation from your power generation set
-  Level control relay Filling or emptying, adapts to all kinds of materials
-  Pump control relay Controls and protects your pump from dry running or overloading
-  Speed control relay Picks up the improper rhythm of your process
-  Temperature control relay for lift application Dedicated to lift temperature monitoring (EN81)
-  Temperature control relays Dedicated to temperature regulation (heating, cooling or heating/cooling of processes)
-  Range Benefits :  Monitoring of your equipmentSimple and accurate adjustments are a sure-fire way to achieve quick and easy setup. These relays can satisfy all the monitoring requirements of mobile process control or network equipment.
-  Range Application Presentation : 

-  Industry and domestic :  switchboards in simple machines, motors and process monitoring
-  Start-up and monitoring of water treatment equipment
-  Packaging, textile, HVAC
MAIN SPECIFICATIONS
Analogue Input Number24...240 V AC/DC 50/60 Hz +/- 10 %
Contacts Type And Composition2 C/O
Discrete Input Number2 C/O
Product Or Component Typecurrent control relay
Range Of ProductHarmony Control Relays
[Uc] Control Circuit Voltage24...240 V
EAN133606480792304
Measurement Range0.15...1.5 A E1-M terminals
0.5...5 A E2-M terminals
1.5...15 A E3-M terminals
150 mA...15 A current AC/DC 50/60 Hz
Mounting Support35 mm DIN rail conforming to EN/IEC 60715
Range NameZelio Control
Relay Monitored Parametersovercurrent or undercurrent detection
overcurrent or undercurrent in window mode
Relay NameRM35JA
Relay Typecurrent control relay
Time Delay Typeadjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
Utilisation CategoryAC-1 conforming to IEC 60947-4-1
AC-15 conforming to IEC 60947-5-1
DC-1 conforming to IEC 60947-4-1
DC-13 conforming to IEC 60947-5-1
COMPLEMENTARY
Output Contacts2 C/O
System Requirements2 C/O
[In] Rated Current8 A
Compatibility CodeRM3
Connections - Terminalsscrew terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
screw connectors
Contacts Materialcadmium free
Control Circuit Voltage Limits- 15 % + 10 % Un
Electrical Durability100000 cycles
Functionalityovercurrent or undercurrent detection
Housing Materialself-extinguishing plastic
Hysteresis3-3 % fixed of full scale for window mode
5-50 % adjustable of threshold setting for overcurrent or undercurrent detection
Immunity To Microbreaks50 ms
Insulationbetween supply and measurement
Insulation Resistance> 100 MOhm at 500 V DC conforming to IEC 60255-27
Internal Input Resistance0.005 Ohm
0.015 Ohm
0.05 Ohm
Maximum Measuring Cycle100 ms measurement cycle as true rms value
Maximum Power Consumption In W1.5 W DC
Maximum Switching Current8 A AC
Maximum Switching Voltage250 V AC
Measurement Error< 1 % over the whole range with voltage variation
0.05 %/°C with temperature variation
Mechanical Durability10000000 cycles
Minimum Switching Current10 mA at 5 V DC
Mounting Positionany position
Net Weight0.12 kg
Nominal Output Current8 A
Power Consumption In VA3.5-3.5 VA AC
Repeat Accuracy+/- 0.5 % for input and measurement circuit
+/- 2 % for time delay
Reset Time1500 ms at maximum voltage
Resistance Across Terminals0.005 Ohm at E3-M terminals
0.015 Ohm at E2-M terminals
0.05 Ohm at E1-M terminals
Response Time<= 500 ms (on crossing the threshold)
Run-up Delay At Power-up0.3 s
Safety Reliability DataB10d = 270000
MTTFd = 296.8 years
Setting Accuracy Of The Switching Threshold+/- 10 % of the full scale
Setting Accuracy Of Time Delay10 P
Status LEDLED (green)power ON
LED (yellow)relay ON
Supply Voltage Limits20.4-264 V AC/DC
Switching Capacity In VA2000 VA
Switching Threshold Drift<= 0.05 % per degree centigrade depending permissible ambient air temperature
<= 1 % within the supply voltage range
Threshold Setting10...100 %
Tightening Torque0.6-1 N.m conforming to IEC 60947-1
Time Delay Drift<= 0.05 % per degree centigrade depending permissible ambient air temperature
<= 1 % within the supply voltage range
Width35 mm
ENVIRONMENT
Ambient Air Temperature For Operation-20-50 °C at 60 Hz
-20-60 °C at 50 Hz AC/DC
Ambient Air Temperature For Storage-40-70 °C
Dielectric Test Voltage2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Electromagnetic Compatibilityconducted and radiated emissions class B conforming to CISPR 22
conducted and radiated emissions class B group 1 conforming to CISPR 11
electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4
electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4
electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
emission standard for industrial environments conforming to EN/IEC 61000-6-4
emission standard for residential, commercial and light-industrial environments (except radiated emission) conforming to EN/IEC 61000-6-3
immunity for industrial environments conforming to EN/IEC 61000-6-2
immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3
surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5
surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5
Environmental Characteristic3K3 C
IP Degree Of ProtectionIP20 (terminals) conforming to IEC 60529
IP30 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Overvoltage CategoryIII conforming to IEC 60664-1
III conforming to UL 508
Pollution Degree3 conforming to IEC 60664-1
3 conforming to UL 508
Product CertificationsCCC
CE
CSA
EAC
GL
RCM
UL
Relative Humidity93-97 % at 25-55 °C conforming to IEC 60068-2-30
Shock Resistance15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
StandardsEN/IEC 60255-1
Vibration Resistance0.035 mm (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6
0.075 mm (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6
0.5 gn (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6
1 gn (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6
OTHER
Poles Descriptioncurrent control relay
[Us] Rated Supply Voltage24...240 V AC/DC 50/60 Hz +/- 10 %
Write Your Own Review
You're reviewing:Harmony, Modular 1-phase Current Control Relay, 5 A, 2 CO, 0.15…15 A,, 24…240 V AC/DC
Your Rating